Continuous Under-Frequency Load Shedding Scheme for Power System Adaptive Frequency Control
Continuous Under-Frequency Load Shedding Scheme for Power System Adaptive Frequency Control
2, MARCH 2020
Abstract—Frequency drop due to loss of massive generation is a to recover frequency in under-frequency scenarios is under-
threat to power system frequency stability. Under-frequency load frequency load shedding (UFLS) which rebalances generation
shedding (UFLS) is the principal measure to prevent successive and load by shedding appropriate amount of loads.
frequency declination and blackouts. Based on traditional stage-by-
stage UFLS scheme, a new continuous UFLS scheme is proposed UFLS can be generally classified into three categories: tra-
in this paper to shed loads proportional to frequency deviation. ditional stage-by-stage scheme, adaptive scheme, and semi-
The characteristic of the proposed scheme is analyzed with a adaptive scheme [6]. The major difference between the three
closed-form solution of frequency dynamics. Frequency threshold schemes lies in the method to determine load shedding amount.
and time delay are added to make the proposed scheme practical. For the stage-by-stage scheme, the loads to shed are predefined
A line-by-line scheme based on precise load control is introduced
to implement the continuous scheme for systems without enough and divided into several stages. Each stage is tripped when
continuously controllable loads. The load shedding scale factor of frequency drops beyond a certain threshold for a few seconds.
the proposed scheme is tuned with an analytical method to achieve It sheds loads based on local frequency and is widely used in
adaptability to different operating conditions. The adaptability of utilities [7]. Difference between the frequency thresholds of
the proposed scheme is validated with 39-bus New England model stages must be set to overcome oscillation between generators.
and simplified Shandong Power Grid of China.
The typical frequency difference between stages is 0.2∼0.25 Hz,
Index Terms—Power systems, frequency stability, under- and 5∼8 stages are usually set. The time delay is adaptively
frequency load shedding (UFLS), continuous control, precise load adjusted according to frequency dynamics in [8] to improve
control.
scheme adaptability. In [9] and [10], the stage-by-stage scheme
is optimized with trigger signal of both frequency deviation and
I. INTRODUCTION rate of change of frequency (ROCOF). Uncertainty of system
REQUENCY is an essential index of balance between parameters is considered in [11] to tune more adaptive scheme.
F active power generation and load. Frequency will drop if
active power generation is inadequate due to loss of generation in
Though the stage-by-stage scheme can be tuned for better adapt-
ability, the limited stages and inherent discreteness make it hard
large-scale power systems [1] or microgrids [2]. Large frequency to set up a scheme suitable for all possible operating condi-
excursion may lead to system blackouts and restoration failure tions. Over-shedding or under-shedding problem can hardly be
[3]. Systems with more integration of intermittent renewable avoided for the stage-by-stage scheme [12].
generation are more vulnerable to frequency deviation [4], [5]. For the adaptive scheme, the loads to shed are calculated
It is compulsory to arrest frequency declination for preventing online based on ROCOF of the center of inertia (COI). It is
power systems from severe consequences. The key technique derived from the fact that the initial ROCOF of COI is pro-
portional to power imbalance [13]. Therefore, loads equal to
the product of ROCOF and system inertia are shed to balance
Manuscript received October 20, 2018; revised April 19, 2019 and July 21, generation and load in one shot. In [14], load shedding amount
2019; accepted September 5, 2019. Date of publication September 26, 2019;
date of current version February 26, 2020. This work was supported in part by is distributed to different loads considering voltage stability
National Key R&D Program of China under Grant 2017YFB0902600, in part and power tracing criteria. The adaptive scheme is improved
by National Science Foundation of China under Grant 51407107, and in part by in [15] considering change of power generation during load
Young Scholars Program of Shandong University under Grant 2018WLJH31.
Paper no. TPWRS-01600-2018. (Corresponding author: Yutian Liu.) shedding process. The difference between measured ROCOF
C. Li, Y. Wu, Y. Sun, H. Zhang, and Y. Liu are with the Key Laboratory and threshold of ROCOF is adopted in [16] for determining
of Power System Intelligent Dispatch and Control of the Ministry of Educa- appropriate load shedding amount. The calculation of ROCOF
tion, Shandong University, Jinan 250061, China (e-mail: [email protected].
cn; [email protected]; [email protected]; [email protected]; of COI requires wide area measurement data from different
[email protected]). locations. Communication channels with high availability are
Yilu Liu is with the Department of Electrical Engineering and Computer Sci- prerequisite of the adaptive scheme for estimating power imbal-
ence, University of Tennessee, Knoxville, TN 37996 USA (e-mail: [email protected]).
V. Terzija is with the School of Electrical and Electronic Engineer- ance and sending load shedding command. Biased estimation
ing, The University of Manchester, Manchester, M60 1QD, U.K. (e-mail: of ROCOF or system inertia further prevents it from industrial
[email protected]). applications.
Color versions of one or more of the figures in this article are available online
at http://ieeexplore.ieee.org. Semi-adaptive scheme adopts both ROCOF and frequency
Digital Object Identifier 10.1109/TPWRS.2019.2943150 deviation to determine loads to shed [17]. It can be treated as a
0885-8950 © 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: National Institute of Technology Andhra Pradesh. Downloaded on September 15,2022 at 04:34:13 UTC from IEEE Xplore. Restrictions apply.
LI et al.: CONTINUOUS UFLS SCHEME FOR POWER SYSTEM ADAPTIVE FREQUENCY CONTROL 951
Authorized licensed use limited to: National Institute of Technology Andhra Pradesh. Downloaded on September 15,2022 at 04:34:13 UTC from IEEE Xplore. Restrictions apply.
952 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 35, NO. 2, MARCH 2020
following frequency-domain equation: where M is a constant scale factor between Δfmin and PD :
λ1
−RPD ωn2 1 + TR s R c1 −c1 λ2 −λ1
Δf (s) = (2) M= − −1
De (s2 + 2δωn s + ωn2 ) s De λ1 c2
where De is equivalent damping, ω n is natural oscillation fre- λ2
quency and δ is damping ratio. De , ω n , and δ are defined as: c2 −c1 λ2 −λ1
+ −1 (9)
⎧ λ2 c2
⎪
⎪ De = Km + (D + KLS ) R
⎨ Therefore, the total load shedding amount is:
ωn2 = 2HRT
De
(3)
⎪
⎪
R
PΣLS = −KLS Δfmin = −KLS M PD = CPD (10)
⎩ δ = 2HR+(D+KLS )RTR +Km FH TR ω
2De n
where C is:
In [18], the analytic time-domain expression of Δf was λ1
Authorized licensed use limited to: National Institute of Technology Andhra Pradesh. Downloaded on September 15,2022 at 04:34:13 UTC from IEEE Xplore. Restrictions apply.
LI et al.: CONTINUOUS UFLS SCHEME FOR POWER SYSTEM ADAPTIVE FREQUENCY CONTROL 953
Fig. 3. The relationship between load shedding factor C and KLS . Fig. 5. Frequency response with different frequency thresholds.
Authorized licensed use limited to: National Institute of Technology Andhra Pradesh. Downloaded on September 15,2022 at 04:34:13 UTC from IEEE Xplore. Restrictions apply.
954 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 35, NO. 2, MARCH 2020
Authorized licensed use limited to: National Institute of Technology Andhra Pradesh. Downloaded on September 15,2022 at 04:34:13 UTC from IEEE Xplore. Restrictions apply.
LI et al.: CONTINUOUS UFLS SCHEME FOR POWER SYSTEM ADAPTIVE FREQUENCY CONTROL 955
Authorized licensed use limited to: National Institute of Technology Andhra Pradesh. Downloaded on September 15,2022 at 04:34:13 UTC from IEEE Xplore. Restrictions apply.
956 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 35, NO. 2, MARCH 2020
To shed the precise amount of loads, it requires frequency To deeper look into the effect of varying damping on system
measurement devices with high accuracy. Secondly, results in frequency control, a load model with frequency dependency and
Fig. 3 indicate that the total load shedding amount is not sensitive load shedding is considered as:
to the change of KLS when KLS is great enough. It is reasonable
PL = PL0 (1 + DΔf ) (1 − PΣLS ) (26)
to select KLS as little as possible while preventing the system
from frequency instability. Thirdly, tmin is usually quite small for where PL is load power and PL0 is nominal load power. With
specific events. If the continuous UFLS scheme is implemented initial nominal load power as base power, PL0 is 1.0 p.u.
with controllable loads, loads need to change greatly in a short When there is no spinning reserve and frequency threshold
time if KLS is too great. It may be impossible for some devices of and additional stage are not considered, the power balance can
which the maximum power change rate is limited by controllers. be modeled as following which is similar to (19):
(1 − PD max ) − (1 + KLS Δfmin ) (1 + DΔfmin ) = 0 (27)
B. Tuning of KLS With Constant Damping
and KLS can be derived as:
It can be readily concluded that the frequency would drop
most if the power imbalance is PDmax when there is no spinning −PD max − DΔfmin
KLS = (28)
reserve. Without spinning reserve, the system minimum fre- Δfmin (1 + DΔfmin )
quency Δfmin is equal to the residual frequency Δf . Therefore, If frequency threshold is further considered when there is no
if no additional stage is considered, the power balance equation spinning reserve, power balance at tmin is:
when the system is stabilized can be modeled as:
(1 − PD max)−[1 + KLS (Δfmin − Δfth )](1 + DΔfmin ) = 0
(1 − PDmax ) − (1 + KLS Δfmin ) − DΔfmin = 0 (19) (29)
or If the additional stage is shed, power balance when the residual
PD max frequency is reached is modeled as:
KLS = − −D (20)
Δfmin (1 − PD max ) − [1 + KLS (Δfmin − Δfth ) + DΔfth ]
If the frequency threshold and additional stage are further (1 + DΔf∞ ) = 0 (30)
considered, the minimum frequency before the additional stage
is shed can be calculated with: From (29), the following relationship can be found:
1 − PD max
(1 − PD max ) − [1 + KLS (Δfmin − Δfth )] − DΔfmin = 0 1 + KLS (Δfmin − Δfth ) = (31)
(21) 1 + DΔfmin
After the additional stage is shed, the power balance when the Substitute (31) into (30), the minimum frequency is
residual frequency is reached is: obtained as:
(1 − PD max ) − [1 + KLS (Δfmin − Δfth ) + DΔfth ] Δf∞ (1 − PD max ) + Δfth (1+DΔf∞ )
Δfmin = (32)
(1 − PD max ) − DΔfth (1 + DΔf∞ )
− DΔf∞ = 0 (22)
Substitute (32) into (29), KLSmin can be obtained with
From (21) and (22), it can be calculated that, Δf = Δfth as:
Δfmin = Δfth + Δf∞ (23) PD max + DΔfmin
KLSmin = − (33)
Substitute (23) into (21), the KLS can be obtained as: (Δfmin − Δfth ) (1 + DΔfmin )
Authorized licensed use limited to: National Institute of Technology Andhra Pradesh. Downloaded on September 15,2022 at 04:34:13 UTC from IEEE Xplore. Restrictions apply.
LI et al.: CONTINUOUS UFLS SCHEME FOR POWER SYSTEM ADAPTIVE FREQUENCY CONTROL 957
TABLE I
STAGE-BY-STAGE UFLS SCHEME OF 39-BUS NEW ENGLAND MODEL
Fig. 13. Generator tripping events of New England model with 10% spinning
reserve.
1000 MW, and 1830 MW. The same events with 10% spinning
reserve are shown in Fig. 13. Nominal frequency and frequency
threshold are shown in the two figures as dotted lines.
Fig. 12. Generator tripping events of New England model with no spinning From Figs. 12 and 13, it can be found that both stage-by-stage
reserve. and continuous scheme can bring system frequency back. How-
ever, in the zero spinning reserve scenario, system frequency will
recover to greater than 60 Hz for the event of tripping 830 MW
simulations and is validated in Section V. A greater α can be generation with the stage-by-stage scheme. Therefore, though
selected to increase KLS if the frequency nadir is too low. the stage-by-stage scheme is well tuned, it still suffers from
the over-shedding problem. The proposed continuous UFLS
V. CASE STUDIES scheme, however, provides far better performance than the stage-
by-stage scheme without any over-shedding problems.
The general performance of the proposed UFLS scheme is
Fig. 12 shows that the recovery speed of the frequency is
analyzed in Sections II and III with the simplified model. It is
relatively slow for the event of tripping 1830 MW generation
worthwhile to check the actual performance of the proposed
with the proposed scheme. A greater KLS can be selected to avoid
scheme with detailed models. In this section, two systems are
starting under-frequency protections of some power plants. Re-
built with detailed models and tested with full time-domain
covery speed can also be increased by adding other action logic
simulation. One is 60 Hz 39-bus New England model, and the
to accelerate the operation of the additional stage according to
other is 50 Hz simplified Shandong Power Grid of China. System
the under-frequency protections of power plants.
damping is modeled as load frequency dependency in the two
To further check the voltage and angle stability, voltage and
systems. Therefore, KLS is tuned as Section IV-C.
angle dynamics of the event of tripping generator 38 in Fig. 13
are illustrated in Fig. 14. It is shown that the voltage deviation
A. Tests of New England Model
is small and system is angular stable.
In the New England model, the total load is 6150 MW and total The tuned continuous UFLS scheme is further implemented as
generating capacity is 7300 MVA. All generators are modeled three line-by-line schemes with 100, 50 and 20 low-voltage lines,
with 6-order GENROU generator model, IEEET1 exciter model, i.e., each line uniformly carries 1%, 2%, and 5% of substation
and IEEEG1 turbine-governor model [26]. Since load model is loads, respectively. The frequency response of the same events
critical for power system dynamics [27], static IEELAL model as Fig. 13 are illustrated in Fig. 15 to compare the line-by-line
with voltage and frequency dependency is used to model loads scheme with the continuous scheme. It can be found from Fig. 15
with typical parameters. The greatest power mismatch with N-2 that though the line-by-line scheme is discrete, the three schemes
contingency is 1830 MW when tripping equivalent generators implemented with precise load control can bring frequency back
at bus 38 and 39. With system total load as base power, system with similar performance as the continuous scheme.
D is 2.0, system R is 0.0421, and PDmax is 0.2975 pu. Δfth To further check the adaptability of the continuous scheme,
is set as –0.5 Hz which is the activating frequency of the first another continuous scheme is tuned as KLS = 28.790 with α =
stage of the stage-by-stage scheme. Thus, KLSmin is calculated 0.2, i.e., shedding 47.984% load per Hz. Results of the two
as 23.992 with (33). Final KLS is tuned as 25.192 with α = 0.05, schemes with KLS = 25.192 and KLS = 28.790 are shown in
i.e., shedding 41.987% load per Hz. The additional stage is set Fig. 16 with the same events as in Fig. 15. The scheme with
as Padd = –DΔfth = 0.0167 pu or 102.5 MW. Time delay for the KLS = 28.790 sheds loads slightly more than the scheme with
continuous part is td = 0.2 s, and time delay for the additional KLS = 25.192 and reduce maximum frequency deviation by
stage is tadd = 10 s. The traditional stage-by-stage UFLS scheme about 0.04 Hz. The performance of the proposed continuous
is listed in Table I [24] for comparison. scheme is tolerant to change of α.
COI frequency of tripping generator 38, generator 39, and The proposed UFLS scheme is dependent on frequency dy-
tripping the two generators is shown in Fig. 12 with no spinning namics which is affected by system inertia. To check the perfor-
reserve. Loss of generation of the three events are: 830 MW, mance of the proposed scheme with different inertia, the New
Authorized licensed use limited to: National Institute of Technology Andhra Pradesh. Downloaded on September 15,2022 at 04:34:13 UTC from IEEE Xplore. Restrictions apply.
958 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 35, NO. 2, MARCH 2020
TABLE II
STAGE-BY-STAGE UFLS SCHEME OF SHANDONG POWER GRID
Fig. 14. Voltage and rotor angle dynamics of New England model with
continuous scheme when generator 38 is tripped.
Authorized licensed use limited to: National Institute of Technology Andhra Pradesh. Downloaded on September 15,2022 at 04:34:13 UTC from IEEE Xplore. Restrictions apply.
LI et al.: CONTINUOUS UFLS SCHEME FOR POWER SYSTEM ADAPTIVE FREQUENCY CONTROL 959
Authorized licensed use limited to: National Institute of Technology Andhra Pradesh. Downloaded on September 15,2022 at 04:34:13 UTC from IEEE Xplore. Restrictions apply.
960 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 35, NO. 2, MARCH 2020
conditions. With precise load control, the continuous scheme can [22] W. Yin et al., “Design of fast communication interface for precision load
be implemented as the line-by-line scheme which can achieve control system,” Autom. Elect. Power Syst., vol. 42, no. 10, pp. 143–149,
2018.
similar performance as the continuous scheme. [23] H. Huang and F. Li, “Sensitivity analysis of load-damping characteristic
in power system frequency regulation,” IEEE Trans. Power Syst., vol. 28,
no. 2, pp. 1324–1335, May 2013.
REFERENCES [24] Northeast Power Coordinating Council, “NPCC regional reliabil-
ity reference directory #12 under-frequency load shedding pro-
[1] Y. Wen, C. Y. Chung, and X. Ye, “Enhancing frequency stability of gram requirements,” Accessed: Oct. 17, 2018. [Online]. Avail-
asynchronous grids interconnected with HVDC links,” IEEE Trans. Power able: https://www.npcc.org/Standards/Directories/Directory12%20Full%
Syst., vol. 33, no. 2, pp. 1800–1810, Mar. 2018. 20Member%20clean%2020150330%20GJD.pdf
[2] P. Ferraro, E. Crisostomi, R. Shorten, and F. Milano, “Stochastic frequency [25] Y. Liu and C. Li, “Impact of large-scale wind penetration on transient
control of grid-connected microgrids,” IEEE Trans. Power Syst., vol. 33, frequency stability,” in Proc. IEEE Power Energy Soc. Gen. Meeting, San
no. 5, pp. 5704–5713, Sep. 2018. Diego, CA, USA, 2012, pp. 1–5.
[3] Y. Liu, R. Fan, and V. Terzija, “Power system restoration: A literature [26] “PSS/E model library V33.5,” Siemens, Munich, Germany, Oct. 2013.
review from 2006 to 2016,” J. Modern Power Syst. Clean Energy, vol. 4, [27] V. Milanovic et al., “CIGRE WG C4.605: Modelling and aggregation
no. 3, pp. 332–341, 2016. of loads in flexible power networks,” Feb. 2014. Accessed: Apr. 10,
[4] N. Nguyen and J. Mitra, “An analysis of the effects and dependency of 2019. [Online]. Available: https://e-cigre.org/publication/566-modelling-
wind power penetration on system frequency regulation,” IEEE Trans. and-aggregation-of-loads-in-flexible-power-networks
Sustain. Energy, vol. 7, no. 1, pp. 354–363, Jan. 2016.
[5] H. Golpîra, H. Seifi, A. R. Messina, and M. Haghifam, “Maximum penetra-
tion level of micro-grids in large-scale power systems: Frequency stability
viewpoint,” IEEE Trans. Power Syst., vol. 31, no. 6, pp. 5163–5171, Changgang Li (M’15) received the B.E. and Ph.D.
Nov. 2016. degrees in electrical engineering from Shandong Uni-
[6] B. Delfino, S. Massucco, A. Morini, and M. Haghifam, “Implementation versity, Jinan, China, in 2006 and 2012, respectively.
and comparison of different under frequency load-shedding schemes,” in He was a Research Scholar with the School of Electri-
Proc. Power Eng. Soc. Summer Meeting, Vancouver, BC, Canada, 2001, cal Engineering and Computer Science, The Univer-
pp. 307–312. sity of Tennessee, Knoxville, TN, USA, from 2012 to
[7] IEEE Guide for the Application of Protective Relays Used for Abnormal 2014. He is currently an Associate Research Fellow
Frequency Load Shedding and Restoration, IEEE Standard C37.117-2007, with the School of Electrical Engineering, Shandong
Aug. 24, 2007, pp. 1–55. University. His research interest includes power sys-
[8] X. Lin, H. Weng, Q. Zou, and P. Liu, “The frequency closed-loop control tem operation and control.
strategy of islanded power systems,” IEEE Trans. Power Syst., vol. 23,
no. 2, pp. 796–803, May 2008.
[9] L. Sigrist, I. Egido, and L. Rouco, “A method for the design of UFLS
schemes of small isolated power systems,” IEEE Trans. Power Syst.,
vol. 27, no. 2, pp. 951–958, May 2012
[10] L. Zhang and J. Zhong, “UFLS design by using F and integrating DF/DT,”
in Proc. IEEE PES Power Syst. Conf. Expo., Atlanta, GA, USA, 2006, Yue Wu received the B.E. degree in electrical en-
pp. 1840–1844. gineering from Zhengzhou University, Zhengzhou,
[11] T. Amraee, M. G. Darebaghi, A. Soroudi, and A. Keane, “Probabilistic China, in 2018. He is currently working toward the
under frequency load shedding considering RoCoF relays of distributed postgraduate degree with Shandong University, Jinan,
generators,” IEEE Trans. Power Syst., vol. 33, no. 4, pp. 3587–3598, China. His research interest includes power system
Jul. 2018. dynamic frequency control.
[12] L. Sigrist, I. Egido, and L. Rouco, “Performance analysis of UFLS schemes
of small isolated power systems,” IEEE Trans. Power Syst., vol. 27, no. 3,
pp. 1673–1680, Aug. 2012.
[13] V. V. Terzija, “Adaptive underfrequency load shedding based on the
magnitude of the disturbance estimation,” IEEE Trans. Power Syst., vol. 21,
no. 3, pp. 1260–1266, Aug. 2006.
[14] T. Shekari, F. Aminifar, and M. Sanaye-Pasand, “An analytical adaptive
load shedding scheme against severe combinational disturbances,” IEEE
Trans. Power Syst., vol. 31, no. 5, pp. 4135–4143, Sep. 2016. Yanli Sun received the B.E. and M.E. degrees in elec-
[15] A. Ketabi and M. H. Fini, “An underfrequency load shedding scheme for trical engineering from Shandong University, Jinan,
hybrid and multiarea power systems,” IEEE Trans. Smart Grid, vol. 6, China, in 2015 and 2018, respectively. She is currently
no. 1, pp. 82–91, Jan. 2015. an Engineer with State Grid Shandong Electric Power
[16] L. Sigrist, I. Egido, and L. Rouco, “Principles of a centralized UFLS Corporation Weifang Power Supply Company, China.
scheme for small isolated power systems,” IEEE Trans. Power Syst., Her research interests include power system analysis
vol. 28, no. 2, pp. 1779–1786, May 2013. and control.
[17] P. M. Anderson and M. Mirheydar, “An adaptive method for setting
underfrequency load shedding relays,” IEEE Trans. Power Syst., vol. 7,
no. 2, pp. 647–655, May 1992.
[18] P. M. Anderson and M. Mirheydar, “A low-order system frequency re-
sponse model,” IEEE Trans. Power Syst., vol. 5, no. 3, pp. 720–729,
Aug. 1990.
[19] Y. Xie et al., “Development approach of a programmable and open
software package for power system frequency response calculation,” Pro- Hengxu Zhang (M’06) received the B.E., M.S.,
tection Control Modern Power Syst., vol. 2, pp. 189–198, 2017. and Ph.D. degrees in electrical engineering from
[20] M. A. Torres L., L. A. C. Lopes, L. A. Morán T., and J. R. Espinoza C., Shandong University, Jinan, China, 1998, 2000, and
“Self-tuning virtual synchronous machine: A control strategy for energy 2003, respectively. He is currently a Professor with
storage systems to support dynamic frequency control,” IEEE Trans. the School of Electrical Engineering, Shandong Uni-
Energy Convers., vol. 29, no. 4, pp. 833–840, Dec. 2014. versity. His research interests include power system
[21] S. Acharya, M. S. E. Moursi, and A. Al-Hinai, “Coordinated frequency security and stability assessment, power system mon-
control strategy for an islanded microgrid with demand side management itoring, and numerical simulation.
capability,” IEEE Trans. Energy Convers., vol. 33, no. 2, pp. 639–651,
Jun. 2018.
Authorized licensed use limited to: National Institute of Technology Andhra Pradesh. Downloaded on September 15,2022 at 04:34:13 UTC from IEEE Xplore. Restrictions apply.
LI et al.: CONTINUOUS UFLS SCHEME FOR POWER SYSTEM ADAPTIVE FREQUENCY CONTROL 961
Yutian Liu (SM’96) received the B.E. and M.S. de- Vladimir Terzija (M’95–SM’00–F’16) has been the
grees from the Shandong University of Technology, EPSRC Chair Professor in power system engineering
Jinan, China, in 1984 and 1990, respectively, and the with the School of Electrical and Electronic Engineer-
Ph.D. degree from Xi’an Jiaotong University, Xi’an, ing, The University of Manchester, Manchester, U.K.,
China, in 1994, all in electrical engineering. He is cur- since 2006. From 1997 to 1999, he was an Assistant
rently a Chair Professor with the School of Electrical Professor with the University of Belgrade, Serbia.
Engineering, Shandong University, Jinan, China. His From 2000 to 2006, he was with ABB AG, Germany,
research interests include power system analysis and working as an Expert for switchgear and distribution
control, renewable energy integration, and artificial automation. His research interests include smart grid,
intelligence application to power system. application of intelligent methods to power system
monitoring, control, and protection, switchgear and
fast transient processes, as well as DSP applications in power systems.
Authorized licensed use limited to: National Institute of Technology Andhra Pradesh. Downloaded on September 15,2022 at 04:34:13 UTC from IEEE Xplore. Restrictions apply.