CONSTRUCTION (ANNEX 5)
(LESS THAN OR EQUAL 1.0 MW SUPPLY - LV Metered Customers)
(REQUIREMENTS FOR ELECTRICAL INSTALLATIONS - BS 7671 [IET WIRING REGULATIONS)
DETAILS OF THE CUSTOMER
Name of the Customer Mr.J.G.N.K Jayasinghe Customer 4291704410
Electricity Account
No. and
Electric Utility
Address of the Customer 22/A,Gnanawimala rd,Walgama Contact No./
Road,Athurugiriya Email/
Fax
DETAILS OF THE CONTRACTOR
Ceylon Super Power Solution (Pvt) ltd SEA Registration
Name of the Contractor SLSEA/SBS/S00529
No.
NO.262/C/23,Crescent Garden, Contact No./
Address of the Contractor
Welivita, Kaduwela Email/ 0743314104
Fax
40 kW roof top grid connected solar power installation at the above address.
Panel Open Circuit Voltage (DC) 52.40 V 10. Panel Rated Voltage 43.59 V
(VMPP)
Panel Short Circuit Current (DC) 14.42 A 12 Panel Rated Current 13.65 A
. (IMPP)
Supported Standards IEC 61215/ IEC 61730/ UL 61730/ ISO 9001/ ISO 14001/ ISO45001
Page 1 of 3
Main Protective Conductors
Connection / continuity verified ✓
2
Earthing conductor Material - Cu CSA – 10 mm
SCHEDULES
The attached Schedules are part of this document and this Certificate is valid only when they are attached to it.
............ Schedules of Inspections are attached.
a. If there are more than one inverter in the installation, provide the particulars of each inverter in the same format in additional
sheets.
b. The test certificates/ compliance certificates from independent agencies or accredited agency or one of the following institutions
in Sri Lanka, should be submitted to prove the mentioned values
Page 2 of 3
SCHEDULE OF INSPECTIONS (for new installation work only) for
ROOOF TOP SOLAR POWER INSTALLATION LESS THAN OR EQUAL TO 1 MW SUPPLY
NOTE 1: This form is suitable for many types of smaller installation, not exclusively domestic.
All items inspected in order to confirm, as appropriate, compliance with the relevant clauses in BS 7671. The list of
items and associated examples where given are not exhaustive.
NOTE 2: Insert ✓ to indicate an inspection has been carried out and the result is satisfactory, or N/Ato indicate that
the inspection is not applicable to a particular item.
ITEM Outcome
DESCRIPTION
NO See Note 2
1.1 Any connections with Earth on the D.C. side is electrically connected so as to avoid ✓
Corrosion
1.2 The protective measures of non-conducting location and earth-free local equipotential ✓
bonding are not on the D.C. side.(712.410.3.6)
1.5 Protection by the use of Class II or equivalent insulation has been adopted on D.C. ✓
side of cell (712.412)
1.6 Overloaded protection is omitted from the PV array string if the cable current-carrying ✓
capacity is rated to at least 1.25 of the short circuit current. Short circuit current
protection is provided at connection to the mains(712.433.1),(712.434.1)
1.7 To minimize voltage induced by lighting, the area of all wiring loops are as small as ✓
possible (712.444,4,4)
1.8 PV modules comply with the requirements of the relevant equipment standards. ✓
(712.511.1)
1.9 PV modules have been installed in such a way that there is enough heat dissipation ✓
under conditions of maximum solar radiation for the site.( 712.511.2.1)
1.10 The selection and erection of equipment shall facilitate safe maintenance (712.513.1) ✓
1.11 PV string cables, PV array cables and PV main D.C. cables have been selected and ✓
erected so as to minimize the risk of Earth faults and short circuits. (712.522.8.1)
1.12 Wiring systems withstand the expected external influences such as wind, temperature ✓
and solar radiation. (712.522.8.3)
1.13 Isolation for maintenance on D.C. and A.C. sides is provided (712.537.2.1.1) ✓
1.15 All junction boxes carry label warning about energization after loss of ✓
mains.(712.537.2.2.5.1)
1.16 Protective bonding conductors run in close contact with D.C. and A.C. PV system ✓
cables (712.54)
1.17 Electrical Single line diagram of the installation is attached with the certificate. ✓