A6V10424583 2 - and 3-Port Valves With BR Flanged Connections en
A6V10424583 2 - and 3-Port Valves With BR Flanged Connections en
Type summary
Stroke 20 mm 40 mm
Stock no. DN kvs Sv Δps Δpmax Δps Δpmax Δps Δpmax Δps Δpmax Δps Δpm
-10…150 °C [m3/h] ax
[kPa]
VVF42.15-1.6 S55204-V100 15 1.6 > 50 1600 400 1600 400 1600 400 - - - -
VVF42.15-4 S55204-V102 15 4
VVF42.25-10 S55204-V105 25 10
VVF42.40-25 S55204-V108 40 25
VVF42.50-40 S55204-V110 50 40
VVF42.65-63 S55204-V112 65 63
-5…150 °C
2
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
VVF42.80-100K S55204-V123 80 100
Stroke 20 mm 40 mm
VXF42.15-1.6 S55204-V127 15 1.6 > 50 400 100 400 100 400 100 - - - -
VXF42.15-4 S55204-V129 15 4
VXF42.25-10 S55204-V132 25 10
VXF42.40-25 S55204-V135 40 25
VXF42.50-40 S55204-V137 50 40
VXF42.65-63 S55204-V139 65 63
1)
Maximum permissible media temperature in all installation positions 130°C.
2)
Maximum permissible media temperature 130°C. In horizontal installation position 150°C .
DN = Nominal size
kvs = Flow nominal value of cold water (5...30 °C) through the fully opened valve (H 100) bat a differential
pressure of 100 kPa (1 bar)
3
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
Sv = Rangeability
∆ps = Maximum permissible differential pressure at which the motorized valve still closes securely against the
pressure
∆pma = Maximum permissible differential pressure across the valve’s throughport for the entire positioning range
x of the motorized valve
Ordering (example)
Delivery
Valves, actuators, and accessories are packaged and delivered separately.
Note
Counter-flanges, bolts, and gaskets must be provided on site.
Equipment combinations
Type Stock no. Stroke Positioni Operating Positionin Spring Positioning LED Manual Auxiliary
ng force voltage g signal return time adjuster function
time s
1)
SAX31.00 S55150-A105 20 mm 800 N AC 230 V 3-position - 120 s - Press
and fix
SAX31.03 S55150-A106 30 s
SAX81.03 S55150-A103 30 s
SAX81.03U S55150-A103-
A100
1)
SKD32.21 SKD32.21 20 mm 1000 N AC 230 V 3-position 8s Opening: - Turn,
30 s position
Closing: is
10 s maintain
ed
SKD32.50 SKD32.50 - 120 s
SKD32.51 SKD32.51 8s
4…20 mA 30 s
SKD62 SKD62 15 s Closing:
0…1000 Ω
SKD62U SKD62U 15 s
4)
SKD62UA SKD62UA
1)
SKD82.50 SKD82.50 3-position - 120 s -
SKD82.50U SKD82.50U
SKD82.51 SKD82.51 8s
SKD82.51U SKD82.51U
1)
SKB32.50 SKB32.50 20 mm 2800 N AC 230 V 3-position - 120 s - Turn,
4
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
Type Stock no. Stroke Positioni Operating Positionin Spring Positioning LED Manual Auxiliary
ng force voltage g signal return time adjuster function
time s
4…20 mA 120 s ed
SKB62 SKB62 10 s Closing:
0…1000 Ω
SKB62U SKB62U 10 s
4)
SKB62UA SKB62UA
1)
SKB82.50 SKB82.50 3-position - 120 s -
SKB82.50U SKB82.50U
SKB82.51U SKB82.51 10 s
SKB82.51 SKB82.51U
1) 5)
SAV31.00 S55150-A112 40 mm 1600 N AC 230 V 3-position - 120 s - Press ,
and fix
SAV61.00 S55150-A110 AC 24 V 0…10 V x 1) 2) 5) 6)
, , ,
SAV61.00U S55150-A110- DC 24 V 4…20 mA
A100
0…1000 Ω
1) 5)
SAV81.00 S55150-A111 3-position - ,
SAV81.00U S55150-A111-
A100
1)
SKC32.60 SKC32.60 40 mm 2800 N AC 230 V 3-position - 120 s - Turn,
position
SKC32.61 SKC32.61 18 s is
maintain
SKC60 SKC60 AC 24 V 0…10 V - Opening: x ed
2)
4…20 mA 120 s
SKC62 SKC62 20 s Closing:
0…1000 Ω
SKC62U SKC62U 20 s
4)
SKC62UA SKC62UA
1)
SKC82.60 SKC82.60 3-position - 120 s -
SKC82.60U SKC82.60U
SKC82.61 SKC82.61 18 s
SKC82.61U SKC82.61U
1)
Auxiliary switch, potentiometer
2)
Position feedback, forced control, selection of valve characteristic
3)
Optional: sequence control, selection of acting direction
4)
Plus sequence control, stroke limitation, selection of acting direction
5)
Stem heating element (optional)
6)
Function module (optional)
Accessories
5
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
Spare parts
4 284 8806 0
4 679 5629 0
Product documentation
6
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
2-port valves
Fluids
Fluids
Note 2-port valves do not become 3-port valves by removing the blank flange!
7
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
3-port valves
Fluids
8
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
Sizing
Flow chart
0,01
0,02
0,03
0,04
0,05
0,06
0,08
0,1
0,2
0,3
0,4
0,5
0,6
0,8
1,5
10
15
20
30
1
2
3
4
5
6
8
3000 800
2000 600
500
1500 400
1000 300
250
800 200
600 150
500
400 100
300 80
200 k VS 60
360 50
150 400 40
315 250
100 30
25
80 200 160
20
60 15
50 125 100
40 10
30 80 63
8
20 50 40
6
5
4
5 25
31. 3
10 2,5
8 16 2
6 1,5
5 10
4 1
3 6.3 0,8
2 4 0,6
0,5
0,4
2.5
1 0,3
1.6 0,25
0,8
0,2
0,6
0,5 0,15
0,4
0,1
0,3 0,08
0,2 0,06
0,05
0,04
0,1 0,03
0,025
0,08
0,02
0,06
0,05 0,015
0,04
0,01
0,03 0,008
0,02 0,006
1
10
100
1000
4
3
6
8
20
30
40
50
60
80
200
300
400
500
600
800
1500
2000
3000
5
Δpmax values apply for the mixing function. Δpmax values for diverting function, see "Type
summary", page 2 [▶ 2].
Valve characteristics
2-port
valves 0…30 %: Linear
9
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
ngl = 3 to VDI / VDE 2173
3-port valves
Throughport A-AB
0...30 %: Linear
Bypass B-AB
0...100 %: Linear
Bypass B-AB
0...100%: Linear
10
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
Operating
pressure
and medium
temperature
Fluids, PN16
with V..F42..
Operating pressure and operating temperatures according to ISO 7005, EN 1092, and
EN 12284
Cold water 1 25 x x x -
150 180 - - - -
Cooling water 2) 1 25 - - - -
11
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
1)
Differentiation due to saturated steam curve
2)
Open circuits
3)
VVF42..K valves cannot be used with media below -5 °C due to the compensation sealing material.
Fields of use
Fields of use Type
Refrigeration plants x x x
Notes
Engineering
Mounting location
Preferably mount the valves at the return, as the temperature is lower there and the strain on
the stem sealing gland is lower.
Dirt trap
Mount a dirt filter or dirt trap before the valve to ensure the proper functioning and long
service life of the valve. Remove dirt, welding beads, etc. from the valves and pipes.
Cavitation
Cavitation can be avoided by limiting the pressure differential across the valve depending on
the medium temperature and prepressure.
Mounting
Mounting position
Indoors Outdoors
12
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
Mounting positions apply to both 2- and 3-port valves.
Commissioning
The valve may be put into operation only if actuator and valve are correctly
assembled.
Note Ensure that the actuator stem and valve stem are rigidly connected in all positions.
Function check
Maintenance
The valves are equipped with maintenance-free, continuously lubricated stem sealing
glands. See Accessories / Spare parts [▶ 5] for replacement stem sealing glands.
CAUTION
When servicing valves or actuators:
• Deactivate the pump and turn off the power supply.
• Close the shutoff valves.
• Fully reduce the pressure in the piping system and allow pipes to completely cool down.
If necessary, disconnect the electrical wires.
Disposal
Warranty
Application-related technical data are guaranteed only when the valves are used in
connection with the Siemens actuators listed under "Type summary" and "Equipment
combinations". When used with actuators of other manufacture, any warranty by Siemens
becomes void.
13
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
Technical data
Functional data
PN class PN 16
Connection Flange
VVF42..K -5…150 °C
Rangeability To DN 25 > 50
From DN 32 >100
Nominal stroke To DN 80 20 mm
From DN 100 40 mm
Materials
Seat Machined
Fluid group 2: PN 16
14
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
Standards, directives and approvals
2)
section 3 (sound engineering practice)
Environmental conditions
Class 1K3
Temperature -15…55 °C
Temperature -30…65 °C
Temperature -15…+5 °C
Environmental compatibility
The product environmental declarations CE1E4403en01 3), CE1E4403en02 3) und CE1E4403en03 3) contain data
on environmentally compatible product design and assessments (RoHS compliance, materials composition,
packaging, environmental benefit, disposal).
Dimensions / Weight
15
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
1)
For certain valve lines and high k vs values, the valve characteristic is optimized for maximum volumetric flow
kV100.
2)
Valves where PS x DN < 1000 do not require special testing and cannot carry the CE label.
3)
The documents can be downloaded from http://www.siemens.com/bt/download.
16
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
Dimensions
VVF42..
VVF42..K
A AB
4030M10
Type DN kg B D D1 D2 L1 L2 X Y K H1 H2 H
25 5.4 15 115 65 14 (4x) 160 106.5 94.4 90.1 85 37 133.5 479 537 612 - -
32 8.4 17 140 76 19 (4x) 180 119 115.6 110.7 100 37 133.5 479 537 612 - -
40 9.3 16 150 84 19 (4x) 200 126 123.2 117.8 110 37 133.5 479 537 612 502 -
50 12.2 16 165 99 19 (4x) 230 144 135.2 128.4 125 50 146.5 492 550 625 525 -
65 17 17 185 118 19 (4x) 290 174 150 142.5 145 75 171.5 517 575 650 540 -
80 25 17 200 132 19 (8x) 310 186 - - 160 75 171.5 517 575 650 540 -
100 35.9 17 220 156 19 (8x) 350 205 - - 180 110 226.5 - - - 575 685
125 52.5 17 250 184 19 (8x) 400 233 - - 210 123 239.5 - - - 588 698
150 74.9 17 284 211 23 (8x) 480 275.5 - - 240 150.5 267 - - - 616 726
VVF42..K 50 12 16 165 99 19 (4x) 230 144 135.2 128.4 125 50 146.5 492 550 625 - -
65 17.7 17 185 118 19 (4x) 290 174 150 142.5 145 75 171.5 517 575 650 - -
80 26.8 17 200 132 19 (8x) 310 186 - - 160 75 171.5 517 575 650 - -
100 35.3 17 220 156 19 (8x) 350 206 - - 180 110 226.5 - - - 575 685
17
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
VXF42..
Type DN kg B D D1 D2 D3 1) L1 L2 X Y K H1 H2 H
25 3.8 15 115 65 14 (4x) 36 160 80 94.4 90.1 85 37 133.5 479 537 612 - -
32 5.7 17 140 76 19 (4x) 46 180 90 115.6 110. 100 37 133.5 479 537 612 - -
7
40 6.3 16 150 84 19 (4x) 56 200 100 123.2 117. 110 37 133.5 479 537 612 502 -
8
50 8.7 16 165 99 19 (4x) 69 230 115 135.2 128. 125 50 146.5 492 550 625 525 -
4
65 12.9 17 185 118 19 (4x) 85 290 150 150 142. 145 75 171.5 517 575 650 540 -
5
80 19.2 17 200 132 19 (8x) 102 310 155 - - 160 75 171.5 517 575 650 540 -
100 29 17 220 156 19 (8x) 124 350 175 - - 180 110 226.5 - - - 575 685
1)
Interior opening of the bypass port
Revision numbers
Type Valid from rev. no. Type Valid from rev. no.
18
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
Type Valid from rev. no. Type Valid from rev. no.
VVF42.50-40K ..B
VVF42.65-63K ..A
VVF42.80-100K ..A
VVF42.100-160K ..B
VVF42.125-250K ..B
VVF42.150-360K ..B
19
Siemens CE1N4403en
Smart Infrastructure 2024-04-09
Issued by
© Siemens 2013
Siemens Switzerland Ltd
Technical specifications and availability subject to change without notice.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies
Document ID CE1N4403en
Edition 2024-04-09