Shop Drawing V3 - Ginza PENTHOUSE PIK 2 Project 20250126
Shop Drawing V3 - Ginza PENTHOUSE PIK 2 Project 20250126
PENGADAAN DAN
PEMASANGAN ELEVATOR
MEREK IFE DI GINZA
PENTHOUSE PIK 2
DRAWING
NO. DRAWING NAME SCALE
REF. NO. Salembaran Jati, Kosambi, Tangerang Regency,
Banten 15214
TASK ASSIGNER:
01 LIFT-001 TABLE OF CONTENTS NTS
PT. CITRA ABADI MANDIRI
PIK 2
02 LIFT-002 ELEVATOR SYSTEM PARAMETERS NTS
APPROVED BY:
03 LIFT-101 PENTHOUSE CIVIL WORK CONSTRUCTION PLAN 1:50
CONSTRUCTION MANAGEMENT:
04 LIFT-201 PENTHOUSE ELEVATOR TYPE A PLAN 1:50, 1:10
APPROVED BY:
PT. MAXWELL
NATANINDO GLOBAL
ICE Business Park D03, Jl. BSD Grand Boulevard,
Pagedangan, Tangerang, Banten 15339
Tel: +62 21 2223 2613
APPROVED BY:
MANUFACTURER:
IFE ELEVATORS
CO., LTD.
Jinlong Road, Jinlong Industrial Park, Qingxi, Dong Guan
City, Guang Dong Province, P. R. China, 523660
Tel: +86 769 8207 8888, Fax: +86 769 8773 2448
APPROVED BY:
V1 2025/01/17 DRAFT W. Y.
DRAWING CONTENT:
TABLE OF CONTENTS
IFE PROJECT
PRJ2400024030
REFERENCE NUMBER
ELEVATOR / ESCALATOR
SHOP DRAWING
SIZE SCALE DRAWING REFERENCE NO. NO.
PENGADAAN DAN
PEMASANGAN ELEVATOR
MEREK IFE DI GINZA
GENERAL REQUIREMENT TO CIVIL WORK CONSTRUCTION - BY OTHERS
ELEVATOR SPECIFICATION & DATA PENTHOUSE PIK 2
ELEVATOR ID PENTHOUSE 1. THE COLUMNS AND BEAMS DESIGNED BY THE ELEVATOR CONTRACTOR IN Salembaran Jati, Kosambi, Tangerang Regency,
ELEVATOR TYPE VILLUX PRO Banten 15214
THIS SET OF DRAWINGS ARE SOLELY INTENDED TO EXPRESS THE POSITION AND
QUANTITY 44 TASK ASSIGNER:
ROPING 2:1 THE DESIGN OF EACH COLUMN AND BEAM, INCLUDING CONCRETE
FLOOR / STOP / OPENING 5/5/5 REINFORCEMENT AND STEEL BEAM DIMENSIONS, IN ACCORDANCE WITH THE APPROVED BY:
QUANTITY OF CAR ENTRANCE 1 (NO CAR DOOR) LOAD REQUIREMENTS PROPOSED BY THE ELEVATOR CONTRACTOR, AND
CAR INTERNAL WIDTH 1000 GENERATE / SUPPLEMENT CORRESPONDING STRUCTURAL DRAWINGS FOR CONSTRUCTION MANAGEMENT:
DOOR OPENING MANUAL SWING HEIGHT MUST NOT EXCEED ±20 MM.
CONTROL SYSTEM CTRL 80 + ARD CIVIL WORK CONTRACTOR:
PT. MAXWELL
COUNTERWEIGHT GUIDE RAIL TK5A
CAR BUFFER TYPE HC-B-2 FREE FROM PROTRUSIONS BEFORE ELEVATOR INSTALLATION. NATANINDO GLOBAL
ICE Business Park D03, Jl. BSD Grand Boulevard,
CAR BUFFER STROKE 30 Pagedangan, Tangerang, Banten 15339
Tel: +62 21 2223 2613
CWT BUFFER TYPE HC-B-2 5. THE ELEVATOR HOISTWAY MUST BE ADEQUATELY VENTILATED AND SHOULD APPROVED BY:
CWT BUFFER STROKE 30 NOT BE USED TO VENTILATE ROOMS OTHER THAN THOSE CONNECTED TO THE
CAR WEIGHT 400 KG ELEVATOR. IN THE ABSENCE OF RELEVANT REGULATIONS OR STANDARDS, IT IS MANUFACTURER:
CAR INTERIOR ALLOWANCE 0 KG RECOMMENDED TO PROVIDE VENTILATION OPENINGS AT THE TOP OF THE IFE ELEVATORS
COUNTERWEIGHT WEIGHT 600 KG CO., LTD.
HOISTWAY, COVERING A MINIMUM AREA OF 1% OF THE HOISTWAY'S HORIZONTAL Jinlong Road, Jinlong Industrial Park, Qingxi, Dong Guan
COUNTERWEIGHT SIZE 400 x 165 City, Guang Dong Province, P. R. China, 523660
SECTION. Tel: +86 769 8207 8888, Fax: +86 769 8773 2448
BALANCING 45% APPROVED BY:
V1 2025/01/17 DRAFT
W. Y.
W. Y.
R1, HITCH BEAM SUPPORT MACHINE SIDE 2. THE POWER SUPPLY SHOULD OPERATE WITHIN A TOLERANCE RANGE OF 380 DRAWING CONTENT:
R2, HITCH BEAM SUPPORT CAR SIDE VAC ± 7% / 50HZ ± 5% (FOR PARKING BUILDING LIFT) OR 220 VAC ± 7% / 50HZ ± 5% ELEVATOR SYSTEM
R3, CAR BUFFER PLINTH 25 KN (FOR PENTHOUSE LIFT). IF THE POWER SUPPLY VOLTAGE FLUCTUATES BEYOND PARAMETERS &
R4, CWT BUFFER PLINTH 41 KN THIS TOLERANCE RANGE, A STABILIZER MUST BE INSTALLED. GENERAL PROVISIONS
R5, CAR GUIDE RAIL IN PIT 12 KN
R6, CWT GUIDE RAIL IN PIT 3. PROVISION OF PROPER ELECTRICAL GROUNDING INSIDE THE POWER
R7, HITCH BEAM SUPPORT CWT SIDE IFE PROJECT
PRJ2400024030
DISTRIBUTION PANEL WITH SPECIFICATIONS MEETING A RESISTANCE LEVEL OF REFERENCE NUMBER
ELEVATOR / ESCALATOR
LESS THAN 4 Ω. SHOP DRAWING
SIZE SCALE DRAWING REFERENCE NO. NO.
400
B5
C C MEREK IFE DI GINZA
HOOK PENTHOUSE PIK 2
CAP. > 10 KN
650
2 2
1300
C1 B3
1050
C1 Salembaran Jati, Kosambi, Tangerang Regency,
B2 Banten 15214
150
R5
R5
HOISTWAY DEPTH 1950
OVERHEAD 3310
B3
TASK ASSIGNER:
B2
200
3600
150
PT. CITRA ABADI MANDIRI
1100
1300
R4
4000
3000
PIK 2
R3
R3
1100
1300
CUTOUT HEIGHT 2230
B2
200
APPROVED BY:
B2
200
1000
C1 CONSTRUCTION MANAGEMENT:
1300
C1 C1
05
05
C1
FLOOR R
110 CUTOUT 960 80 80 CUTOUT 960 110 FFL+17.000
1050
1300
HOISTWAY WIDTH 1150 HOISTWAY WIDTH 1150
400
FLOOR 3
TYPE A (RIGHT OPENING) TYPE B (LEFT OPENING) FFL+9.000 APPROVED BY:
400
1400
1100
CIVIL WORK CONTRACTOR:
1300
950
B3
B2
200
150
B3 B2
4000
200
APPROVED BY:
150
150
150
B3
1150
1350
4000
ELEVATOR / ESCALATOR CONTRACTOR:
1100
1300
PT. MAXWELL
CUTOUT HEIGHT 2230
200
ICE Business Park D03, Jl. BSD Grand Boulevard,
Pagedangan, Tangerang, Banten 15339
B2
200
Tel: +62 21 2223 2613
APPROVED BY:
950
1300
FLOOR 5
1300
FFL+13.000
1150
MANUFACTURER:
IFE ELEVATORS
400
FLOOR 2
FFL FFL FFL+5.000 CO., LTD.
Jinlong Road, Jinlong Industrial Park, Qingxi, Dong Guan
City, Guang Dong Province, P. R. China, 523660
400
110 CUTOUT 960 80 80 CUTOUT 960 110 Tel: +86 769 8207 8888, Fax: +86 769 8773 2448
APPROVED BY:
HOISTWAY WIDTH 1150 HOISTWAY WIDTH 1150
HOISTWAY SECTION &
1250
05 SEPARATOR BEAM CONSTRUCTION PLAN
800
TYPE A (RIGHT OPENING) TYPE B (LEFT OPENING)
02 LANDING HALL CONSTRUCTION PLAN 04 LANDING HALL CONSTRUCTION PLAN B2
200
NOTE:
1050
1250
1. THE TOLERANCE OF PERPENDICULARITY ACROSS THE ENTIRE HOISTWAY
HEIGHT MUST NOT EXCEED ±20 MM. OVERHEAD, HOOK & FLOOR NAME
V3 2025/01/26 W. Y.
REVISION BY OWNER
B3
5000
B2 2. THE SEPARATOR BEAMS ARE INTENDED TO BE DEPLOYED ON THE REAR V2 2025/01/22 TEMPLATE REVISION W. Y.
200
150
SIDE OF THE HOISTWAY ONLY. ITS INSTALLATION SHALL NOT COMPROMISE V1 2025/01/17 DRAFT W. Y.
C1 PRACTICAL COLUMN BY CONCRETE 150 x 150 BY CIVIL THE MINIMUM HOIST WAY PLAN DIMENSIONS. NO. DATE REVISION DRAFTER
150
2
360
LIFT CONTROL HOP Salembaran Jati, Kosambi, Tangerang Regency,
FIRE SWITCH @ FIREMAN'S
SERVICE
650
RUN
PKG
TASK ASSIGNER:
PARKING KEY
@ FLOOR 1 ONLY
PT. CITRA ABADI MANDIRI
3115
485
HOP38
PIK 2
04 HOP38 MAGNIFICATION
485
1200
680
FFL
30
CONSTRUCTION MANAGEMENT:
OPENING 800
FLOOR R CAR POSITION
110 CUTOUT 960 80 FFL+17.000 OPENING 800 INDICATOR
HOISTWAY WIDTH 1150
750
MACHINE INSTALLATION SECTION EMERGENCY
02
LIGHT & CALL
NOTE: R
1. IFE TO PROVIDE PROPER CAPACITY (LOAD &
FLOOR 3 5
PERSONS) SIGNATURE
BUTTONS APPROVED BY:
VENTILATION IFE在 COP上需提供正规的载重标识,包括公斤和人 1 2
CEILING 数。
CEILING
CAR CLEARANCE HEIGHT 2200
R
COP42 HANDRAIL NOT PROVIDED
3
1
5
2
150
2
360
HOP Salembaran Jati, Kosambi, Tangerang Regency,
LIFT CONTROL FIREMAN'S
SERVICE
650
RUN
FLOOR
PKG
TASK ASSIGNER:
PARKING KEY
CAR DEPTH 1300
3115
485
HOP38 PIK 2
04 HOP38 MAGNIFICATION
485
1200
680
170 APPROVED BY:
40
FFL
30
CONSTRUCTION MANAGEMENT:
OPENING 800
FLOOR R CAR POSITION
80 CUTOUT 960 110 FFL+17.000 OPENING 800 INDICATOR
HOISTWAY WIDTH 1150
750
MACHINE INSTALLATION SECTION EMERGENCY
02
LIGHT & CALL
NOTE: R
1. IFE TO PROVIDE PROPER CAPACITY (LOAD &
FLOOR 3 5
PERSONS) SIGNATURE
BUTTONS APPROVED BY:
IFE在 COP上需提供正规的载重标识,包括公斤和人 1 2
VENTILATION
数。
CEILING CEILING
CAR CLEARANCE HEIGHT 2200
WALL WALL ICE Business Park D03, Jl. BSD Grand Boulevard,
COP或电梯轿厢内任何位置不得显示制造商的标志 Pagedangan, Tangerang, Banten 15339
CAR 05 COP42 MAGNIFICATION Tel: +62 21 2223 2613
B
FLOOR APPROVED BY:
C D
A
COP42 MANUFACTURER:
ITEM MATERIAL IFE TYPE
IFE ELEVATORS
60
V1 2025/01/17 DRAFT W. Y.
OPENING HEIGHT 2000