Larsen & Toubro is a leading technology-driven company in India, specializing in engineering and manufacturing low voltage switchgear, including Air Circuit Breakers (ACBs) designed for extreme tropical conditions. With over 30 years of proven performance, L&T's ACBs offer a wide range of features such as complete selectivity, user-friendly designs, and compliance with international standards. The product range includes various configurations and breaking capacities to meet diverse customer needs.

Uploaded by

DANIEL J
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
7 views

C-Power.132121415

Larsen & Toubro is a leading technology-driven company in India, specializing in engineering and manufacturing low voltage switchgear, including Air Circuit Breakers (ACBs) designed for extreme tropical conditions. With over 30 years of proven performance, L&T's ACBs offer a wide range of features such as complete selectivity, user-friendly designs, and compliance with international standards. The product range includes various configurations and breaking capacities to meet diverse customer needs.

Uploaded by

DANIEL J
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 31

Air Circuit Breakers

About us

Larsen & Toubro is a technology-driven company that infuses engineering with imagination. The
Company offers a wide range of advanced solutions in the field of Engineering, Construction,
Electrical & Automation, Machinery and Information Technology.

L&T Switchgear, a part of the Electrical & Automation business, is India's largest manufacturer of low
voltage switchgear, with the scale, sophistication and range to meet global benchmarks. With over
five decades of experience in this field, the Company today enjoys a leadership position in the Indian
market with a growing international presence.

It offers a complete range of products including powergear, controlgear, industrial automation,


building electricals & automation, reactive power management, energy meters, and protective
relays. These products conform to Indian and International Standards.

Switchgear Factory, Mumbai

Switchgear Factory, Ahmednagar


Air Circuit Breakers

L&T’s Air Circuit Breakers (ACBs) are specially designed for extreme tropical conditions and have a proven
track record of more than 30 years. Presently more than 3,50,000 Air Circuit Breakers supplied by L&T are
being used for diverse applications. The Air Circuit Breakers provide technologically driven
solutions to meet customer needs.

Complete selectivity
Unique feature of lcu=lcs=lcw for 1 second across the entire range. This ensures complete selectivity for
system with time based discrimination.

Perfect for Indian conditions


Inherent design to perform in extreme tropical conditions. Typical site conditions like high ambient
temperature, humidity and dusty environment are best handled by ACBs without compromising on
performance and safety.

Optimal compactness
Designed to ensure
lLow inherent temperature rise
lAdequate interface clearances

Widest choice of over current protection releases


Advance micro-controller based with option of communication & metering-SR71
l

Micro processor based releases-SR18/SR18G/SR21i


l

Thermo-magnetic release-DN1
l

Elegant design & rugged construction


Common door cutout for entire range
l

Left aligned cutout for all ratings


l

Uniform height and depth for ACBs upto 4000 Amp


l

Range to meet every customer’s need


Various options to choose from
lBreaking capacity from 50kA to 100kA
l3 Pole or 4 Pole configuration
lFixed or Drawout version
lAuto or Manual reset mechanism
lIndependent manual or stored energy type, manual or electrically operated mechanism
lDifferent terminal orientations : Flat, Horizontal and Vertical
1
User friendly features
Front accessible over current release settings, telescopic racking handle and various racking
l

interlocks; no need to open the panel door


Unique ‘Maintenance position’ in drawout type ACBs to facilitate maintenance & inspection without
l

removing ACB from the panel


Multitap CTs for enhancing protection range in DN1 release
l

Wide variety of Amperemetric and Voltmetric releases


l

Fully rated neutral pole for the entire range


l

Lockable sliding shutters to prevent unauthorized access to “TRIP” and “CLOSE” push buttons
l

Can be used as an ON / OFF Load Isolator


l

Extendable Electrical Life:


l

- By replacing the arcing contacts at site, for all ratings


- Without changing pole assembly
Programmable SICs: Auxiliary contacts in drawout ACBs are programmable for only Service, Only
l

Test, Test and Service, and All Positions


Protection releases are easily interchangeable at site
l

Facility for site conversion of manually operated ACBs to electrically operated ACBs
l

Jaws on breaker facilitate ease of maintenance & replacement of contact jaws


l

Safety
“ ’’ marked for C, S1 & H ranges
l

Superior quality engineering grade plastics used for insulation purpose; conforms to Glow wire test
l

(Ref: IEC 60695-2-1)


In-built mechanical anti-pumping to prevent auto-reclosing of ACB on persisting faults
l

In-built rating error preventor in drawout ACBs ensure correct rating of drawout portion in
l

corresponding cradle
Safety shutters prevent accidental contact with live cradle terminals
l

Variety of Safety Interlocks


l

Easily removable arc chutes without use of any tool


l

Operating voltage ranges from 10% Un to 110% Un for shunt release ensures intentional tripping
l

even at high voltage drops during short circuit


Transparent safety shutter offers easy inspection of cradle contacts & reduces the maintenance time
l

Conformance to standards
IEC - 60947 (Part 1 & 2)
l

IS/IEC - 60947 (Part 1 & 2)


l

IEC 60695 - 2 - 1
l

BS EN 60947 - 2
l

2
Range

Breaking capacities:
Icu = Ics = Icw

Rated Current 400A 630A 800A 1000A 1250A 1600A 2000A 2500A 3200A 4000A 5000A 6300A
CN-CS : E 50kA 50kA 50kA 50kA 50kA 50kA 50kA
Frame-1

CN-CS : S1 50kA 50kA 50kA 50kA 50kA 50kA 60kA 60kA

Frame-1 Frame-2

CN-CS : C 50kA 50kA 50kA 50kA 50kA 55kA 60kA 95kA 95kA

CN-CS : H 65kA 65kA 65kA 65kA 75kA 75kA


CN-CS : H0 75kA 75kA

CN-CS : H/H1 100kA 100kA

Frame-1 Frame-2 Frame-3 Frame-4

3
Technical Data Sheet

Rating (A) 400 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300

Type Designation E E S1 E S1 C H E S1 C H E S1 C H E S1 C H E S1 C H S1 C H S1 H0 H1 H0 H C C

Rated current (A) at 50°C In 400 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
*
Rated operational voltage (V), 50/60Hz U e 415 415 415 415 415 415 415 415 415 415 415 415

Rated insulation voltage (V), 50/60Hz Ui 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

No. of poles 3 3 3/4 3 3/4 3 3/4 3 3/4 3 3/4 3 3/4 3/4 3/4 3/4 3/4 3/4

Rated ultimate short circuit breaking Icu 380/415/500V 50 50 50 50 50 50 65 50 50 50 65 50 50 50 65 50 50 50 65 50 50 55 75 60 60 75 60 75 100 75 100 95 95


capacity 50/60Hz (kA rms) - - - - - 35 50 - - 35 50 - - 35 50 - - 35 50 - - 40 65 - 40 65 - 65 85 65 85 DD
690V

Rated service short circuit breaking Ics 380/415/500V 50 50 50 50 50 50 65 50 50 50 65 50 50 50 65 50 50 50 65 50 50 55 75 60 60 75 60 75 100 75 100 95 95


capacity 50/60Hz (kA rms) - - - - - 35 50 - - 35 50 - - 35 50 - - 35 50 - - 40 65 - 40 65 - 65 85 65 85 DD
690V

Rated short time 0.5 sec 50 50 50 50 50 50 65 50 50 50 65 50 50 50 65 50 50 50 65 50 50 55 75 60 60 75 60 75 100 75 100 95 95


**
withstand capacity Icw 1 sec 50 50 50 50 50 50 65 50 50 50 65 50 50 50 65 50 50 50 65 50 50 55 75 60 60 75 60 75 100 75 100 95 95
50/60Hz (kA rms) - - - - - 35 50 - - 35 50 - - 35 50 - - 35 50 - - 50 65 - 55 65 - 70 85 70 85 DD
3 sec

Icm 380/415/500V 105 105 105 105 105 105 143 105 105 105 143 105 105 105 143 105 105 105 143 105 105 121 165 132 132 165 132 165 220 165 220 209 209
Rated making capacity
50/60Hz (kA peak) - - - - - 73.5 105 - - 73.5 105 - - 73.5 105 - - 73.5 105 - - 84 143 - 84 143 - 143 187 143 187 DD
690V
Rated impulse withstand voltage Uimp
of main circuit (kV) 8 8 12 8 12 8 12 8 12 8 12 8 12 12 12 12 12 12

Rated impulse withstand voltage Uimp


of aux. circuit (kV) 4 4 4 4 4 4 4 4 4 4 4 4

Typical opening time (ms) 40 40 40 40 40 40 40 40 40 40 40 40


Typical closing time (ms) 60 60 60 60 60 60 60 60 60 60 60 60
Utilization category B B B B B B B B B B B B
Suitability for isolation PP P P P P P P P PPP
Fixed PPx Px PPPx PPPx PPPx PPPx PPx PPx x x x x x x

Draw out x x Px PPPx PPPx PPPx PPPx PPPPPPPPPPPPP

Manual PPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPP

Electrical x x Px PPPx PPPx PPPx PPPx PPPPPPPPPPPPP



Electrical & Mechanical life (operating cycles) 15000 15000 20000 15000 20000 15000 20000 20000 20000 20000 20000 10000 10000 5000 5000

Electrical life without maintenance 6000 6000 8000 6000 8000 8000 8000 6000 8000 8000 8000 6000 7000 7000 7000 6000 7000 7000 7000 4500 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 2500 2500

Dimensions (in mm) Fixed H 385 385 - 385 - 394 385 - 394 385 - 394 385 - 394 385 - 394 - 394 - D D - -

3 Pole 316 316 - 316 - 326 316 - 326 316 - 326 316 - 326 316 - 482 - 482 - D D - -
W
4 Pole - - - - - 414 - - 414 - - 414 - - 414 - - 628 - 628 - D D - -

D 423.5 423.5 - 423.5 - 431 423.5 - 431 423.5 - 431 423.5 - 431 423.5 - 431 - 431 - D D - -

Draw out H - - 468 - 468 - 468 - 468 - 468 - 468 468 468 468 468 468 583 583

3 Pole - - 399 - 399 - 399 - 399 - 399 - 399 555 555 555 701 701 913 913
W
4 Pole - - 487 - 487 - 487 - 487 - 487 - 487 701 701 701 909 909 1182 1182

D - - 587 - 587 - 587 - 587 - 587 - 587 587 587 587 587 587 691 691

* Please consult us for application at dc voltages & higher operational voltage upto 690V AC. Electrical life = Mechanical life. However, arcing contacts need to be replaced depending upon wear & tear.
** Icw values are indicated based on thermal considerations. While selecting a breaker please ensure that Icw requirement for the application is not more than D Please consult us.
Ics / Icu at the point of installation.
4 5
Protection releases

Microprocessor-based, Communication-capable Release - SR71

Salient Features
True RMS sensing
l

Offers comprehensive protection for overload, short circuit,


l

instantaneous, earth fault and neutral overload


High resolution backlit LCD display
l

Intelligent Pre-trip alarm to prevent system shutdown


l

Password protected settings and commands


l

MODBUS RTU protocol with intrinsic RS 485 port


l

LED indication for POWER ON, different faults and Pre-trip alarm
l

2 sets of storable protection settings


l

Last 5 trips & 128 Event records with time & date stamping
l

3 programmable contacts-1 for micro controller failure, 2 for basic


l

fault annunciation
4 relay contacts for indication of exceeding maximum demand, Pre-trip
l

alarm and control on breaker (closing and opening)


Rating-plug for precise protection at lower load currents
l

Auto-doubling features to prevent nuisance tripping


l

Selectable I2t based current for short-time and earth fault zones
l

Thermal reflectivity enables faster tripping on recurrent overloads


l

Inbuilt Zone Selective Interlocking


l

Provision for Self-diagnostic test


l

Conformance to EMI/EMC standards


l

Parameter Screen Details Factory


Abbreviation Settings
Overload Current Settings (A), Ir = In x .... PICKUP 0.4 to 1.0 In in steps of 0.05 In 1.0 In
(Phase) Time Delay, Tr (sec) at 6 x Ir TMS-tr 0.5-1-2-4-6-12-18-24-30 30 sec
Pre-trip Alarm Settings PREALAR 0.5 to 0.95 Ir in steps of 0.05 Ir 0.95 Ir
Thermal Reflectivity THM-MEM ON / OFF OFF
Function FUNC Enable / Disable
Neutral Fault Current Settings (A), In = Irx .... PICKUP 0.5-1.0 1.0 Ir
Time Delay (sec) DELAY Same as 'Overload (Phase)' 30 sec
Short Circuit Current Settings (A), Isd = In x .... PICKUP 2 to 10 In in steps of 0.5 In 10 In
Time Delay, tsd (msec) at 10 x In l2t OFF DELAY 20-100-200-300-400 400 msec
l2t ON DELAY 20-100-200-300-400 400 msec
Pre-trip Alarm Settings PREALAR 0.5 to 0.95 Is in steps of 0.05 Is 0.95 Is
l2t l 2t ON / OFF
Cold-load Pickup COLDPIC Enable / Disable Disable
Cold-load Pickup Delay CP-DLY 0.1 to 10 sec in steps of 0.1 sec 0.1 sec
Instantaneous Function FUNC Enable / Disable Enable
Current Settings (A), Ii = In x .... PICKUP 2 to 16 In in steps of 0.1 In 16 In
Earth Fault Function FUNC Enable / Disable Enable
Current Settings (A), Ig = In x .... PICKUP 0.1 to 0.6 in steps of 0.05 In for l2t ON 0.6 In
0.1 to 0.6 in steps of 0.01 In for l2t OFF
Time Delay (sec), tg DELAY 100 to 400 msecs in steps of 100 msec for l2t ON 3 sec
2
0.1 to 5 sec in steps of 100 msec for l t OFF
Pre-trip Alarm Settings PREALAR 0.5 to 0.95 Ig in steps of 0.05 Ig 0.95 Ig
l2t l 2t ON / OFF OFF
Cold-load Pickup COLDPIC Enable / Disable Disable

Note: Both Protection Groups 1 & 2 carry the same factory settings.

6
Additional Protections

Parameter Screen Details Factory


Abbreviation Settings

Under Current Function FUNC Enable / Disable Disable


Current Setting (A) x In PICKUP 15% to 80% in steps of 5% In 0.8 In
Time Delay (secs) DELAY 1 to 255 in steps of 1 second 1 second
Trip / Alarm MODE Either / Both Alarm
Current Unbalance Function FUNC Enable / Disable Disable
Current Setting (A) x In PICKUP 10% to 95% in steps of 5% In 0.2 In
Time Delay (secs) DELAY 1 to 10 in steps of 5 secs 2.0 secs
Over Voltage # Function FUNC Enable / Disable Disable
Voltage Setting (V) Vs = Vn x .. PICKUP 105% to 150% in steps of 5% Vn 1.2 Vn
Time Delay (secs) DELAY 0.1 to 100 in steps of 0.1 secs 5.0 secs
Reset Voltage RSTSET 85% to 98% in steps of 1% Vs 0.95 Vs
Trip / Alarm MODE Either / Both Alarm
Under Voltage # Function FUNC Enable / Disable Disable
Voltage Setting (V) Vn x .. PICKUP 45% to 65% in steps of 5% Vn 0.6 Vn
Time Delay (secs) DELAY 0.1 to 5 in steps of 0.1 secs 1 second
Reset Voltage RSTSET 102% to 115% in steps of 1% Vs 1.02 Vs
Trip / Alarm MODE Either / Both Alarm
Under Frequency # Function FUNC Enable / Disable Disable
45 to 50Hz for 50Hz in steps of 0.01Hz 48.0Hz
Frequency Setting (Hz) PICKUP
57 to 60Hz for 60Hz in steps of 0.01Hz 59.0Hz
Time Delay (secs) DELAY 0.1 to 100 secs in steps of 0.1 Second 0.2 secs
Drop Off Frequency DRPOFF 0.02 to 0.10Hz in steps of 0.1Hz 0.1Hz
Trip / Alarm MODE Either / Both Alarm
Over Frequency # Function FUNC Enable / Disable Disable
50 to 55Hz for 50Hz in steps of 0.01Hz 52.0Hz
Frequency Setting (Hz) PICKUP
60 to 62Hz for 60Hz in steps of 0.01Hz 61.0Hz
Time Delay (secs) DELAY o.1 to 100 secs in steps of 0.1 second 0.2 secs
Drop Off Frequency DRPOFF 0.02 to 0.10Hz in steps of 0.1Hz 0.1Hz
Trip / Alarm MODE Either / Both Alarm
Reverse Power # Function FUNC Enable / Disable Disable
Settings (kW) PICKUP 0.02 to 0.4 in steps of 0.01 Pn 0.2 Pn
Time Delay (secs) DELAY 1 to 100 in steps of 0.1 secs 2.0 secs
Trip Alarm MODE Either / Both Alarm
Phase Sequence # Function FUNC Enable / Disable Disable
Settings PICKUP 123 - 132 123
Time Delay (secs) DELAY 0 to 5 in steps of 0.5 secs 2 secs
Trip / Alarm MODE Either / Both Alarm
Breaker Failure Function FUNC Enable / Disable Disable
Time Delay (secs) DELAY 0.05 to 2 secs in steps of 0.01 secs 1.0 second
Maximum Demand Function FUNC Enable / Disable Disable
Exceed
Settings (kW) PICKUP 40 kW - 1600 kW 100 kW
Step DELAY 10 kW - 1000 kW 10 kW
i -Discrimination i -Discrimination Enable / Disable Disable

# Requires SR71-PM module

7
Metering
Parameter Screen Abbreviation Details
Current I Phase, Earth and Neutral
Imax Maximum running Current per Phase
%Load Percent Loading
Voltage# V Phase-Neutral
Vph-Vph Phase-Phase
Frequency # F System Frequency
Power Factor # PF System Power Factor
Power # kW Active Power per Phase and Total (kW)
kVAr Reactive Power per Phase and Total (kVAr)
kVA Apparent Power per Phase and Total (kVA)
kW Maximum Demand (kW)
Energy # kWh Total Active Energy (kWh)
kVArh Total Reactive Energy (kVArh)
kVAh Total Apparent Energy (kVAh)
Harmonic-Current I1HAR R-Phase Current Harmonics
I2HAR Y-Phase Current Harmonics
I3HAR B-Phase Current Harmonics
Harmonic-Voltage # V1HAR R-Phase Voltage Harmonics
V2HAR Y-Phase Voltage Harmonics
V3HAR B-Phase Voltage Harmonics
Display High Resolution Backlit LCD

# Requires SR71-PM module

Additional Features
Parameter Screen Abbreviation Details
LED Indications Auxiliary Power ON P
Overload P
Short Circuit P
Instantaneous P
Earth Fault P
Neutral Fault P
Trip P
Alarm P
Auxiliary Supply 24V DC
Digital Inputs 4 Nos.
Output Relays 3 Internal + 4 External Relays
240V AC / 5A, 30V DC / 5A (resistive load)
Rating Plug In Multiplier 630-800-1000-1250-2000-3200-5000
Communication Protocol MODBUS RTU
Link used RS 485
Maintenance Indication I2t based
Event Records (128) Pick-up, Alarm, Trip, Date, Time and Cause of Event,
voltage and current readings in all phases
Trip Records Last 5 records with date and time stamping,
Testing Self-Diagnostic Test P
Supplementary Modules Comunication Module (SR71-COM) MODBUS RTU using RS485
Power Supply Module (UN-PS) Input:26V to 60V DC, 90 to 300V AC/DC Output:24V DC
Power Metering Module (SR71-PM) 240V AC, 415V AC
Relay Module (SR71-REL) 4 Relay Outputs (Breaker OPEN, Breaker CLOSE, Pre
Trip alarm and MD Exceed)
No. of Storable Settings 2

8
Protection releases

Microprocessor Based Release - SR21i

Salient Features
Self-powered & true RMS sensing
l

Inbuilt Zone Selective Interlocking (ZSI)


l

Provision for Self-diagnostic test(without tripping the breaker)


l

Switchable thermal memory takes care of residual heat in case of


l

repetitive overloads
Multi-state LED to indicate
l

- Power ON condition
- Test mode
Individual fault annunciation through LEDs
l

Provision for AN1 module for remote fault indication through LEDs with
l

changeover contact for each kind of fault


Direct tripping of breaker-reliable tripping with minimum time delay
l

Test kit available for testing the release (SRT-2)


l

Realistic hot and cold curves which take into account integrated heating
l

effect
Conformance to EMI/EMC standards
l

Type of Setting Range


Protection Pickup Current Time Delay
Ir - 0.5 to 1.0 times In 0.2 to 30 sec. at 6 times Ir
Long Time Steps : 0.50, 0.60, 0.65, 0.70, Steps : 0.2, 0.5, 1, 1.5, 2, 3.5,
0.75, 0.80, 0.85, 0.9, 0.95, 1.00 6, 12, 17, 30 Sec

20 ms to 600 ms
2 to 10 times In
Short Time Steps : 20, 60, 100, 160, 200,
Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10
260, 300, 400, 500, 600 ms

2 to 16 times In
Instantaneous Steps : 2, 3, 4, 6, 8, 10, 12, -
14, 16, OFF

100 to 400 ms
0.2 to 0.6 times In
Ground Fault* Steps : 100, 200, 300, 400 ms
Steps : 0.2, 0.3, 0.4, 0.5, 0.6
& OFF

In 3 phase, 4 wire system, Neutral CT is required for ground fault protection.

Test-kit SRT-2

Salient Features
l Test-Kit for SR18/SR18G/SR21i Releases
l Operates from 230V AC supply & generates single-phase voltage test signals
l Tests the release for
- Phase fault i.e. for long time, short time and instantaneous protection
- Ground fault protection
Test current multiples
l

- For phase faults: 2.5 In, 4.5 In, 6.5 In, 9.5 In, 11 In, 13 In
- For ground fault: 0.25 In, 0.35 In, 0.45 In, 0.55 In
Five 7-segments LED display indicates the trip time (two places after
l

decimal)

9
Protection releases

Microprocessor Based Release - SR18 & SR18G

Salient Features
Self-powered & true RMS sensing
l

Comprehensive protection
l

- SR18; Long Time and Short Time


- SR18G; Long Time, Short Time and Ground fault protection
True Hot & Cold characteristics & switchable thermal memory
l

Multi-state LED to indicate


l

- Power ON condition
- Test mode
Individual fault annunciation through LEDs
l

AN1 module for remote fault indication through LEDs with changeover contact
l

for each kind of fault


Provision for Self-diagnostic test (without tripping the breaker)
l

Test kit (SRT-2) available for testing the releases


l

Conformance to EMI/EMC standards


l

Setting Range
Type of
Protection Pickup Current Time Delay

Ir - 0.5 to 1.0 times In


Long Time Steps : 0.50, 0.60, 0.65, 0.70, 2.5 sec at 6 times Ir
0.75, 0.80, 0.85, 0.9, 0.95, 1.00

20 to 600 ms
2 to 10 times In Steps: 20, 60, 100, 160, 200,
Short Time
Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10 260, 300, 400, 500, 600 ms

Instantaneous 6 & 12 In -

100 to 400 ms
0.2 to 0.6 times In
Ground Fault* Steps : 100, 200, 300,
Steps : 0.2, 0.3, 0.4, 0.5, 0.6
400 ms & OFF

* Available in SR18G release only


In 3 phase, 4 wire system, Neutral CT is required for ground fault protection.

Thermo-magnetic Release Type - DN1


DN1 thermo-magnetic release offers reliable protection against overload, short circuit
and ground faults via multitap Cts. with ambient temperature compensation
from -50C to 500C
Protection
Overload Protection
lUnique individual phase O/L setting adjustment helps to avoid the nuisance tripping of
ACBs in unbalance load condition (due to single phase loads) on distribution
transformer. Long time pick-up range: 0.75 to 1 times In
Short Circuit Protection
lTwo taps on CTs (working as rating plug) help in selecting operating threshold.
Short-time pickup range: 5.5 to 7.5 times In with minimum impulsion time of 25ms
to prevent nuisance tripping due to transients
Ground Fault Protection
lOffered with auxiliary earth fault release module. Ground-fault pick-up range: 0.2 to
0.5 times In

10
Protection Characteristic
Overload Curve (SR71)
10,000

1000

100
Trip Time (s)

10 30 sec
24 sec
18 sec

12 sec

6 sec
4 sec
1
2 sec Tolerance: Short Circuit - I2t ON (SR71)
Trip Time: ±20%
10,000
1 sec

0.5 sec

0.01 0.6

1.5 2 3 4 5 6 9
1000
Current Multiples ( x Ir) 1.0

1.5

2.0

100 3.0

4.0
6.0

8.0
Trip Time (s)

9.0
10
10.0

0.4

0.3

0.2

0.1 0.1

0.02

0.01
0.05 0.1 1 10 50

Current Multiples ( x In)

11
Protection Characteristic
2
Short Circuit - I t OFF (SR71)
10,000

0.6

1000
1.0

1.5

2.0

100 3.0

4.0

6.0

8.0
Trip Time (s)

9.0
10
10.0

0.4
0.3

0.2

0.1 0.1
Instantaneous (SR71)
10.000

0.01
0.05 0.1 1 10 50
1000
Current Multiples ( x In)

100
Trip Time (s)

10

2.0

3.0

4.0
1 5.0

6.0

8.0

10.0

16.0

0.1

0.01
0.05 0.1 1 10 50

Current Multiples ( x In)

12
Protection Characteristic
2
Earth Fault - I t ON (SR71)
10,000

1000

100
Trip Time (s)

10

0.2
0.3
0.4
0.5
0.6

0.4s

0.1 0.1s Earth Fault - I2t OFF (SR71)


10,000

0.01
0.8 2.4
0.05 0.1 1 10 50
1000
Current Multiples ( x In)

100

0.2 0.3
0.4
0.5
Trip Time (s)

10 0.6

5.0

1 1.0

0.4s
0.3s

0.2s

0.1 0.1s

0.01
0.05 0.1 1 10 50

Current Multiples ( x In)

13
Protection Characteristic

Overload (SR21i)
10000

1000

100
Trip Time (s)

30
10
17
12

3.5
1
2.0
1.5
1.0

0.5

0.1 Short Circuit (SR21i)


0.2

2 10
0.01 0.6 0.6
1 1.2 1.5 2 3 4 5 6 7 8 9 10 0.5 0.5

Current Multiples ( x Ir) 0.4 0.4

0.3 0.3
0.26

0.2 0.2

0.16
Trip Time (s)

0.1 0.1

0.06

0.02

0.01
1 2 3 4 5 6 7 8 9 10 20 100

Current Multiples ( x In)

14
Protection Characteristic

Ground Fault (SR21i)


1

0.2 0.6
0.4

0.3

0.2
Trip Time (s)

0.1 0.1

Overload (SR18/18G)
1000

0.01
0.1 1 10 100

Current Multiples ( x In)

100
Trip Time (s)

10

0.1
1 1.2 1.5 2 3 4 5 6 7 8 9 10 20

Current Multiples ( x Ir)

15
Protection Characteristic

Short Circuit (SR18/18G)


1

2 10

0.6 0.6

0.5 0.5

0.4 0.4

0.3 0.3
0.26

0.2 0.2

0.16
Trip Time (s)

0.1 0.1

0.06

0.02
Ground Fault (SR18G)
1

0.01
1 2 3 4 5 6 7 8 910 20 100
0.2 0.6
Current Multiples ( x In)
0.4

0.3

0.2
Trip Time (s)

0.1 0.1

0.01
0.1 1 10 100

Current Multiples ( x In)

16
Protection Characteristic

Time-current (DN1)
10000

}1.05
1.2
Operating Limits
Thermal

1000

100

Zone of Short Circuit Operation (M1/M2)


10
Trip Time (s)

0.4
0.3
M1
0.2
M2
0.1

DN1

25ms

Total Operating Time


Min. Impulsion Time
0.01

0.7 1 2 3 4 5 678910 20 304050 100 400 1000

Current Multiples ( x In)

17
18
N R Y B

1 3 5 7 9 11 13 15 E C 81 41 41 H 50 73 70 B 88

(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(

(
Wiring Diagram

(
x x x x

CA-1
C11 H

Only for DC
4 ECD

(
DN1/SR18/SR18G anti
CC NCT MV CP pumping
SR21i/SR71

(
EA/

Internal Wiring
EA1

(
F

Internal Wiring
81

(
82

FCA

(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(

(
(
C6
Load 2 40 6 8 10 12 14 16 A B D 82 42 42 F 52 55 74 75 71 72 E 89 90
Micro switch
Main Protection & Aux Shunt Aux Aux Aux Aux Aux Aux Closing Electric Neutral U/V Closing Spring Common Separate Shunt Under Electrical for ground
Circuit Control Unit NC release NC NO NC NO NC NO Coil Charging C.T. release Preventer Charging fault fault trip voltage anti-pumping fault in DN1
Device Indication Indication Indication Indication Indication release

Ref no. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

As per order/requirement

The above drawing is for EDO breakers. FCA Limit switch(Shown in breaker reset condition)
1) For MDO/MF versions R Economy Resistor
Ref no. 3, 10, 11 are not applicable C11 Limit switch operates when closing electromagnet is held on
C6 ‘Service’ position microswitch for withdrawable circuit breakers(shown in ‘test’ position)
E, B, C, D, A are applicable only in electrical breakers.
For SR21i release (P&C unit)
2) For EF versions
The ref. no. 12, 13, 14, 15, 16, 17, 18, 19, 20, 21 are provided as per customer requirement. SI, SO i discrimination Short circuit i/p & o/p
GI, GO i discrimination Ground fault i/p & o/p
G Ground
Accessories

Type Data

Lockable Trip Push Mounted in place of normal trip push button. With this, ACB can be locked
Button (LTPB)
in trip condition. For interlocking, LTPBs are offered in the following
combinations:
l 4 different types of keys i.e. AA, BB, CC and DD suitable for 2 I/C & 1 B/C
schemes
l Combination of L, M, N, LM and MN locks, which are suitable for
3 I/C & 2 B/C schemes
l Combination of K, L, M, N, KL, LM and MN locks, which are suitable for
4 I/C & 3 B/C schemes
l Combination of J, K, L, M, N, JK, KL, LM and MN locks, which are
suitable for 5 I/C & 4 B/C schemes

View of the Cradle Locking in Isolated Position (LIP)


The facility of locking the ACB in Isolated position is available in Drawout
ACBs. This is useful to achieve interlocking between Main & Standby
source. Similar lock is available as LOCK IN ANY POSITION.

Door Interlock
This ensures:
Door Racking Locking in lUnless the panel door is closed, breaker cannot be racked in or out
Interlock Interlock ‘Isolated’ lUnless the breaker is in Isolated Position, it is not possible to open the
Position panel door

Racking Interlock
This ensures that breaker cannot be racked in/out unless the ACB is in
tripped/open condition.

Mechanical Interlock It is possible to provide ‘Mechanical Interlock’ between two breakers of


the same or different ratings in vertical or horizontal configurations.
Mechanical interlock is available for ACBs up to 4000A. Mechanical
interlocking for ACBs in vertical configuration can be provided by links or
by flexible cables. Same for horizontal configuration can be provided by
flexible cables.

19
Accessories

Type Data
C1
Common indication of tripping due to overload, short circuit
and ground faults.
lProvided by micro-switch C1 fitted inside the ACB
lAvailable as an option in all releases

C2
Separate indication of tripping due to overload, short circuit
and ground faults.
lFor release type DN1, this is provided by micro-switch C1 &
C2 (C2 fitted inside release)

AN1-Annunciator Module
Remote indication of tripping due to overload, short circuit
and ground faults.
lCan be used with releases type SR18/SR18G/SR21i
lIndividual fault indication provided by three separate LEDs for
- Long time faults
- Short time fault/instantaneous fault
- Ground fault
- One potential free contact rated 5A at 230V AC available for
each type of fault
lFlush mounting on panel (H-W-D=92mm x 46mm x 105mm)
lOperating voltage: 240V AC

C5
Indication for operation of shunt release or undervoltage
release.
l Provided by micro-switch C5 fitted on the shunt release or
undervoltage release

20
Accessories

Type Data Technical Data

Shunt Release For remote tripping of the


l
Type Rated Power Operation
breaker of Operational consum- Limit
Shunt release coil is short time
l Release voltage ption at
(Ue) pick-up
rated and is disconnected from
the circuit by an auxiliary 240 AC 800 VA 10-130%
EA1
contact when the ACB trips 415 AC 800 VA Ue
(Refer to wiring diagram) 24V DC 32 W 65-130%
Low power consumption
l 48V DC 125 W Ue
EA
Two types available:
l 110 DC 45 W
- EA for DC application 220 DC 30 W

- EA1 for AC application Note : Other voltages available on request

Undervoltage Release l Type MV With no intentional Parameter Specification


time delay
Rated Operational 240V & 415V: 50Hz
voltage (Ue) 220V & 415V: 60Hz
Notes: When undervoltage
release is provided, the ACB can Pick up (V) 80% Ue
be closed only when supply is
Drop OFF (V) 35-65% Ue
available to the undervoltage
release. Consumption (VA) Pick up - 23 VA
Hold on - 10 VA

Watt loss 6W

Closing Release Closing release remotely closes Rated Power Range of


operational consumption operation
the circuit breaker if the
voltage
mechanism spring is already (Ue) Pick-up Hold-up
charged. 110V AC
240V AC 320VA 50VA
220V AC
85-110%
110V DC Ue
300W 50W
220V DC
24V DC 350W 50W

Spring charging Motor Electrical charging device Rated Power Range of


automatically charges the operational consumption operation
voltage
mechanism spring of the (Ue)
circuit-breaker. After circuit-
breaker closing, the geared 240V AC 320VA
motor immediately recharges
85-110%
the closing spring. Thus 110V DC Ue
instantaneous reclosing of 154W
220V DC
the circuit-breaker is possible
following opening operation.

Auxiliary Contacts Two combinations available: Electrical Voltage Rated current


circuit (V) (A)
l2 NO + 2 NC
l6 NO + 6 NC Resistive 24 to 415 AC 16
250V AC 1.2

Non- 24 to 415 AC 16
resistive 250V AC 1.0 #

# L/R = 15ms with two contacts in series

21
Overall Dimensions

Fixed Breakers

For 800A to 2500A 3P/4P C/H


For Metallic Components

To Remove
340 min Arc Chute
For Insulating Sheet

200 min
7

140 min
Door

100 min
20 min Bezel
36 min 36 min 9
A 27
26 58 264 26

385

256
33
394
309

22
16

68.8
27
30 230
104

Earthing Terminal 35
20 301 54
2 Holes-Ø6.3 2.6 min
21 16 405 86 10

D E F E D

Ratings Dimensions (mm) Weight (kg.)


CN - CS
A D E F Manual Electrical
800/1000A C/H 3P 50 57
326 57 102 -
1250/1600A C/H 3P 51 58
800/1000A C/H 4P 54 61
414 56 98 98
1250/1600A C/H 4P 55 62
2000/2500A C/H 3P 482 83 154 - 72 79
2000/2500A C/H 4P 628 82 150 156 77 84

For CN-CS...E 400A-2000A 3P


340 min
Insulator

+1.0
40 min 316 40 min 20 min
100 min

23.5
58 102 102 56
Rating
Type X Y

400E -
1250E 5 150
X
1600/ 15 140
385

4 Holes 2000E
325

286

Ø12 X
227

216
20 20
32

298
22 137.5
402 21
179.5

Note : All Dimensions are in mm.

22
Overall Dimensions

Fixed Breakers

Terminal

2 Holes-Ø13 3 Holes-Ø13

30 15 30 15

12.5 25 50 25
25

50 100

400 to 2000E & 800/1000/1250/1600C/H 2000/2500C/H

Terminal Connections
23.5

23.5
10 15

10 15
227
227

140
145

Terminal for 800/1000C/H Terminal for 1250/1600/2000/2500C/H

Bezel Fixing Plan for all Fixed Breakers

305
12 Holes-Ø4 101
332

Hinge Hinge
112
112

363
325

112

5.5
91

11 min 59 294 15 min

Door Cutout Door Drilling for Bezel


Bezel Fixing Plan
Note:
A = 89 for 4000C
A = 91 for other
fixed ACBs

Note : All Dimensions are in mm.

23
Overall Dimensions

Drawout Breakers

For 630A to 3200A C/H/S1 3P/4P, 3200H1/4000H 3P/4P


For Metallic Components
75 Isolated Position
A
380 min
51 Test Position

200 min
122 For Insulating Sheet
40 max 7

100 min
94.5 264 Service Position
Door
40 64.5 26 Bezel

*5

256
468

397.5
404

68.8
160
M 10
46 28
4 74
6 10 54
17.5 min.
199.5 20
6 18.9 max.
538 8.9 min. 18 245

*Terminal For 630/800/1000 C/H/S1,


1250/2500S1 & 2000C/H
D E F E D
64.5 Earthing Terminal 40 65 60
5 25 15
15 15
308.5
308.5

308.5
221.5

221.5

221.5

*Terminal for *Terminal for *Terminal for


1250/1600/2500C/H for 3200S1 3200H0/H1
& 800/1000H & 4000H0/H

Ratings Dimensions (mm)


CN - CS
A D E F
630/800/1000A C/H/S1 3P
2000A S1 3P 399 97.5 102 -
1250/1600A C/H/S1 3P
630/800/1000A C/H/S1 4P
2000A S1 4P 487 96.5 98 98
1250/1600A C/H/S1 4P
2000/2500A C/H 3P
555 123.5 154 -
2500/3200A S1 3P
2000/2500A C/H 4P
701 122.5 150 156
2500/3200A S1 4P
3200A H0/H1 3P
701 148.5 202 -
4000A H0/H 3P
3200A H0/H1 4P
909 151.5 202 202
4000A H0/H 4P

Note : All Dimensions are in mm.

24
Overall Dimensions

Drawout Breakers

Flat Terminal Connections 63


50 100
25
25 30 30
19
12.5 10.2 20
10.2 10.2
4 slots 4 Slots 6 Slots

58.4

58.4
58.4

38

38
8.5 x 9.5 8.5 x 9.5
38

8.5 x 9.5

8.5 8.5 8.5

800 - 1000C & 630 - 1250S1 800 - 1000H, 1250/1600C/H & 1600 - 2000S1 2000C

106 106 160


25 25 25 25 25
33 33 33 33 6 Holes-Ø14
17.5
20 106 20
12 12

6 Holes-Ø14 6 Holes-Ø14

70
50
43

25
67

67
43

62
38

12.5
6 Holes- Ø14
2500C/H & 2000H 2500S1 3200S1 3200H0/H & 4000H0/H1

For 5000C/6300C 3P/4P


For Metallic Components
75 Isolated Position
A 400 min 51 Test Position
200 min

124 For Insulating Sheet


Service
20 max 7
100 min

96.5 264 Position Door


102 26 Bezel

256
404

467

68.8
M 10
160

46 28
6 5 74
10 54
199.5 10 17.5 min 20
5 18.9 max.
615 8.9 min. 18 245

D E F E D 8 Holes-Ø14

217
63

28
683

17.5

40 50 40 43.5
42
Terminal Connections
64.5
Earthing Terminal 5000C/6300C

Dimensions (mm)
Ratings
A D E F
5000A C 3P 913 187.5 269 -
6300A C 3P 913 187.5 269 -
5000A C 4P 1182 187.5 269 269
6300A C 4P 1182 187.5 269 269

Note : All Dimensions are in mm.

25
Overall Dimensions

Mounting Details

For Horizontal Mounting of all Draw-out Breakers


For 630A to 3200A C/H/S1 3P/4P 3200 H0/H1, 4000 H0/H 3P/4P
107.5 367.5 40 10 Holes-Ø11
24

G
Ratings Type
(mm)
800A - 1600A 3P C/H 280.3
*G

Front 630A - 2000A 3P S1 280.3


800A - 1600A 4P C/H 368.3
630A - 2000A 4P S1 368.3
2000/2500A 3P C/H 436.3
24
64.1 2000/2500A 4P C/H 582.3
2500/3200A 3P S1 436.3
20 481 37
2500/3200A 4P S1 582.3
3200A 3P H0/H1 582.3
For 5000C/6300C 3P/4P
592 3200A 4P H0/H1 790.3
10 Holes-Ø11
522 4000A 3P H0/H 582.3
25
4000A 4P H0/H 790.3
5000/6300A 3P C 863
5000/6300A 4P C 1132

25

50
108.5
184.5

Bezel Fixing Plan for all Draw-out Breakers


6 Holes-Ø4 305 332

Hinge Hinge
224
412

450
199

1 5.5
Base of
Cradle

20.5 min A 294 5 min

Door Cutout Door Drilling Bezel


for Bezel Fixing Plan
Note: For 4000A C 3P/4P, 5000C/6300C 3P/4P ACB, A = 81.5
For other Drawout Breakers A = 79.5

Note : All Dimensions are in mm.

26
Overall Dimensions

Terminals

Horizontal Terminals Rear Side


80 80 80 80
10

10
15

15
308.5

221.5
800 - 1000C 1250 - 1600C/H 2000C 2500C/H
& 800/1000H & 2000H
2 Holes-Ø14 3 Holes-Ø14 4 Holes-Ø14 6 Holes-Ø14
12.5

20
12.5

15

25 25 25
16.5

33 33
160
100
50

63
25

16.5

12.5 25 12.5 30
12.5 25 12 43

Vertical Terminals
V S W

U 40.0

4 Holes-ØT O P Top

R
N
M
387.5
X

308.5
221.5

Side View Rear View

Ratings M N P Q R S T U V W X
630-1250 S1 & 800-1000 C 10.2 38 20 25 29.2 5 9 65 95 10 58.4
1600-2000 S1 & 1250-1600 C/H
20 40 20 25 29.2 5 9 65 95 10 80
800-1000 H
2000C 20 40 20 40 29.2 22.5 14 80 110 15 80
2500 C/H
20 40 20 40 33.5 7.5 14 80 110 15 80
2000 H

Note : 1) All Dimensions are in mm. 2) Consult us for other Terminal Orientations.

27
Overall Dimensions

Terminals

Vertical Terminals
V

U S

Q P W
ØT 60
15
N
M

R
X

308.5
221.5

The dimensions for 3200 H1/H0 and 4000 H0 are as under:

Ratings M N P Q R S T U V W X
3200 H1/H0 & 4000 H0 30 100 45 40 29.5 95 14 80 140 15 160

Note : 1) All Dimensions are in mm. 2) Consult us for other Terminal Orientations.

28
Electrical Standard Products (ESP) Branch Offices:

REGISTERED OFFICE AND Khairasol, Degaul Avenue EBG North Wing Office-Level 2
HEAD OFFICE Durgapur 713 212 Gate 7, Powai Campus
L&T House, Ballard Estate Tel: 2559848, 2559849, 2559844 Mumbai 400 072
P. O. Box 278 Fax: 0343-2553614 Tel: 022-67052874 / 2737 / 1156
Mumbai 400 001 e-mail: [email protected] Fax: 022-67051112
Tel: 022-67525656 e-mail: [email protected]
Fax: 022-67525858 Milanpur Road, Bamuni Maidan
Website: www.Larsentoubro.com Guwahati 781 021 12, Shivaji Nagar
Tel: 0361-2550562 / 65 North Ambazari Road
ELECTRICAL STANDARD PRODUCTS (ESP) Fax: 0361-2551308 Nagpur 440 010
501, Sakar Complex I e-mail: [email protected] Tel: 0712-2260012 / 3
Opp. Gandhigram Rly. Station Fax: 0712-2260020 / 30
Ashram Road II Floor, Vasantha Chambers e-mail: [email protected]
Ahmedabad 380 009 5-10-173, Fateh Maidan Road
Tel: 079-66304006-11 Hyderabad 500 004 32, Shivaji Marg
Fax: 079-66304025 Tel: 040-67015052 P. O. Box 6223
e-mail: [email protected] Fax: 040-23296468 New Delhi 110 015
e-mail: [email protected] Tel: 011-41419514 / 5 / 6
38, Cubbon Road, P. O. Box 5098 Fax: 011-41419600
Bangalore 560 001 Monarch Building, 1st Floor e-mail: [email protected]
Tel: 080-25020100 / 25020324 D-236 & 237, Amrapali Marg
Fax: 080-25580525 Vaishali Nagar L&T House
e-mail: [email protected] Jaipur 302 021 P. O. Box 119
Tel: 0141-4385914 to 18 191/1, Dhole Patil Road
131/1, Zone II Fax: 0141-4385925 Pune 411 001
Maharana Pratap Nagar e-mail: [email protected] Tel: 020-26164048
Bhopal 462 011 Fax: 020-26164048/26164910
Tel: 0755-3080511 / 05 / 08 / 13 / 17 / 19 Akashdeep Plaza, 2nd Floor e-mail: [email protected]
Fax: 0755-3080502 P. O. Golmuri
e-mail: [email protected] Jamshedpur 831 003 Crystal Tower, Plot No. 606/1
Jharkhand 4th Floor, G. E. Road
Plot No. 559, Annapurna Complex Tel: 0657-2312205 / 38 Telibandha
Lewis Road Fax: 0657-2341250 Raipur - 492 006
Bhubaneswar 751 014 e-mail: [email protected] Tel: 0771-4283214
Tel: 0674-6451342, 2436696 e-mail: [email protected]
Fax: 0674-2537309 Skybright Bldg; M. G. Road
e-mail: [email protected] Ravipuram Junction, Ernakulam 3rd Floor
Kochi 682 016 Vishwakarma Chambers
SCO 32, Sector 26-D Tel: 0484-4409420 / 4 / 5 / 7 Majura Gate, Ring Road
Madhya Marg, P. O. Box 14 Fax: 0484-4409426 Surat 395 002
Chandigarh 160 019 e-mail: [email protected] Tel: 0261-2473726
Tel: 0172-4646840, 4646853 Fax: 0261-2477078
Fax: 0172-4646802 3-B, Shakespeare Sarani e-mail: [email protected]
e-mail: [email protected] Kolkata 700 071
Tel: 033-44002572 / 3 / 4 Radhadaya Complex
L&T Construction Campus Fax: 033-22821025 / 7587 Old Padra Road
TC-1 Building, II Floor e-mail: [email protected] Near Charotar Society
Mount-Poonamallee Road Vadodara 390 007
Manapakkam A28, Indira Nagar, Faizabad Road Tel: 0265-6613610 / 1 / 2
Chennai 600 089 Lucknow 226 016 Fax: 0265-2336184
Tel: 044-2270 6800 Tel: 0522-4929905/04 e-mail: [email protected]
Fax: 044-22706940 Fax: 0522-2311671
e-mail: [email protected] e-mail: [email protected] 48-8-16, Dwarakanagar
Visakhapatnam 530 016
67, Appuswamy Road No: 73, Karpaga Nagar, 8th Street Tel: 0891 670 1125 to 30
Post Bag 7156 K. Pudur Fax: 0891 670 1139
Opp. Nirmala College Madurai 625 007 e-mail: [email protected]
Coimbatore 641 045 Tel: 0452-2537404, 2521068
Tel: 0422-2588120 / 1 / 5 Fax: 0452-2537552
Fax: 0422-2588148 e-mail: [email protected]
e-mail: [email protected]

Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.

Larsen & Toubro Limited


Electrical Standard Products