0% found this document useful (0 votes)
2 views

1wind & seismic

The document outlines the calculation of design wind pressure and seismic load for a residential building in Delhi, specifically a 50m high structure. It details the steps involved in determining wind load using IS-875 Part-3 and seismic load using IS-1893-2016, including factors such as regional wind speed, terrain, and building importance. Additionally, it provides formulas for calculating design wind speed, basic wind pressure, and seismic weight, along with considerations for load transfer in structural analysis.

Uploaded by

Shahsad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2 views

1wind & seismic

The document outlines the calculation of design wind pressure and seismic load for a residential building in Delhi, specifically a 50m high structure. It details the steps involved in determining wind load using IS-875 Part-3 and seismic load using IS-1893-2016, including factors such as regional wind speed, terrain, and building importance. Additionally, it provides formulas for calculating design wind speed, basic wind pressure, and seismic weight, along with considerations for load transfer in structural analysis.

Uploaded by

Shahsad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 17

Exercise:- Calculate Design wind pressure for Residential Building in Delhi, of 50 m height.

Consider this is the close

1. Wind Load:- (IS- 875 Part-3)

Step-1 Where as ,Vb = Regional Basic Wind Speed (m/s)


In any structure the wind speed is to be taken same as 10m height if structurte is less than or more than 10m height.
Step-2 K1= Probability risk factor.

Step-3 K2= Terrain & Height factor.

(Faraway = 50m radius)


(Closely = 10m radius)

Step-4 K3=Topograpy Factor

Step-5 K4 = Importance factor for Cyclone Region

Step-6 Where as Vz Design Wind Speed = Vb X K1 XK2 XK3 X K4 (Sec 6.3)

Step-7 Basic Wind Pressure atPzany


= 0.6
height
X Vz^2
= (Sec 7.2)

Step-8 Kd = Wind Directionality factor


(Plan area affecting factor)

Step-9 Ka = Wind tributory area facotr


(Elavation affecting factor)

Step-10 Kc = Combination factor

Step-11 Design Wind Pressure Pd= Kd X Ka X Kc X Pz

calculate the Final wind pressure for DELHI Consider this is the close
height),falls under K2TC

Regional basic wind speed for delhi Vb= Vb=


K1=
K2=
K3=
K4 =
Design Wind Speed = Vz= Vb X K1 X K2 X K3 X
Design Wind Speed = Vz=

Basic Wind Pressure Pz=

Kd =
Ka =
Kc =
Design Wind Pressure Pd=
Pd=

Step-12 Wind Load effects in building structures other than SWAY effect such as Concave & Convex effects to be
and as per Table -5 reduction or increment pressure coeffients to be applied before using Pd.

As per Table 5, For h/w = 2.5 and l/w = 1, the Local Cp means for Beams & Columns without wall surface
there fore Final Pressure for wall & Beams/columns (Pf) = 1.475

Step-13 Application of Wind Load:-


Note:- This Wind Pressure is to be multiplied by the wind force facing wide of beam or columns toget UD
But if RCC shear wall then wind loads to be shared to beams as well depends on its oneway or two way a
Exercise:- Calculate Design wind pressure for Residential Building in Delhi, of 50 m height.
Consider this is the closed square shaped residential building of size 20m long X 20m wide X50m height

2. Siesmic Load:- (IS- 1893-2016)

For example to calculate the siesmic loads of a fixed RCC Residential Building house balcony at Lucknow, 10m wide
Roof & Floor Beam =0.3X0.23, Columns=0.3*0.3, Roof & Floor Slabtk=0.1, Clay brick wall=0.23 wide, Clay brick wall
Step-1 Siesmic Weight of Building Sw :- F1
( Sw= 1.0 DL +0.25 LL for LL<=3 KN/m2 )
( Sw= 1.0 DL +0.50 LL for LL>3 KN/m2 )
DL:-
Columns + Ped = 36
Roof & Floor Beams= 138
Roof & Floor Slab= 500
Walls & Parapet = 693.68
FFL= 121.6
Slab Plastering 12mm thk= 24.48
Wall & Parapet Plastering 12 mm thk= 78.336
Total DL= 1592.096
LL 600

Siesmic Weight = Sw= 1742.096


Step-2 Design horizontal Siesmic Coefficient Ah= Z/2 * I/R*Sa/g
From Fig-1 zone map of IS 1893 , Lucknow falls under Zone-III
Zone factor Z for Zone -III of Lucknow location =
Importance Factor I =

Lucknow
is in Zone
III, So
SMRF to
be
Response Reduction Factor, R selected.

Fundamental natural vibration period of Structure T= 0.075 h^0.75 for RCC building, 0.085h^
T= 0.25
Average response acceleration coefficient Sa/g =

Design horizontal Siesmic Coefficient Ah= Z/2 * I/R*Sa/g

Therefore Ah=

Step-3 Base Shear Vb= Ah X Sw

There fore Vb = 70

This lateral force is tobe applied to the bottom of building box.


Since we need point load to apply to columns in our analysis,consider this load is distributed t
So, Point load at each column's top at beams joint = Vb/4 =

Step-4 Floor Wise Design Lateral Force Qi = Vb X (Swi*hi^2/ Swj*hj^2)


i= Actualfloor number

j=entire floor numbers.


Note : In Section 6.4.3.1 , MI of columns, Beams to be taken as 70% & 35% of MI respectivel

Exercise:-
Calculate the siesmic points loads floor wise of a RCC public assembly building without fixed s
Roof & Floor Beam =0.3X0.23, Columns=0.3*0.3, Roof & Floor Slabtk=0.1, brick wall=0.23 wid
ADVANCED LOAD TRASFER EXERCISE:-

Calculate the axial force, HF,BM at column bottom at GL of structure measuring 12m L X5m L X ht 9m.(3
with plinth beam and floor slab. Use 150mm for both plinth & roof slab thickness, column size 300X300m
Consider this building as residential hotel type, store room. Also consider services lo

List of Loads transferred to FDN:-


1.Axial Load reaction at GL of column due to Gravity loads from Slab, Beam, Column due to D
2. Horizontal forces like SF & 3. BM of Column only due to Wind & Siesmic
Note the BM of Beams & Slabs not being transferred to ground.
Consider this is the closed square shaped residential building of size 20m long X 20m wide X50m height ,falls under K2TC1 and located o

(From Basic Wind Speed map in Fig-1)


han 10m height.
(Table -1) K1 is Risk factor based on 50 years record of varrying wind speed.

(Table -2) TC-1=


TC-2=
TC-3=
TC-4=

( Sec 6.3.3.1) Hill If our construction ground has more than 3 degree inclination,then K3 =1.36
Plain If construction ground has less than 3 degree inclination,then K3 =1.0

(Sec.6.3.4) (For east coast of India & Gujarat west coast cyclone regions only)
All General structures in cyclone & all non clyclone case =
Industrial str in cyclone =
Post cyclone stay buildings (hosp,school) in cyc.zone

(Sec.7.2.1) (For Square, Rectangle, triangle plan shape structures in low cyclone zone Kd = 0.9,
(For Square, Rectangle, triangle plan shape structures in high cyclone zone Kd = 1.0,
(For Circular to near circular structures = 1.0)

(Table -4) (Depend on wind facing areas, ie max lateral wind facing dimention of the building)

(Sec.7.3.3.13) For frames that have combination of Partially closed and many openings, a pressure re
Rest all ONLY closed structure = Kc=1.0
(Sec 7.2) ( The value of Pd shall not be less than 0.7 X Pz)

Consider this is the closed rectangle shaped residential building of G+2 (15m long X 9m wide X10m
height),falls under K2TC4 and located on the hill with ground more than 3 degree inclination.

47 m/s (Fig-1 Map)


1 (Table -1)
1.39 (Table -2)
1 ( Sec 6.3.3.1)
1 (Sec.6.3.4)(Mumbai is not in cyclone zone)
Vz= Vb X K1 X K2 X K3 X K4
65.3 m/s

0.6 X Vz^2= 2561 N/m2

0.9 (Sec.7.2.1)(Rectangle Shape & Mumbai is not in cyclone zone)


0.8 (Table -4) (Max wind facing area = 15 X 10 = 150 m2)
1 (Sec.7.3.3. Fully Closed RCC building
KdXKaXKcXPz = 1844 N/m2
Convert to KN/m2 1.84 KN/m2

e & Convex effects to be considered


fore using Pd.

mns without wall surface use 0.8 as pressure coefficient. For Wall surfaces use max coefficient in A,B,C & D.
KN/m2

eam or columns toget UDL load. If brickwalls,wind loads wont transfer to beams.
n its oneway or two way actions.

X 20m wide X50m height ,falls under K2TC1 and located on the plain ground surface.

ny at Lucknow, 10m wide X 10m breadth X 3m height size, for medium soil type site.
0.23 wide, Clay brick wall Parapet(0.23mtk)=1m high, pedestal 1m.
F2
(From Sec 7.3.2 & Table-10)
(From Sec 7.3.2 & Table-10)

KN (Unit weight of RCC = 25 KN/m3 from IS 875-Part-1)


KN
KN
KN
KN Mortar = 81.6 KN
KN Tiles= 40 KN
KN
KN (Note here services load, equipments load, water tank load are not added)
KN (3KN/m2 * 10mX10m)

KN ( W= 1.0 DL +0.25 LL if LL <=3)


For Residential bldg house

for RCC building, 0.085h^0.75 for steel structures.


Secs ( Bldg ht = 1m+3m+1m)

0.04 4 % or magnitude or richter

KN

r this load is distributed to four columns on its top joint.


17.4 KN

i= Actualfloor number Swi*hi =Siesmic Weight of current floor box * height of current floor box from base.
Swj*hj = Siesmic Weight of total floor boxes * total height of building from base.
j=entire floor numbers.
& 35% of MI respectively during structural analysis for SMRF only.

y building without fixed seats at Delhi, 10m wide X 10m breadth X 9m height size(3floors), for medium soil type site.
=0.1, brick wall=0.23 wide, Parapet=1m, pedestal 1m.

g 12m L X5m L X ht 9m.(3floors), (Consider 4 columns at the corners only)


ss, column size 300X300mm, Clay burnt Brick Wall & 1m high Parapet thickness=0.23m, 1.5 m pedestal height, both plinth and roof beam
Also consider services load of 2KN/m2 over slab, Consider this building is located in Culcutta in K2TC-2, with loose soil type, construction

, Beam, Column due to DL+LL+FFL+Serv.L+Eqp.L


tial building of size 20m long X 20m wide X50m height ,falls under K2TC1 and located on the plain ground surface.

(Sec 6.2)
K1 is Risk factor based on 50 years record of varrying wind speed.

Scattered buildings of less than 1.5m ht far away to our building.


Scattered buildings of 1.5-10m ht far away to our building.
Closely arranged buildings of 1.5-10m ht to our building and someare more than 10m ht.
Closely arranged high rise buildings more than 10m ht to our building .

If our construction ground has more than 3 degree inclination,then K3 =1.36


If construction ground has less than 3 degree inclination,then K3 =1.0

(For east coast of India & Gujarat west coast cyclone regions only)
All General structures in cyclone & all non clyclone case = 1
Industrial str in cyclone = 1.15
Post cyclone stay buildings (hosp,school) in cyc.zone 1.3

(For Square, Rectangle, triangle plan shape structures in low cyclone zone Kd = 0.9,
(For Square, Rectangle, triangle plan shape structures in high cyclone zone Kd = 1.0,
(For Circular to near circular structures = 1.0)

(Depend on wind facing areas, ie max lateral wind facing dimention of the building)

For frames that have combination of Partially closed and many openings, a pressure reduction factor Kc= 0.9
Rest all ONLY closed structure = Kc=1.0
e less than 0.7 X Pz)

ential building of G+2 (15m long X 9m wide X10m


with ground more than 3 degree inclination.

for K2, 50 m height, and building class B, from Table 2


Plane ground
(Mumbai is not in cyclone zone)

(This Unit of N/m2 is given in Sec 7.2)

(Rectangle Shape & Mumbai is not in cyclone zone) For rectangle shape bldg
(Max wind facing area = 15 X 10 = 150 m2)
Fully Closed RCC building
(This Unit of N/m2 is given in Sec 7.2) 72 %

cient. For Wall surfaces use max coefficient in A,B,C & D.

oads wont transfer to beams.

ated on the plain ground surface.

ht size, for medium soil type site.


h, pedestal 1m.

/m3 from IS 875-Part-1)

uipments load, water tank load are not added)


(From IS 875-Part-2)

(From Table-10)
(6.4.2)
0.16 (Table-3)
1 (Table-8)

5.0 (Table -9)

(Clause 7.6.2)
(Soil Type to be referered from Soil analysis report & Table-4)
2.5 (From Fig-2, 2A)

(6.4.2)

gnitude or richter

(7.6.1)

(7.6.3)
esmic Weight of current floor box * height of current floor box from base.
Siesmic Weight of total floor boxes * total height of building from base.

is for SMRF only. Info

10m breadth X 9m height size(3floors), for medium soil type site.

mns at the corners only)


& 1m high Parapet thickness=0.23m, 1.5 m pedestal height, both plinth and roof beam size 300mmX250mm.
Consider this building is located in Culcutta in K2TC-2, with loose soil type, construction ground has plain.
Faraway = 50 m radius
closely = 10 m radius
As per IS 13920,

For Zone 3,4,5 SMRF to be selected.


For Zone 2 OMRF to be selected.
h= height of total structure from base/fdn.

For T=0.25 sec & for medium soil type

You might also like