Experion PKS R431 1 Support Software Media Software Change Notice SCN EPDOC-X175-En-431
Experion PKS R431 1 Support Software Media Software Change Notice SCN EPDOC-X175-En-431
EPDOC-X175-en-4311A
February 2015
Release 431.1
Document Release Issue Date
EPDOC-X175-en-4311A 431.1 0 February 2015
Disclaimer
This document contains Honeywell proprietary information. Information contained herein is to be used solely
for the purpose submitted, and no part of this document or its contents shall be reproduced, published, or
disclosed to a third party without the express permission of Honeywell International Sàrl.
While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied
warranties of merchantability and fitness for a purpose and makes no express warranties except as may be stated
in its written agreement with and for its customer.
In no event is Honeywell liable to anyone for any direct, special, or consequential damages. The information
and specifications in this document are subject to change without notice.
Copyright 2015 - Honeywell International Sàrl
2 www.honeywell.com
Contents
1 Introduction ............................................................................................................................................ 5
1.1 About this document ........................................................................................................................................... 6
1.1.1 Revision history ................................................................................................................................... 6
1.2 Check for updates on Honeywell Process Solutions website ............................................................................. 7
2 Issues ...................................................................................................................................................... 9
2.1 .......................................................................................................................................................................... 10
2.2 .......................................................................................................................................................................... 16
2.3 .......................................................................................................................................................................... 50
2.4 .......................................................................................................................................................................... 51
3 Notices .................................................................................................................................................. 53
3.1 Documentation feedback .................................................................................................................................. 54
3.2 How to report a security vulnerability .............................................................................................................. 55
3.3 Support .............................................................................................................................................................. 56
3.4 Training classes ................................................................................................................................................. 57
3
CONTENTS
4 www.honeywell.com
1 Introduction
Note
Known Issues are covered in this SCN, for other information refer to the Experion R431 General Release SCN.
Related topics
“About this document” on page 6
“Check for updates on Honeywell Process Solutions website” on page 7
5
1 INTRODUCTION
6 www.honeywell.com
1 INTRODUCTION
4 Click the document, security update, or antivirus notification link to open it.
7
1 INTRODUCTION
8 www.honeywell.com
2 Issues
This chapter provides the information about the Experion issues and workarounds.
Attention
Experion PKS R431.1 Support Software Media Software Change Notice reflects only Product Anomaly Reports
(PARs) with priority severity position 2.1 and above.
The PARs positioned at 2.2 and below are not included in this Software Change Notice.
Related topics
page 10
page 16
page 50
page 51
9
2 ISSUES
2.1
PAR Description
1-DLHZ3R Error Indication: LCNP4 board not loading occasionally.
Description: Occasionally it is observed that after the pc restart/LCNP Reset,
emulators refuse to load the board.
Recovery: Perform the following steps.
1. From the Start menu select Settings/Control Panel/ Administrative Tools.
Select Services in the Services window, scroll down to TDC Emulators
Service. Right click TDC Emulators Service and select stop option. Once
the service is in stopped state Right click and select start option. Afte the
TDC Emulators Service Stop/Start, reset the LCNP board by selecting the
LCNP Reset option from the Start Menu->All Programs-> Honeywell
Experion PKS-> TPS Applications-> LCNP Status dialog.
2. Load the TPS\EPKS node which is stuck up in POWER_ON state from
another GUS/EST/US node in the same LCN.
Workaround: None.
OPC Gateway
PAR Description
1-2GZIVP6 Error Indication: Data values coming from the OPC Gateway may freeze based
on incorrect OPC Server function.
Description: Once the OPC Gateway subscribes to an OPC Server for a data
value, it is unable to detect if the OPC Server has stopped updating this point
correctly. This can be visible where the data is seen to be "frozen" coming from
the OPC Gateway but a new connection to the OPC Server by another client can
get correct "live" data.
Recovery: The OPC Gateway is unable to recover only a single data value. If an
OPC Server stops updating one of the points to the OPC Gateway one of two
actions can be taken. (1) (2)
1. Remove all requests for this point by clients of the OPC Gateway. This
requires unloading these points from Monitor.
2. Set the OPC Gateway to IDLE. This will result in the connection to the OPC
Server being closed and ALL DATA from the OPC Gateway will go to
Failsafe values. Commanding the OPC Gateway to RUN will restore all data
from all points coming from the OPC Gateway.
Workaround: None.
10 www.honeywell.com
2 ISSUES
PAR Description
Error Indication: Experion nodes stop communicating and/or deployment of
secure communications policies fail after a re-synchronize command.
Description: This outcome is possible if the configuration information of a
restored Security Manager does not match or is incompatibly different than the
secure communication policies deployed and operating in the system.
Recovery: Modify secure communications configuration to restore system
communications. The changes to be made are dependent on which nodes have
lost communication and whether the nodes are currently secured or not.
Workaround: First, always backup the Security Manager after secure
communications configuration changes, so that subsequent restores of the
Security Manager will always match what has been deployed to the system.
Secondly, before using the Reysnchronize command, carefully evaluate the
configuration to be deployed vs the current system to decide if the command
should be executed. See the Secure Communications User Guide for additional
information on backup/restore considerations and use of the re-synchronize
1-1TRB5UD command.
Error Indication: Hardware replacement of the ESV node designated as
Security Manager with no backup or unusable backup results in a loss of Secure
Communications configuration data.
Description: If the Security Manager node is replaced and a backup of the
Secure Communications configuration (through EBR or other means) was not
taken or cannot be restored, the configuration data is effectively lost and Secured
nodes can no longer be managed through the Secure Communications tool.
Recovery: Recovering the Secured nodes requires clearing their individual
Secure Communications configuration and re-configuring the Secure
Communications system. Please refer to the "Secure Communications User's
Guide", Section "Node Maintenance" - Scenario "Restoring Security Manager
without a valid backup".
Workaround: Plan regular backups of the Security Manager node. Recommend
taking a backup of the Security Manager node and its Secure Communications
configuration whenever a new node has been Secured or an already Secured node
1-289JLQB has been Unassigned / removed.
11
2 ISSUES
PAR Description
1-3JXC9T1 Error Indication: Secured, redundant Experion Servers with ServerB as primary
and ServerA as backup, ServerA is rebooted and ends up taking over as primary.
Description: This can occur when ServerA is started after reboot. Server A may
timeout waiting for communications with Server B to be established before the
IPSec negotiation succeeds, which can be up to 2minutes. ServerA will assume a
primary role, resulting in dual primary Servers. Once the IPsec negotiation
succeeds the Servers will start communicating and Server B will step down to the
backup role knowing that ServerA is the preferred primary.
Recovery: None needed if ServerA in primary role and ServerB in backup role is
ok. If ServerB needs to be in the primary role, then command a Server swap.
Workaround: Take secured Experion Server pairs out of Secure
Communications before staring critical operations that will cause a reboot, such
as an Experion migration or Windows patch update. After the operation is
completed, the Experion Sever pair can then be re-secured. From the Secure
Communications user interface, nodes are taken out of Secure Communications
by Unassigning them from the Secured Nodes list, and nodes are added to Secure
Communications by Securing them from the Unassigned Nodes list.
Furthermore, when it is known in advance that the system is expecting to be
running Server B as primary and Server A is likely to have a period where it may
not be able to communicate with Server B, additional action is recommended to
ensure that when communications are re-established, ServerA will not elevate to
a primary role. Follow the instructions documented (associated with PAR
1-2TXBDD5) to stop and disable the Experion System service on Server A
before doing the critical operation, and subsequent restart and enable of the
service after the operation is completed.
1-288O73J Error Indication: C300 remain "updating" in Secure Communications UI;
policies are not applied
Description: After un-assigning a Security Manager proxy from the Secure
Communications UI, any nodes communicating with the Security Manager
through that proxy will no longer receive policy updates.
Recovery: Secure the removed proxy node
Workaround: To prevent this situation do not un-assign proxy nodes or ensure
all BOOTP servers point to one proxy node. See the Secure Communications
User Guide for further information.
1-1XVYCPZ Error Indication: C300 temporarily lose communication with console stations
during policy deployment.
Description: When securing a large number of Windows and C300 nodes at
once, C300 has been observed to temporarily lose communication with consoles
stations in the same security zone.
Recovery: Not required, communication restores automatically.
Workaround: Refer to the Secure Communications User Guide for the
recommended procedure to secure nodes. In addition, securing nodes in several
parts (for example 10-15 nodes at a time) vs all at once will further increase the
probability of avoiding interruptions in communication.
12 www.honeywell.com
2 ISSUES
System Management
PAR Description
1-MZ6L8J Error Indication: FTE nodes disjoin and reconnect.
Description: FTE nodes gets disjoined and reconnected when time in NTP
source is slightly modified.
Recovery: None required system automatically recovers.
Workaround: None.
1-MNAFT7 Error Indication: Server data connection is lost
Description: Server lost data connection to System management by launching
the L2.5 switch display from the station. Issue is caused by slow response from
the switch.
Recovery: Switch to another display to continue working, and retry the switch
display later.
Workaround: None
1-28CKTBT Error Indication: The memory usage for the System Management Synchronized
Repository service (SyncRep.exe) rapidly increases on multiple nodes on a
network and network utilization increases significantly. There may be system
performance impact, and the synchronization of alarms between the nodes may
be delayed. If a syncrep memory leak occurs on only a single system, it is not
this issue, and this recovery procedure does not apply.
Description This behavior has been encountered on only one network to date,
and only under the specific scenario of unplugging the current primary server
from the network, and then later plugging it in again. Warning: until there is a fix
for this issue, all sites should avoid the above scenario. Even under this specific
scenario, the frequency of occurrence of the syncrep memory leak is low.
Recovery: Contact Honeywell TAC for more information about this issue.
Workaround. The best way to avoid this problem is to avoid the specific
scenario where this has been observed . If this issue occurs even once at a site,
the following procedure is recommended in order to prevent repeated occurrence.
1. Log on to one of the systems affected using a domain administrator account.
2. Open the system management display.
3. Ensure the correct set of computers displayed is correct for your current
configuration.
4. Right-click the scope item (domain or OU) in the left pane and select
properties.
5. In the properties dialog, as the Settings Source, select one of the nodes that is
properly configured for the Synchronized Repository settings (in particular,
the multicast address)
6. In the Synchronized Repository Configurations section at the bottom of the
properties page, for each of the three selectable values for Repository Name
(TPS_ComponentInfo, TPS_SysEvt, and TPS_SysEvtExt), set the value of
Maximum Response Time (ms) to 250.
7. Click OK or Apply, which causes the Save Common Configuration dialog to
appear. This dialog will list all the nodes the above settings will apply to.
Check the list, and if any nodes are red, determine the cause, and get them
back on-line if possible, as this timing change will not be applied to nodes
that are not running, only to the nodes that have the status Connection OK.
Click the OK button to apply the changes. For each node that displays
Connection OK, the status should change to
8. Configuration information was changed successfully.
9. Once this process has completed, click the Close button.2/28/2014 12:05:37
AM.
13
2 ISSUES
PAR Description
1-1EYHNCP Error Indication: Missing Managed Component alarm in alarm summary.
Description: Sometimes the MANCOMP is not shown when a network failure
occurs (such as disconnecting one of the FTE cables).
Recovery: Restart System Event Provider.
Workaround: Same as the recovery.
System Repository
PAR Description
1-1RTR2H5 Error Indication: CDA disconnects seen when performing "Load with contents"
of a controller.
Description: CDA disconnects were seen when doing "Load with contents" of a
controller having a huge amount of heavy strategies ( 1000+ RCMs) is done on a
heavily loaded setup.
Recovery: Perform switchover of servers to recover from the CDA disconnect if
the recovery doesn't happen automatically.
Workaround: The workaround to avoid this issue is to download the strategies
under the controller in smaller chunks instead of doing a "Load with contents"
for the controller.
1-3ILK9CN Error Indication: Failed to get the parameter information from System
Repository for Parameter.
Description: Failed to get the parameter information from System Repository for
Parameter error for CEE SCADA points on reload after modifying the previous
CEE SCADA in Expressions.
Recovery: Close control builder, invoke again and load.
Workaround: None.
OPM-Upgrade Tool
PAR Description
1-3N3C5RD Error Indication: Readiness Check of C300 controllers having 500 or more
references blocks goes to Pending state2.
Description: One or more L1 or L2 node in Upgrade Tool goes to pending state
on a relatively larger system with controllers having 500 or more references
blocks . 3.
Recovery: Relaunch Upgrade Tool and follow the steps mentioned in
Workaround.
Workaround:
• After Readiness check enumeration, for the C300 which have more reference
blocks, unselect the readiness check. Are there any dangling control
connections and proceed.
• Run ECC to identify the dangling control connections.
14 www.honeywell.com
2 ISSUES
PAR Description
1-3NGCUTW Error Indication: Native Window Access level shows OPR (Operator)
irrespective of Signon Manager access.
Description: In case of a FTE connection reset (both Yellow and Green cable
Disconnect/Connect), it is observed that sometimes Native Window access level
shows OPR irrespective of the Signon Manager access level.
Recovery: None.
Workaround:
• Close the Native Window and re-open to get the correct access level.
• or
• Log-off and log-on again to the system.
15
2 ISSUES
2.2
CDA-Embedded
PAR Description
1-15CPF6R Error Indication: You notice that connection to C200E is in RED state
and all the IOs in the C200e do not give any value and display data access
of these IOs shows reverse video.
Description: On removal of Enet module the C200e connection is lost.
Recovery: There is no specific recovery mechanism for this scenario, one
way to ensure any connection loss for C200e, Enet module must be verified
if it is connected properly or not.
Workaround: None.
1-1NJX441 Error Indication: Noticed un-command shutdown ACE nodes during
stable run.
Description: This error is observed on stable system run, when ace.exe
process shuts down you try to restore the check point and activate them to
make them work properly.
Recovery: Restore check point of ACE nodes and make the controller
active.
Workaround: None.
1-NI0RKX Error Indication: Momentary failure in exchange block communication
with C300/C200E & PLC 5/PLC5550.
Description: Momentary failure in exchange blocks communication with
C300/C200E & PLC 5/PLC5550 observed while C300 connected through
ENET, C200E to PLC5 while connected through Control net, C200E
connected to PLC5550 through remote chassis.
Recovery: This error is a temporary condition and recovery happens
automatically. This error does not have any major impact on the execution.
Workaround: None.
1-QL372H Error Indication: Parent phase block displays that child activity already
exists.
Description: The phase block is out of sync with the child activity
Recovery: The child RCM will need to be executed then aborted and reset.
After this the parent Activity will take control of the child RCM. This has a
greater chance of happening on an inter cluster peer to peer configuration.
Workaround: None.
1-VI032H Error Indication: Connection will be disconnected for 7 seconds to
exchange block during C300 switch over when exchange block configured
on different FTE community.
Description: Seven seconds connection loss is observed for exchange
blocks during C300 switch over when exchange block configures on
different FTE community.
Recovery: Automatic recovery after 7 seconds.
Workaround: None.
16 www.honeywell.com
2 ISSUES
1-3OO0E8N Error Indication: LOV and LOC observed on C300 while doing
continuous switch over (Power switchover).
Description: C300 switchover by cutting down the primary controller
power, there was a LOV and LOC observed after it has switched over
about 200 times (Primary restarted 200 and Secondary restarted 200
times ). The C300 is configured with the max load as specified in the PCT
spec.
Recovery: Stop the switchover and restart the Controllers.
Workaround : None.
CDA-Server
PAR Description
1-1EE8TQT Error Indication: New devices added to the Experion network are not
detected in FDM, also any existing device removal do not dynamically get
updated in FDM.
Description: This error occurs in a scenario where dynamic loading/
unloading of device and dynamic removal/connection of devices happen.
Recovery: If its redundant software mux, you have to stop the software
mux service on primary which enables software mux to switch over to back
up . On non redundant system, you have to rebuild network after stopping
the software mux service to recover from this issue.
Workaround: None.
1-1JLODM1 Error Indication: You can notice that the connection to FIM4 fails on
Load while active operation.
Description: This error occurs in scenario where cable is disconnected
from yellow CF9 and you try to perform Load while active operation, the
load fails.
Recovery: No Recovery.
Workaround: Reconnect the Yellow UPlink cable from CF9. the
connection is restored.
1-1LSM0ZQ Error Indication: You may notice server lost data connection to CDA
after server failover from Server B to Server A.
Description: After server fail over from server B to server A, continuous
data disconnect is observed.
Recovery: Synchronize the server and do fail over to server A.
Workaround: None.
1-1U5Z8ST Error Indication: CDA Server stops responding during normal operation.
Description: pscdasrv.exe(CDA Server) terminated unexpectedly during a
stable load with ActivityCreate/Delete. This may result in loss of view
condition. The probability of this occurrence is very low.
Recovery: Manual Start of EPKS Control Data Access service.
Workaround : None.
1-SZJRS9 Error Indication: Peer to Peer between 2 SIM C300 nodes does not work.
Description: After rebooting the SIM node and checkpoint restore, it is
observed that Peer to Peer between 2 SIM C300 nodes does not work.
Recovery: Restart the Primary Server.
Workaround: None.
17
2 ISSUES
1-WCPMRX Error Indication: Console CDA crashed after deleting OPCG & ICG.
Description : CDA on console station crashed, after deleting OPCG and
ICG. This may result in loss of view condition. The probability of this
occurrence is very low.
Recovery : Manual Start of EPKS Control Data Access service.
Workaround : None.
1-Y3OQTM Error Indication: You may see reverse videos on Display and may view
loss of trend values.
Description: During normal operation, the servers may lose view to the L1
network in a situation where an unresponsive component exists around
CDA Server. This may be because of a faulty device, too high
communication load. This may result in a loss of view condition.
Recovery: Remove the device/node that causes unresponsiveness or
reduces the communication load to be within spec. Stop/Restart EPKS
Control Data Access service.
Workaround: None.
PAR Description
1-MXX9XL Error Indication: CDAsp on a SIM node stops responding if there are 10
or more SIM nodes configured on a single SIM node and all of them have a
p2p reference to Safety Manager.
Description: During loading CM's to SIM nodes which have a p2p
configured to Safety Manager, cdasp on the SIM node might crash if there
are 10 or more SIM nodes are created on the same node.
Recovery: none
Workaround: Do not configure 10 or more SIM nodes on a single
machine and all initiating
1-N2IKQ7 Error Indication: You may see reverse videos on display and may observe
loss of trend values.
Description: During normal operation, the servers may lose view from the
controllers under very high communication load situation. This may result
in a loss of view condition.
Recovery: Manual. Stop/Restart of EPKS Control Data Access service.
Workaround: None.
1-NE4TG3 Error Indication: Loss of View observed or Server failover is observed.
Description: If for any reason, the primary CF9 loses power and switches
over to the partner CF9, you may notice Loss of View to the controllers in
the cluster. In case of redundant Servers, you may notice that Server has
failed over.
Recovery: For non-Redundant Servers, restart the Control Data Access
Server service manually if not already running. For Redundant Server
setup, if Server has failed over, go over to the old Primary and restart the
Control Data Access Server service manually if not already running.
Workaround: None.
18 www.honeywell.com
2 ISSUES
1-P9OBD9 Error Indication: The Server may lose data connection to the Controller
and result in LOV.
Description: If there are multiple controllers switching over
simultaneously, this will cause a burst of alarms to be regenerated which
may affect the data connection to the controllers that are not switching
over.
Recovery: Automatically recovers after few seconds
Workaround: None.
1-UNZ125 Error Indication: None.
Description: Removal of cable from QCS node will not be detected in
Experion station.
Recovery: Since this feature is not supported there is no specific recovery
mechanism. When you detect that the values do not get updated in QCS,
one way to recover is manual verification of the cables, ensure that the
cables are connected and working.
Workaround: None.
1-VK9U47 Error Indication: LOV observed and controller status shows red in
control builder.
Description: You may see reverse video for display data access, and
controller status shows red in Control Builder.
Recovery: Switchover the Server A where this issue is observed or you
must start the CDA server manually in case of permanent LOV observed.
Workaround: None.
C300 Controller
PAR Description
1-OBTIOP Error Indication: In Control Builder, C300 block is red but CEE block is
green. platform block parameters are not available.
Description: A network loop, possibly between two CF9s, is creating
excessive traffic, resulting in high CPU load, CEE/control parameter access
is given higher priority.
Recovery: Remove loop. May have to switchover or power cycle the
affected module.
Workaround: When performing network maintenance, be careful to not
connect cables between switches, especially CF9s, that create a network
loop.
1-OF7R1R Error Indication: Different communications are observed after powering
up a C300 controller.
Discription: Experion embedded nodes when powered up may not
properly detect duplicate IP Addresses. They will attempt to join the
network, and this willo disrupt communications with the other already-
running node(s). However, the FTE Status Display will correctly report
duplicate device index.
Workaround: Keep a record of assigned addresses to avoid duplicates..
Verify through the FTE status display that the intended device index is free.
Recovery: change the device index on the newly powered node and reboot/
power cycle it.
19
2 ISSUES
CEE-Database
Control Builder-Fieldbus
PAR Description
1-107BU07 Error Indication: EPKS is unable to differentiate the case-sensitive units
like mpa & Mpa, Mg & mg.
Description: Experion displays selected units as Mpa and value is process
with unit mpa. Same is the case with other units which differs with case-
sensitive.
Recovery: None.
Workaround: None.
1-1ZQHZDT Error Indication: "Unspecified FMS Initiate" error message is displayed
while loading CM.
Description: When you triy to make Azbil FF device as the Link Master
the error is displayed.
Recovery: Acknowledge the message and try the workaround.
Workaround: Try keeping the FIM or other devices as Link Master.
1-1ZQHZJN Error Indication: Method Manager application stops responding.
Description: Method Manager stops responding while executing "Test Key
2" method of Sensor TB block.
Recovery: Kill the process using windows task manager (or) wait until
error info is generated. Clean the database locks to continue executing other
methods.
Workaround: None.
1-MDH0OZ Error Indication: Cannot use a block from one FF link in a CM on a
different link (6L.101.10746)
Description: It was observed, CM with FF device function block assigned
to FF link is not able to re-assign to any other CEE (like C300 or ACE) of
other controllers. But other way i.e from C300 to FF link working fine. And
CM under FF link is not able to un-assign as well.
Recovery: Acknowledge the error message.
Workaround: Create a new CM in the C300 and re-assign the FF blocks.
20 www.honeywell.com
2 ISSUES
21
2 ISSUES
22 www.honeywell.com
2 ISSUES
1-3ILPKOZ Error Indication: HART channels are not displayed in the Bulk Edit list.
Description : Hart channels are not displayed in the bulk edit list. You
cannot edit the HART channel parameters.
Recovery : None.
Workaround : Use Bulk Configuration Tools->Bulk Edit work flow.
1-3JZ83JT Error Indication: Display of error message "Runtime Error R6025 - Pure
Virtual Function Call" during Bulk Edit on update Monitor of CHANNUM.
Description: The error is displayed due to an internal error that is causing
the issue. This issue is not reproducible on demand.
Recovery: Retry Bulk Edit.
Workaround: None.
1-3NHR0K1 Error Indication: "Save to ERDB failed error is displayed.
Description: If you do not specify the new channel names for the Replica
IOM in the configuration sheet, the existing channels in Typical IOM is
moved to the replica IOM.
Recovery: Reassign the channels to Typcial IOM using Bulk Edit.
Workaround: Provide new channel names in the configuration sheet so
that the new channels are created and assigned to new IOM.
1-12RNGG1 Error Indication: When you perform controller migration you will be able
to close the Configuration Studio.
Description: While performing Migration of Controllers, closing of
configuration must be restricted. Closing of Configuration studio while
performing migration of controller leads to incomplete migration of
Controllers.
Recovery: None.
Workaround: You must not close the Configuration studio during the
migration of Controller.
1-1A4KN3Z Error Indication: There are two Error indications:
1. Control Builder stops responding
2. Two different IO channels with same number
Description: Two different IO channels of same IO module are showing
same IO channel number during Series C IO channel assignment, after the
strategies exported from TP 5.4 and imported in TP 6.1. Also one of the
channel still hold the last assign channel block name even though it already
unassigned. Control builder also got crashed when we were trying to assign
any of these two channels.
Recovery: None.
Workaround: None.
1-1T9HS0S Error Indication: No Units are showing for Bearing PV in the Control
Builder.
Description: Wireless Vibration Transmitter has a vendor provided units
for Bearing PV which are not shown/supported in the Control Builder.
Recovery: None.
Workaround: For you to check the ZFS user interface understand the
configured unit for Bearing PV.
23
2 ISSUES
24 www.honeywell.com
2 ISSUES
1-Z3FUD5 Error Indication: Assigning CMs with particular CDB blocks to ACE/
C300 failing.
Description: After importing attached CM files, when trying to assign the
CM to C300/ACE it fails to assign and shows CDB not compatible with
execution environment.
Recovery: Since this happens only for particular CDB blocks, the below
compatible platforms must be added in CDB def xml file and then it can be
imported.
<CompatiblePlatform>C200</
CompatiblePlatform><CompatiblePlatform>C300</
CompatiblePlatform><CompatiblePlatform>SCE</
CompatiblePlatform><CompatiblePlatform>C200E</CompatiblePlatform>
Workaround:Add the below lines in exported CDB Block's def xml file
and then import it. Then it will allow CM to be assigned to C300.
<CompatiblePlatform>C200</
CompatiblePlatform><CompatiblePlatform>C300</
CompatiblePlatform><CompatiblePlatform>SCE</
CompatiblePlatform><CompatiblePlatform>C200E</CompatiblePlatform>
Control Builder-Batch
1-13BFFO7 Error Indication: Proxy CBR is not listed after the validation of Proxy
CBR. You cannot configure it manually.
Description: If you create and validate new Proxy CBR in local cluster (for
Newly created CBR in remote cluster), the Proxy CBR does not list in Unit
function reference point picker and it is not validated manually as well.
Recovery: Delete the proxy CBR from Control Builder and re create the
proxy CBR.
Workaround: Same as recovery.
1-WJV6I5 Error Indication: An orphan activity will be created in the orphan activity
summary display.
Description: After Terminal Stop command given to PROC layer Activity
and it finishes, UPROC layer Child activity is listed under orphan activity
summary. CEE and UPROC MR show activity associated with them too.
Recovery: Remove the orphan activity from the orphan activity summary
display. This will resolve the issue.
Workaround: None.
1-XFDMT9 Error Indication: No error displayed, The default value of new parameter
added in the phase block is not displayed in datablock.
Description: In Datablock default value is not populated for the newly
added parameter for a phase block.
Recovery: Open the PDE of phase block and deselect the Use Value
reference option and save the Phase block. then open the Datablock of
receipe. Observe that default value is displayed for newly added
parameter.then open the phase block in PDE and select the "Use value
reference" option and save the PDE
Workaround: None.
25
2 ISSUES
1-ZESYD7 Error Indication: Reverse video observed in Child RCM and Child SCM
detail display during ICPP runtime.
Description: It is observed that Parent navigation option does not exist
after navigating to Child detail display
Recovery: Go back to parent detail display through back button in Station
tool bar.
Workaround: None.
Control Builder-Load/Upload/Update
26 www.honeywell.com
2 ISSUES
Control Builder-Profibus
1-16JFE8J Error Indication: You are able to delete the first item from any grouped
modules when there is a DSB associated with that NETTAG.
Description: It must give an error popup message (for example, "You have
made a change to I/O definitions that has PDC references in the Control
Application.") when you try to remove an item from the grouped modules
when there are PDC references. Currently it allows to remove the first item
from the group where as it works as intended when deleting other modules
than the first one.
Recovery: Re-configure the modules
Workaround: Re-configure the modules
27
2 ISSUES
Control Builder-Delete
1-1A27Z5V Error Indication: Cannot force delete the offline device from monitoring
tree
Description: Unable to delete OW Adapter device from CB tree
monitoring when the device is in offline state. 'Force Delete' option does
not appear for OW Adapter device which is in offline state.
Recovery: Check if device is powered off or run out of battery.
Workaround: None.
Control Builder-Chart
1-1A58B5B Error Indication: IOP details are missing for PMIO channels.
Description: After assigning unassigned channels multiple times in CM
Loaded C200 with IOLIM and PMIO shows IOP details are missing on the
assigned channels.
Recovery: None.
Workaround: None.
1-1P915L9 Error Indication: After adding a phase block with function reference into a
Master Recipe chart, saving the Master Recipe, closing and opening the
Master Recipe again sometimes crashes Control Builder.
Description: After adding a phase block with function reference into a
Master Recipe chart, saving the Master Recipe, closing and opening the
Master Recipe again sometimes crashes Control Builder. Opening Control
Builder again and opening the same Master Recipe chart will work.
Recovery: Open Control Builder again and open the Master Recipe chart
again.
Workaround: None.
1-Q2XSJX Error Indication: Chart Visualization displays in Point detail displays
sometimes take 10-20 seconds come up.
Description: Chart Visualization displays in Point detail displays
sometimes take 10-20 seconds come up.
Recovery: None.
Workaround: Open the monitoring side charts from Control Builder for
the same point to view the details.
1-3L4KQ9D Error Indication: In certain scenarios REF parameter defaults to UDT
template name.
Description: Manual configuration of REF parameter.
Recovery: Re-enter correct REF value.
Workaround: Use Point Picker to enter REF value rather then typing
manually.
28 www.honeywell.com
2 ISSUES
1-1PQWSTZ Error Indication: Duplicate phase block created due to change parent in
specific scenario.
Description: Change Parent operation for phase block creates duplicate
copy in the chart.
Recovery: Delete the duplicate phase block.
Workaround: Delete the duplicate phase block.
1-3Q0K7WY Error Indication: On performing Change Parent(CP) of UDTCM1 to be
the child of UDTCM2 both configured with old style channels AIChannel-
>PID->AOchannel blocks, CP fails with unexpected error in case there is an
instance for the UDTCM1 and if there is no instance, then shows error
"Existing background connection exists...".
Description: Doing a change parent operation between two UDTs
containing Channel blocks throws an error.
Recovery: None.
Workaround: None.
Checkpoint
29
2 ISSUES
Control Builder-HART
30 www.honeywell.com
2 ISSUES
Control Builder
31
2 ISSUES
Control Builder-Load
32 www.honeywell.com
2 ISSUES
Control Builder-Assign
1-TETYQT Error Indication: The Print Preview is crashing the Control Builder.
Description: In Experion R410.1 , The Print Preview is Crashing the
Control Builder. This is happening only when Macrocycle chart view
(double click on the segment) is opened and Print Preview is clicked.
Control builder crashes both from Monitoring and Project side. also the
Print option does not print any details or chart regarding Macrocycle (both
monitoring and project side).
Recovery: None.
Workaround: None.
Control Builder-Search
1-UXS811 Error Indication: Display of error message "Search will be aborted due to
server connection timeout error" during simultaneous execution of Where
Used Search and Online Data Search from Configuration Studio on the
Primary server.
Description : The error is displayed since the services "Experion PKS
Browser Orchestration" and "Experion PKS Browser Support Service" are
stopped in the Primary server on which the search is executed.
Recovery : Restart the services "Experion PKS Browser Orchestration" and
"Experion PKS Browser Support Service" on the Primary server.
Workaround : None.
Control Kernal
1-XGHDCZ Error Indication: An alarm generated from CAB function block may
appear active in Station, though it is in normal condition. This can be cross
verified by monitoring faceplate of the CAB function block.
Description: If an active alarm generated by CAB function block is returned
to normal condition while C300 switchover is in progress; there is
possibility that this particular alarm still appears as active in station.
Recovery: Toggle ALMENBSTATE parameter of CM containing CAB
function block. This will trigger a re-notification of alarm state to station.
Workaround: None.
33
2 ISSUES
EIP-COMMUNICATION
1-1LSBQ9M Error Indication: After switchover or power cycle, a C300, FIM4, FIM8 or
PGM2 pair stops communicating.
Description: An unknown condition has caused a duplicate IP Address
situation that shuts down network communications. The node display of one
or both may show "DUP". CTools may show one or both nodes at the same
IP Address.
Recovery: Warning: You may lose your configuration and have to reload
from Control Builder. Power cycle the backup of the pair and wait to see if
the condition clears. If it does not, then power cycle the primary. If this does
not clear the problem, power cycle both together. Contact the Technical
Assistance Center and report the problem.
Workaround: None.
1-2ED9BQB Error Indication: Loss of communication with Ethernet/IP device.
Description: Any break in the communication path to a singly-attached
device may take up to a minute for FTE to resolve, if there is an alternative
path.
Recovery: An alternative path is resolved and the connection is restored
after a minute.
Workaround: None.
34 www.honeywell.com
2 ISSUES
1-J3B3SH Error Indication: In a dual primary scenario while migrating form R400.1
to R410.1 release, the Assets or Alarm Groups configuration builder
launched from ServerA indicated that the connection is made to the primary
server. The OPM status is indicated in the status bar. However instead of
indicating secondary server the status bar shows that the connection has
been made to the primary server.
Description: In a dual primary scenario while launching the Assets or
Alarm Groups Builder, it is expected that the status bar on the right bottom
corner must indicate OPM and Secondary Server connection status. In this
scenario you see a primary server connection indicated on the status bar. In
this scenario, the configuration change is not allowed at this time as the
OPM status is enabled. This is a cosmetic anomaly and you can ignore the
indication on the status bar.
Recovery: None.
Workaround: None.
EBM-Controller
35
2 ISSUES
1-PK1QJ5 Error Indication: After performing freeze and switchover , when a new
activity is created and started, it is struck in Acquiring Resource in Pre-Exec
State.
Description: When an OPM is performed on a controller having an MR
with multiple CR's running, the old CR's get removed as expected but after
OPM newly created Activities are not executing, they are struck in Pre-Exec
state with Acquiring Resource as Info.
Recovery: None.
Workaround: Remove the CR. Inactviate and Actviate the MR then Create
a new CR.
1-3QM82LT Error Indication: A step block displays an error of 2447 when trying to set
a unit.
Description: You are unable to select a unit.
Recovery: Abort the strategy.
Workaround: None.
1-LU37LJ Error Indication: You may observe that some activities you thought you
created do not show up in the activity summary display. The same activity
detail display may update from multiple activities which may cause
incorrect to be presented.
Description: Scenario:-
RCM_1 is running and it is acquired (either by another recipe or an
activity).
RCM_2 is trying to acquire RCM_1 (RCM_2 is in RCM_1s arbitration
queue, or listed as an un managed conflict). Idle->Cold start the controller.
Command RCM_1 to start. RCM_1 will reuse its Activity ID.
Recovery: There are no user steps for recovery. Once RCM_1 is run a
second time after the cold start, the problem will correct itself.
Workaround: Do not idle the controller when RCMs/SCMs are not in a
terminal state.I.E. Do not idle the controller when RCMs are in the running
state.
EBM-Tools
1-NS6M1L Error Indication: Load operation fails to load or does not give any error for
the updated range values of formula parameters in Data block/phase block.
Description: Loading of an RCM configured with the phase block having
invalid range values for its parameters does not give any errors and the
updated values are not reflected on monitoring side.
Recovery: None.
Workaround: None.
1-O0GF6A Error Indication: Key parameters in Table view display.
Description: When batch is executing across clusters such as parent and
child are in different clusters, the key parameter in table view of the parent
recipe that display child recipe key information could display.
Recovery: N/A.
Workaround: You must click the blank area which is right above key
parameters. This allows you to navigate to the child recipe detail Display
which displays all the information of the child recipe including the key
information.
36 www.honeywell.com
2 ISSUES
1-PADH2J Error Indication: Running SCM after CP Save/ Restore after LWA of Alias
may result in harmful effect.
Description : When LWA is performed for SCM/RCM in active state and it
has changes to selected instances in alias table, then selected instances are
not loaded but the values in checkpoint are updated. CP save and restore
after that may point to the new values.
Recovery: For such scenario, when LWA is performed for SCM/RCM in
active state and it has changes to selected instances in alias table, perform
Checkpoint Rebuild after LWA
Workaround: After CP rebuild, CP save and restore works properly.
1-UMLIDH Error Indication: Proxy blocks are not listed from different release servers.
Description: ICP2P is not supported on two different releases during
configuration time due to GCL connection limitation.
Recovery: None.
Workaround: None.
1-VIAD8V Error Indication: The number of activities shown in CEE statics Tab is
different from the number of activities shown in Batch tab of CEE.
Description: The NUMACT value as seen in the Batch Tab of the CEE
shows a mismatch with the CEE-Activity Staistics -TOTALACTCAP.
Recovery: Reload the ACE node in server.
Workaround:Same as Recovery.
1-ZX2IMV Error Indication: C300 controller and FTEB CPUFREE goes down by
7%-8% when UT is running
Description: C300 controller and FTEB CPUFREE goes down by 7%-8%
when UT is running. This issue is observed for all C300 controller and
FTEBs when executing Readiness Check of the controllers/chassis.
Recovery: None.
Workaround: None.
1-OMCM9H Error Indication: "Store Echo curve of the Setup" method fails to execute
for Vegapuls FF device.
Description: "Store Echo curve of the Setup" method fails to execute for
the following Vegapuls Rev 6 Devices and crashes Methods manager.1)
Vegapuls 612) Vegapuls 623) Vegapuls 634) Vegapuls 655) Vegapuls 666)
Vegapuls 677) Vegapuls 688) Vegapuls SR 689) Vegapuls WL 68
Recovery: Clear the ERDB lock and Invoke the Methods manager again
and do not execute "Store Echo curve of the Setup" method.
Workaround: None.
1-Q407YH Error Indication: Scroll bar is not available & Get string value built-in
method is not supported.
Description: In Method manager, for drop down menu if menu more of
option then user has to use scroll bar to scroll down or up, but scroll bar is
not available and Get string value built-in method, Experion in unable to
read the parameter.
Recovery: None.
Workaround: None.
37
2 ISSUES
1-R3X0ZN Error Indication: Flow Units and User Units of the Transducer block
displays unit as "Kbytes".
Description: Which is "Kbytes" for "1599".
Recovery: None.
Workaround: None.
1-Y3T5WR Error Indication: Some ST800 Resource block parameters not updating in
FDM.
Description: Some Resource block parameters on the ST800, including
Simulation Active and Write Lock, will not reflect updates in FDM if the
value changes on the device. If the DTM on FDM is connected to the
Device then these parameters will also not appear to update in the Control
Builder block configuration pages.
Recovery: Values update correctly in Control Builder if the DTM is not
connected to the Fieldbus device. Close the DTM on the FDM and monitor
static parameters through Control Builder configuration forms only.
Workaround: When enabling Simulation or changing Write Lock of the
ST800, close the DTM on the FDM and verify the changes to these
parameters through the Control Builder block properties page.
IEC61850_Embedded
PAR Description
1-3KPXXJX Error Indication: After the first read request error 6520-6530 is displayed.
Description: The provided SCL file does not match the IED.
Recovery: The Physical device must be unloaded and the correct CID file
must be loaded.
Workaround: None.
38 www.honeywell.com
2 ISSUES
PAR Description
1-3OZ2O8L Error Indication: Data takes longer than 6 seconds to refresh
Description: Data takes longer than 6 seconds to refresh, due to some
network issue.
Recovery: 850M recovers on its own.
Workaround: None.
1-3OGBUW7 Error Indication: Secondary 850M fails with error 0x00d2 while reloading
multiple IEDs (more than 13 IEDs at once).
Description: While reloading multiple IEDs from project view after
making changes, sometimes, 850M secondary fails with error 0x00d2. This
failure is observed only when you reload multiple devices in a single load
operation and is not observed during single device reload. Reloading
multiple IEDs at once results in improper stack fragmenting which may be
a major contributing factor to this failure.
Recovery: Reboot the failed 850M module.
Workaround: Reduce the number of IED devices getting loaded in a single
load operation or maintain more than 4.0 mb driver reserved free memory
of 850M.
1-1275R3B Error Indication: On removal and re-insertion of Profibus cable from both
primary and the secondary PGM, output channels become bad in TURCK
and SiemensET200M DSB.
Description: When Profibus cable is removed from primary PGM,
switchover is initiated and when the Profibus cable is again removed from
the new primary also all the outputs will go bad and is expected. But when
the cable is reconnected on both the PGM's, output channels remain bad
and does not recover.
Recovery: It does not recover automatically.
Workaround: Perform PGM Switchover, all the output channels become
good.
1-1WK0AHV Error Indication: During PGM Switchover if a channel goes BAD then all
the channels in the grouped PDC will go BAD.
Description: Upon PGM switchover, just after the secondary takes over the
role of Primary and the new secondary is still coming up, at that time if a
channel goes bad, then all the channels in that PDC become BAD.
Recovery: Perform PGM Switchover.
Workaround: None.
1-3HBNUST Error Indication: After loading link1 master shows as offline with number
of configured slaves as zero. Connecting to PGM master in SYCON, error
message in link1 shows Timeout while resetting Profibus.
Description: This is observed in testbed with 125 slaves configured on
each link with lots of simulated slaves. Happens only during load so not
very critical.
Recovery: Reboot PGM2,. Switchover PGM in case of redundant PGM. In
non redundant case reboot PGM and load.
Workaround: None.
39
2 ISSUES
IXP-Import Export
1-1L2XTPG Error Indication: Error appears as "An unexpected error was encountered"
in QVCS window.
Description: This issue appears in ERDBs migrated from releases before
R310.2, with strategies having duplicate FF IO channel names, which are
checked in QVCS. When you do a revert operation for the channel or CM
from a newer QVCS version to older version, then error appears as 'An
unexpected error was encountered" in QVCS window.
Recovery: Acknowledge the error. Keep the strategy or IO Channel in the
source QVCS version itself.
Workaround: Delete the strategy from monitoring side, re-configure to
older QVCS version.
1-28C3M4F Error Indication: After DD import(FF\wireless) QVCS checked in
strategies are editable.
Description : Checked in Control modules (having referece to FF blocks)
become editable after performing dd import of the same FF device.
Recovery : Close and reopen Control Builder.
Workaround : Close and reopen Control Builder.
1-3IWH9K7 Error Indication: Problem is observed after import of CM using
IXPTOOL.exe, block connections are missing.
Description: Export a CM using IXPTOOL.exe.Export is successful. After
the Export delete the CM in Control Builder. Import the exported CM using
IXPTOOL. Import is successful but when the chart is opened the pin
connections in the CM is lost.
Recovery: Import using Control Builder.
Workaround: Import using Control Builder.
1-VM137H Error Indication: Error appears as "Entry does not exist
[EXPKS_E_CL_ENTNOTEXIST (4L .101.10020)].
Description: When we have a tagged basic block which is an embedded
child in a CM (for eg: HART AO BLOCK with Hart enabled, embedded
and assigned in a CM), importing another CM with an assigned HART AO
with the same name fails and connection to the HART AO Block is lost in
imported strategy. Error appears as the import failed and there is a name
conflict for child blocks.
Recovery: Acknowledge the error. Re-configure the imported strategy with
non-conflicting IO channel name and assignment.
Workaround: Ensure that there are no name conflicts within child blocks.
Need to check the IO Channel names in CMs, correct it before import if
possible.
40 www.honeywell.com
2 ISSUES
I/O-Serial Interface
41
2 ISSUES
Series A IO Modules
42 www.honeywell.com
2 ISSUES
1-3KWWNT3 Error Indication: Exp R430, Profit Loop, Step Testing Bug in Level Loops
Description: When step testing level loops (i.e. integrators) there is a
problem if you change parameters which effect the future signal generation
(PRBS signal). In this case the SP of the loop gets set to match the OP of
the process for a single interval and then resumes its step. This can cause a
large spike in the SP to the loop if there is a large mismatch between the SP
and OP of the loop. This is a problem if any of these parameters are
modified during a test: upper/lower bounds of step, estimated response
time, move filter.
Recovery: None.
Workaround: Do not modify any of the following parameters during a test:
upper/lower bounds of step, estimated response time, move filter.
Table View
1-F8BHKD Error Indication: Trendparameter for SCM is not displayed in mini trend
display in the station.
Description: Trendparameter for SCM is not displayed in mini trend
display in the station.
Recovery : None.
Workaround : None.
1-HI1PMN Error Indication: When Report and Formula parameter is printed for
RCM, the report does not show the correct value.
Description: When Report and Formula parameter is printed for RCM, the
report does not show the correct value.Printing the report and formula
parameters, does not prints the current value.
Recovery: None.
Workaround: None.
PGM
43
2 ISSUES
Rockwell Network
1-11H1RD1 Error Indication: RsLinx does not show the Series A IO/SIM Card with
Module Icon.
Description: RsLinx application does not show the Series A IO/SIM Card
with Module Icon.
Recovery: None.
Workaround: None.
1-13QB7PX Error Indication: RsLinx automation tool fails when executed.
Description: RsLinx Automation doesn't stop the required services and
throws error
Recovery: None.
Workaround: Manually stop the Experion Server logger service from
Services.msc application and then re-run this tool. After stopping this
service RsLinx Automation works fine.
44 www.honeywell.com
2 ISSUES
FF-Configuration
1-123KRXP Error Indication: "VCR Limit exceed" error is displayed while loading
Fieldbus device
Description: VCR limit exceed error while loading.
Recovery: Acknowledge the error.
Workaround: Cross check if the connections are done within the limitation.
if not, try to delete the block and recreate the required connections.
1-14E2RC8 Error Indication: None.
Description: Control Builder allows to un-assign even if the device is
loaded.
Recovery: None.
Workaround: Ensure the device is not loaded before making any changes in
the Project side.
1-3PF1Q5L Error Indication: When user executes Read Echo Curve method for
Honeywell GWR level transmitter SLG700, graph does not get plotted.
Description: The data is not fetched from the Auxillary transducer block for
this device while executing the method in Experion.
Recovery: None.
Workaround: None.
1-3KTUVO9 Error Indication: C300 PCDI CM array Error flag does not turn "ON"
when a single Modbus device communication (TCP) is lost.
Description: C300 PCDI Device disconnect is not updating in a timely
manner - can take up to five minutes.
Recovery: Once the device is flagged as failed - ERROR FLG = "ON" then
no recovery is necessary.
Workaround: None.
45
2 ISSUES
46 www.honeywell.com
2 ISSUES
1-17FPCH Error Indication: Internal error occurs when you try to open the documents
related to SST_PFB_CLX in SST Profibus installation CD part nr.705-0004,
Rev. 03-02.
Description: Internal error occurs when you try to open the documents
related to SST_PFB_CLX in SST Profibus installation CD part nr.705-0004,
Rev. 03-02. Because of this the user documentation cannot be used which
will assist in installation or up-gradation of firmware.
Recovery: None.
Workaround: Use next version of SST_PFB_CLX in SST Profibus
installation CD part nr.705-0004, Rev. 07.10.0.0 where issue is resolved.
1-PPG7GR Error Indication: C200 5ms controller is losing Connection with Server
Intermittently resulting in loss of View at Control Builder (everything turns
RED at Monitoring side) and Loss of View at Station for C200 Detail
Display.
Description: Loss of View / Server Connection fail on Control Builder &
Station for C200 5ms (Non-Redundant), when there is Peer-to-peer (P2P)
Connection between C200 5ms & ACE on CNET and cable is disconnected
as per below: Remove Control Net Cable A of Non-Redundant C200 5ms &
Remove Control Net Cable B of ACE. Remove Control Net Cable B of Non-
Redundant C200 5ms & Remove Control Net Cable A of ACE. In the above
two Scenarios, Loss of Peer-to-peer data communication between C200 &
ACE is observed which is expected. But in this scenario, the C200 5ms is
losing Connection with Server Intermittently (disconnects and connects
back) and hence resulting in Loss of View at Control Builder (everything
turns RED at Monitoring side) and Loss of View at Station for C200 Detail
Display.
Recovery: Reconnect the cables back.
Workaround: None.
CF-Control Function
47
2 ISSUES
SE-System Engeneering
1-SKJSF4 Error Indication: The user may see reverse videos on display, may see loss
of trend values.
Description: During normal operation, the servers may lose view from the
controllers under a situation where an unresponsive node may exist in the
network. This may be because of a faulty device below the unresponsive
node. This may result in a loss of view condition.
Recovery: Manual. Remove the device/node that is causing
unresponsiveness and Stop/Restart EPKS Control Data Access service.
Workaround: None.
Network-CNI
1-WCZEO9 Error Indication: Remote IO communication failed with a CNI Line error
3416.
Description: Remote IO communication failed with a CNI Line error 3416.
Recovery: None.
Workaround: None.
1-XG5K9X Error Indication: CNET cable removal system alarm RTN even though
cable fault is live
Description: CNET cable removal system alarm RTN even though cable
fault exists
Recovery: None.
Workaround: None.
Network-FTE
1-3G2TAP4 Description:
Recovery:
Workaround:
I/O-Series C
1-3GAHYYS Error Indication: Outputs that were POWERED when field power was lost
will return POWERED momentarily before initializing when power is again
restored.
Description: Unexpected output behavior upon return of lost field power.
For more details of anamoly see PN2014-30.
Recovery: None.
Workaround: For any output that was POWERED when field power was
lost ensure that the output cannot return immediately to the POWERED state
when the field power is restored. For more detail on how this can be
accomplished see PN2014-30.
1-3I90BL7 Error Indication: HART communication errors continuously accumulate.
Description: AI-HART Analog Input module cannot communicate properly
with a WIKA T32 transmitter.
Recovery: None.
Workaround: None.
48 www.honeywell.com
2 ISSUES
1-3NDHL6P Description: When we try to connect the Control Builder from Server A
which is in R430.1 release, it fails to connect with the following errors:1.
ERR_DB_SWITCHTOREPLICA "Failed to connect to primary ER,
connected to secondary@@DB_SWITCHTOREPLICA"2.
ERR_ERCLI_REQID "Invalid Request Id@@ERCLI_REQID"3.
ERR_CBCANNOTLOGON "Cannot connect to database. View Error Log
for details.@@CBCANNOTLOGON"4. ERR_PROV_COMINTERFACE
"Failed on COM interface.@@PROV_COMINTERFACE"
Recovery: Same as Workaround
Workaround: Connect Control Builder from Console/Flex station.
Error Indication: This error occurs when we are trying to Open the Control
Builder from ServerA which is in R430.1 release while ServerB has been
migrated to R431.1 release.
Description: When we try to connect the Control Builder from Server A
which is in R430.1 release, it fails to connect with the following errors:1.
ERR_DB_SWITCHTOREPLICA "Failed to connect to primary ER,
connected to secondary@@DB_SWITCHTOREPLICA"2.
ERR_ERCLI_REQID "Invalid Request Id@@ERCLI_REQID"3.
ERR_CBCANNOTLOGON "Cannot connect to database. View Error Log
for details.@@CBCANNOTLOGON"4. ERR_PROV_COMINTERFACE
"Failed on COM interface.@@PROV_COMINTERFACE".
Recovery: Same as Workaround.
1-3OD3HT0 Workaround: Connect Control Builder from Console/Flex station.
Redundancy-RM
49
2 ISSUES
2.3
OPM-Upgrade Tool
PAR Description
1-3N3C5RD Error Indication: Readiness Check of C300 controllers having 500 or more reference blocks go to pending
state.
Description: One or more nodes go to pending state on a relatively larger system with controllers having
500 or more references blocks . This issue can be observed only on R431.1 system.
Recovery: Close and re launch the Upgrade Tool4.
Workaround: Perform the following steps :
1. After Readiness check enumeration, for the C300 controller which has more reference blocks, clear the
readiness check box, clear any dangling control connections and proceed.
2. Run ECC tool to identify the dangling control connections.
50 www.honeywell.com
2 ISSUES
2.4
PAR Description
1-3O9NPMP Error Indication: You get Data entry error on attempting to change mode of emulated
points from Cut Over Display before performing Cut over .
Description: You observe the error on performing the following steps.
1. HASE (Emulated) points are loaded to C300 controller but CUT OVER from HIWAY
to FTE is not performed.
2. Invoke Cut Over Display from Experion Station by entering SYSHSECTMGTB in
command prompt.
3. Enter Hiway Number and Box Number in COD Display to invoke faceplates for above
emulated points.
4. Attempt to store mode parameter of any of the above points from bottom (CDA) face
plates.
5. Mode store is unsuccessful and you get " Data entry error" while attempt to change
Mode of emulated points from Cut Over Display before performing Cut over .
Recovery: None.
Workaround: Perform the following steps if Application Engineer wants to change Mode
of HASE (Hiway Algorithm Slot Emulation) Slot CMs (Emulated Combo points) before
cut over.
1. Open Control Builder and Open the appropriate CM (Named as TPN point name).
2. Click on HRB block and click on MODEEM parameter.
3. Change to required Mode (AUTO/MAN/BCAS)
Perform the following steps if Application Engineer wants to change Mode of HASE Slot
CMs after cut over.
1. If AE wants to change mode of HASE slot CMs from COD then use the top faceplates
(TPN) faceplate.
or
Open Native Window and call Detail Display of the desired point and change the
mode.
Server
PAR Description
1-3PUQQQ5 Error Indication: Perfmon logs show increased memory usage for the process
hscodbcn.exe. Experion logs show constant authentication of ODBC client connections.
Description: ODBC driver resource usage can increase if an ODBC client does continuous
connect/disconnect. In this case the ODBC driver may eventually terminate and
automatically restart.
Recovery: None.
Workaround: Decrease the rate at which an ODBC client re-connects to and disconnects
from the Experion server. For AEA set the event collection period to 10 minutes.
51
2 ISSUES
PAR Description
1-3S5PF5Z Error Indication: IEC61850 SCADA HCI interface terminates abruptly when logging
level is set to 'FLOW'.
Description: IEC61850 SCADA HCI interface terminates abruptly when logging level is
set to 'FLOW'. In this case the interface terminates and restarts automatically.
Recovery: Same as workaround.
Workaround: Perform the following steps.
1. Open the corresponding OPC Config.XML that is terminating.
2. Change the Driver log level from FLOW to ERROR as per the following entry.
<DrvrLogLvl btype="Enum" type="LogLvl">ERROR</DrvrLogLvl>
3. Restart the corresponding driver.
FF Interface Modules
PAR Description
1-3QIZ2V1 Error Indication: During FIM4 failover test of15 FIM4s, 5 FIM4s stops responding with
the following error 0x03B3. Some FIM4s fail after 30 failovers and 2 fail after 100
failovers.
Description: A crash is observed in Fieldbus stack: FB_FS 0x0002-C 0x00-T 0xCF-M
166-L 0x0000-C 0x00D1-D with some kind of time out on fieldbus operation. This may
lead to control shed.
Recovery: Restart the affected module.
Workaround: None.
52 www.honeywell.com
3 Notices
Trademarks
Experion®, PlantScape®, SafeBrowse®, TotalPlant®, and TDC 3000® are registered trademarks of Honeywell
International, Inc.
OneWireless™ is a trademark of Honeywell International, Inc.
Other trademarks
Microsoft and SQL Server are either registered trademarks or trademarks of Microsoft Corporation in the
United States and/or other countries.
Trademarks that appear in this document are used only to the benefit of the trademark owner, with no intention
of trademark infringement.
Third-party licenses
This product may contain or be derived from materials, including software, of third parties. The third party
materials may be subject to licenses, notices, restrictions and obligations imposed by the licensor. The licenses,
notices, restrictions and obligations, if any, may be found in the materials accompanying the product, in the
documents or files accompanying such third party materials, in a file named third_party_licenses on the media
containing the product, or at http://www.honeywell.com/ps/thirdpartylicenses.
53
3 NOTICES
54 www.honeywell.com