General
The concrete column module designs concrete rectangular or circular columns against axial,
uniaxial or biaxial bending as well as shear based on ACI 318-02/05/08/11/14 Code Provisions.
The program generates EXACT (not approximate or empirical) P-Mx-My interaction surfaces for all
sections according to user-specified design criteria. The capacity ratio is computed for each
column based on capacity interaction surfaces and axial force-biaxial bending in each load
combination. Slenderness effects are considered for both non-sway (braced) and sway (unbraced)
frames. Shear design in columns is based on the shear force envelope with the option to include or
exclude axial force influence on concrete shear capacity.
Solution Assumptions
• The strain in reinforcement and concrete is directly proportional to the distance from the
neutral axis (ACI 318-02/05 10.2.2).
• The maximum usable strain at the extreme concrete compression fiber is equal to 0.003
(ACI 318-02/05 10.2.3).
• The stress of steel is fs = Es * εs but fs <= fy where Es = 29000 ksi, εs is steel strain and fy
is the yield strength of steel (ACI 318-02/05 10.2.4).
• The tensile strength of the concrete is neglected in flexural calculation (ACI 318-02/05
10.2.5).
• A uniformly distributed stress of 0.85fc is assumed over an equivalent compression zone
bounded by the edge of the cross section and a line parallel to the neutral axis at a distance
a = β1* c where c is the distance from extreme compression fiber to neutral axis (ACI 318-
02/05 10.2.7.1).
• β1 = 0.85 – 0.05 * (f’c - 4) and 0.65 <= β1 <= 0.85 and f’c unit is ksi
• Reinforcement ratio ρ should be 1% <= ρ <= 8% for column sections (ACI 318-02/05
10.2.7.3).
Solution Algorithms
1. All sections are EXACTLY solved biaxially based on the solution assumptions above.
Each section is solved based on the following steps.
The number of biaxial angle steps is analogous to the number of sides of a polygon used to
approximate a circle or ellipse. A uniaxial solution in the program is therefore analogous to using a
square to approximate a circle or a rectangle to approximate an ellipse. A biaxial solution with 16
angle steps is analogous to using a 16-sided polygon to approximate a circle or an ellipse.
Obviously, the 16-sided polygon is closer or more accurate to approximate a circle than a square.
The moral of this comparison is that a low value of biaxial angle steps tends to give more
conservative biaxial capacity for the section.
2b). For each biaxial angle, Pn, Mnx, Mny and maximum tensile steel strain εt are computed at
successive choices of neutral axis distance c using strain compatibility and stress-strain relations to
establish bar forces and the concrete compressive results. The choices of c are based on the
neutral axial steps found in the command Concrete > Design Options. Neutral axial steps affect the
solution accuracy and speed. A value of 250 ~ 500 for neutral axis steps is sufficiently accurate for
most sections. The adequacy of neutral axis steps can be determined by smoothness of the P-Mx
and/or P-My interaction diagrams. In addition, the program always computes several control
points. They are maximum Pn (compression), minimum Pn (tension), fs = 0; 0.25fy; 0.5fy and 1.0fy
(balanced condition). Concrete displaced by steel may be optionally included or excluded (by
default).
2c). Mnx-Mny contour curves are computed for successive choices of axial forces. This is achieved
through interpolation on the Pn, Mnx and Mny already calculated for each biaxial angle in the
procedure above. The choices of axial forces are based on the neutral axial steps found in the
command Concrete > Design Options.
4. Capacity Ratio
Capacity ratio is computed for each section based on the loads and the capacity of the section. It is
defined as the following:
For a given load set (Pu, Mux, Muy), find the section capacity Mx-My contour at φPn= Pu. The
capacity ratio for the load set is the larger of:
Where (φMnx,max, φMny, max) is the interaction point between the line from point (Mux, Muy) to
point (0, 0) and the Mx-My contour line. is the maximum compression or tension capacity of the
section, depending on the positive or negative sign of Pu. If Pu is outside the maximum
compression or tension capacity, a capacity ratio of 99.9 is assigned.
A capacity ratio equal or less than 1.0 means the design strength is greater than the required
strength; and the section is adequate to resist all input loads. A capacity ratio greater than 1.0
means the design strength is less than the required strength and the section is inadequate to resist
all input loads. It is important to realize that capacity ratio defined in the program is just a measure
of section adequacy against loads. It should not be equated to a factor of safety.
To illustrate the calculation of capacity ratio in the program, see the following example.
For a given load set (Pu, Mux, Muy) = (333 kip, 180 ft-kip, 125 ft-kip), a Mx-My capacity contour at
φPn = 333 kip is obtained as shown below. In addition, the maximum compression capacity =
1050.2 kip.
The interaction point between the line from point (180 ft-kip, 125 ft-kip) to point (0, 0) and the
contour line is obtained as (214.1 ft-kip, 148.7 ft-kip)
Therefore, the capacity ratio corresponds to the load set is 0.841. The section is adequate to resist
the load.
2). P-Δ effect is associated with the lateral drifts of the frame members. Additional second-order
moment may develop by axial force (P) acting upon the lateral translation (Δ) of the frame nodes
relative to their original position. It is NOT possible to account for P-Δ effects on columns
independently.
Slenderness Effects
For a non-sway frame, P-Δ effect may be safely ignored and the first-order structural analysis is
therefore sufficient. The program then accounts for P-δ effect by magnifying the first-order
moments using ACI moment magnification method.
For a sway frame, the second-order structural analysis must be performed to account for P-Δ effect.
In addition, the program accounts for P-δ effect by magnifying the second-order moments using
ACI moment magnification method. In fact, all columns in sway frames must first be considered as
braced columns under gravity loads acting alone.
Criterion 2: Stability index Q for the column story under consideration from the first-order analysis
Note:
a). Ig and Ag are based on the gross concrete cross section, neglecting reinforcement.
a). Ig for Tee beams can be closely approximated as 2 times Ig for the web.
b). 0.70 Ig should be used for walls first. If the factored moments and shears indicate that a portion
of the wall will crack due to stresses reaching the concrete modulus of rupture, the analysis should
be repeated with 0.35 Ig for the cracked portions of the wall.
[Ref. 16 pp577]
The program allows a user to modify the moments of inertia through Element Cracking Factor from
Concrete > Cracking Factors. In order to use stiffness reduction, you also need to check “Use
cracked section properties (Icr) for members and finite elements” in Analysis Options. This allows
you to consider or ignore cracking in the analysis without re-entering element cracking information.
Radius of Gyration
Section properties are the same as used in the first-order analysis (step 1)
For practical reasons, for fixed end and for hinged end.
The effective length factor K is solved from the from the following equations
For braced frames:
The program provides a tool to calculate the effective length factor K based on the input .
The equations above provide a more accurate K calculation than what is given by (ACI 318-02/05
10.12.1)
Unsupported Length Lu
The unsupported lengths Luy, Luz of a column are the clear distances between lateral supports in
column local y and z directions (ACI 318-02/05 10.11.3.1). A zero value of Lu means that it is equal
to the member length between the end nodes.
For non-sway frames, an optional check is made kLu / r <= 34 – 12(M1/M2) (ACI 318-02/05 Eq10-
7). Braced frame k is used here. Lu is unbraced length in local x and y directions. M1 and M2 are
the smaller and larger factored end moments on the compression member respectively. (M1/M2) is
positive if the member is bent in single curvature and negative otherwise.
For sway frames, an optional check is made kLu / r <= 22 (ACI 318-02/05 10.13.2). Sway frame k
is used here.
Minimum Moments
The program calculates minimum moments for both braced and unbraced frames,
, where h is in inches (ACI 318-02/05 10.12.3.2). The program
conservatively applies the minimum eccentricity about both axes simultaneously.
Although not required, the program also conservatively applies for ACI 318-08 /11/14.
The sign of is: positive if the column is bent in single curvature, negative otherwise.
Note, Cm is only applicable to non-sway frames. You have the conservative option to always use
Cm = 1.0 from Model Design Criteria under Concrete > Design Criteria.
The Infamous
The ratio of maximum factored axial sustained load to maximum factored axial total load. The
factor accounts for the effects of creep.
Generally:
Critical Load Pc
Pu is the average of axial force at both ends. If , the design fails and a capacity ratio
of 999.9 is assigned.
Other Requirements
Reinforcement ratio for columns:
Bar requirements: minimum 4 bars for tied columns, 6 bars for spiral columns.
Tie requirements: >= #3 for No. 10 longitudinal bars and smaller; >= #4 for No. 11 14, 18
longitudinal bars.
Based on rectangular or circular sections used for analysis, the program will generate column
sections with different reinforcement configurations.
Given bw, d, fc, fy, number of stirrup legs n, and stirrup (tie) area Av, the required stirrup spacing is
computed at every analysis station.
Note:
• For circular section, and d = 0.8(2R) where R is the radius of the circular section.
(ACI 318 11.3.3 and 11.5.7.3)
• Nu = 0 if the influence of compression on concrete shear strength is ignored.
The following is the algorithm used to compute the stirrup (tie) spacing(s) in the program.
If , no stirrup required (ACI 318-02/05 11.5.6.1). The program does not check member
depths when applying minimum shear reinforcement for ACI 318-08/11/14.
According to ACI 318-02/05, column confinement spacing shall not exceed 16 longitudinal bar
diameters, 48 tie bar or wire diameters, or the least dimension of the compression members.