IJEIR_1610_Final
IJEIR_1610_Final
Abstract – A step-up bulk-power transformer had just been winding transformer installed by MELCO (Nig.)
installed for the Unit 1 of Egbin Thermal Power Plant in the LIMITED in 1985 for Unit 1 of the Egbin Thermal Power
Lagos area, Nigeria. It was required by due practice to Plant, Lagos. Such a transformer is otherwise called
ascertain that it was in good functional condition and that it generator transformer; the name which arises from the
was installed to international standards. In this paper, the
practice that it is always located as close to the associated
author presents details of the physical inspection and thirteen
tests that were carried out. The observations from inspection generator as possible, in order to transfer bulk power from
and the results of the tests were analyzed with a view to the generator to a given transmission line system [1]. After
ascertaining the condition and availability of the equipment it was successfully installed it had to be thoroughly
for service delivery. The analysis indeed proved the power inspected and tested before putting it into service.
transformer to have satisfied international standards in By way of organization of the paper, the next section
virtually all aspects of the transformer tests considered and shall deal with General Physical Inspection Exercise; to
that it did not suffer defects arising from transportation be followed by the third section entitled Actual Pre-
hazards. To that extent the equipment was properly installed Commissioning Test Exercises; whilst the fourth and final
only that it yielded over 50% excess resistance than the
section takes care of Summary and Conclusion.
factory stipulated (reference) resistance on the high voltage
side which was, however, not satisfactory.
II. GENERAL PHYSICAL INSPECTION EXERCISE
Keywords – Bulk Power Transfer, Transformer Tests.
Details of the various aspects of the apparatus inspected
I. INTRODUCTION and the observations made are as given in Table I(a).
Table I(b): Recommended Torque for various Sizes of 100Megohms; whereas, IR values of 10 to 100Megohms
Spanner, Bolt and Nut [4] are indicative of deteriorating insulation between the core
S/ SPANNER BOLT/NUT TORQUE and ground. For the windings generally IR values of
No. SIZE SIZE (Nm) 600Megohms and above are acceptable for transformers
i M08 M05 5.7 rated 10MVA and above [6]. Hence, the transformer of
ii M10 M06 7.9 this work did possess good IR property.
iii M13 M08 17 B. Core & Winding Polarization Index (PI) Test.
iv M17 M10 28 This test was effected under the same condition as in (a)
v M19 M12 45 above. The same apparatus and method was used, only
vi M22 M14 61 that the 5kV(d.c.) was applied for 10 minutes in each case
vii M24 M16 91 here.
viii M30 M20 136 Test Results:
ix M32 M22 170 (i) Core-to-Earth = 1628Megohms
x M36 M24 125 (ii) HV-to-Earth = 2090Megohms
(iii) LV-to-Earth = 1700Megohms
(iv) HV-to-LV = 2566Megohms
III. ACTUAL PRE-COMMISSIONING TEST
Analysis:
EXERCISES Polarization Index (PI) = {10 min IR value}/{1 min IR
value}. Very good PI values are usually above 2.0 [7].
The actual pre-commissioning exercises involving But, the limit of acceptable values is 1.6 as in [8]. The
various tests carried out on the generator transformer Egbin Station generator transformer gave PI values of not
yielded results as detailed in the subsections that follow. less than 1.6 which is good enough.
A. Core & Winding Insulation Resistance (IR) Test. C. Turns Ratio Test Exercise.
The test was carried out at an Oil Temperature of 28 oC This involved the use of Transformer Turns Ratio Test
by applying 5kV(d.c.) for 1 minute in each case using a Set (Make – KEIHIN DENSOKKI, Type – TR 10).
5kV Megger Insulation Tester (Make – Yew, Type –
Test Results:
3213).
Results of the exercise were as presented in Table II
Test Results:
(i) Core-to-Earth = 1005Megohms
Analysis:
(ii) HV-to-Earth = 1254Megohms The percentage deviation from the rated turn ratio, Trated,
(iii) LV-to-Earth = 1030Megohms should be within ± 0.5% [9].
(iv) HV-to-LV = 1510Megohms However, acceptable values of %deviation extend up to
±1.0% according to [10]. It is therefore clear from Table II
Analysis:
that the transformer turns were produced to standard
As in [5], a new transformer should give Core-to-Earth
judging from the maximum %deviation from tap to tap.
IR value greater than 1000Megohms; a service-aged
transformer should give a value greater than
D. Voltage Vector Relationship Test Exercise. Table III: Results of the Voltage Vector Test Exercise
AVO Multi-meter Model 8MK.V was use in conducting Test Voltage Terminals
this test. Winding Applied Linked
Test Results: H.V. 420V H1-to-x1
Results of the exercise were as presented in Table III. (a.c.)
Measured Voltage
Between Between Between Between
H2 & x2 H2 & x3 H3 & x2 H3 & x3
405V 435V 405V 405V
(a.c.) (a.c.) (a.c.) (a.c.)
(NB: Values of R include the d.c. resistance of the connecting leads. The LV d.c. winding resistance was, however, not
measured during the exercise).
Table VII: Average Resistance of all the Three Phases for each Tap Position
Tap Pos
Winding 1 2 3 4 5
HV 0.628Ω 0.621Ω 0.633Ω 0.630Ω 0.603Ω
H. Bushing Current Transformer (BCT) Insulation I. Bushing Current Transformer Polarity Test
Resistance Test Exercise: Exercise:
The same test equipment and method as applicable to The induction-kick method with d. c. voltage was used
the auxiliary-circuit insulation resistance test exercise as shown in the apparatus arrangement of Fig. 3(a); whilst
above were used here. Fig.3(b) shows details of the BCT winding per phase (the
Test Results: 1st in this case).
Results of the exercise were as presented in Table IX.
Analysis:
A table of insulation resistance values and the associated
voltages is given in [17] which is tailored here to suit the
purpose of this test as it is acceptable generally for all
electrical equipment (see Table X); the applicable test
temperatures of 25oC through 30oC ( or a rough average of
28oC) having been considered appropriate to that effect .
Table X: Acceptable Values of Insulation Resistance
obtained during Tests [7]
EQUIPMENT TEST ACCEPTABL Fig. 3(a): Apparatus setup for the Polarity Test Exercise
S/ RATED VOLTAGE E READING
No. VOLTAGE (Vdc) (MΩ)
1 <1000Vac 500Vdc >5
2 1000 to 2500Vac 1000Vdc >100
3 2501 to 5000Vac 2500Vdc >100
4 >5000Vac 5000Vdc >100
K. Bushing Current Transformer Magnetization Test rated 1Amp, it was mandatory to use a step-up interposing
Exercise. transformer in order to obtain the necessary voltage for
A variable voltage supply was connected across the proper assessment of the magnetizing curve [18].
terminals of the full length of a given B.C.T secondary Moreover, the average oil temperature at the time of
winding and the current measured at different voltage testing was 30oC. Among the apparatus used were: 0 –
values using a suitable ammeter. It is important to note 260V variable auto-transformer; 220/6600V 1-phase step-
that the ammeter was connected absolutely in series with up transformer; 6600/110V single-phase potential
the B.C.T winding to avoid reading the voltmeter branch transformer; 0 – 1A moving-iron ammeter; 0 – 200V
current, which in some cases could be of the same order of voltmeter.
the B.C.T magnetizing current [17]. As the magnetizing Test Results:
current was not going to be sinusoidal, an ammeter of the Results of the exercise were as presented in Table XIII.
moving-iron type was used [18]. And it is often found that Analysis:
current transformers with secondary ratings of 1Amp or It can be observed from Table XIII that the magnetizing
less do have a knee-point voltage higher than the local currents for the same input voltages are close to one
mains supply [18]. Hence, the B.C.T secondary being another in respect of the No.1 and No.2 sets of B.C.Ts on
Copyright © 2015 IJEIR, All right reserved
515
International Journal of Engineering Innovation & Research
Volume 4, Issue 3, ISSN: 2277 – 5668
all the phases and neutral. Taking average current of both phases, an average value can be taken in each case (see
sets of B.C.Ts, values of current are obtained applicable to Table XV) for the purpose of plotting one magnetizing
both sets as given in Table XIV for the purpose of curve for this set. Figure 4 shows the curves for the Nos.1
generating magnetizing curves (i.e. 4 in number) common & 2 B.C.T sets; whilst Fig. 5 reflects the one curve for
to both B.C.T sets. Also, as the currents for No.3 set of No.3 B.C.T set. MATLAB was used in accomplishing the
B.C.Ts are not too different from one another on all the plots.
L. Buchholtz Relay Function Test Exercise. sufficiently capable of withstanding the expected stresses
The ALARM CONTACTS were tested by supplying of the transformer rated voltages.
nitrogen gas through the gas sampling valve into the top N. Dial Oil & Winding Temperature Thermometer
chamber and the TRIP CONTACTS were tested by Test Exercise
releasing the pressure (of about 0.15Kg/cm2) from the top The indicator bulb of the dial thermometer was
of the transformer, thus causing a pressure surge. A hand suspended in an oil bath together with an accurate mercury
pump was used. thermometer; care being taken to avoid their touching the
Test Results: side or bottom of the container.
Alarm contacts made at the right level of oil fall in the Hotplate was used to heat the oil while stirring and the
upper chamber with 450cm3 of gas. Trip contacts made in readings of the two thermometers were taken as the
the lower chamber following the pressure surge created. temperature increased. Oil bath test kit (Qualitrol),
Analysis: hotplate, mercury thermometer were thus chief amongst
Buchholz alarm and trip systems observed to be the apparatus used.
functional judging from the test results. Test Results:
M. Transformer Oil Dielectric Strength Test Results of the exercise were as presented in Table XVII.
Exercise. Analysis:
For this exercise, five samples of the oil were taken with The error temperature for any of the dial thermometers
oil-sampling bottles that were rinsed many times with the should be within ±5oC [5]. Thus, both dial thermometers
same transformer oil and a small amount of the oil was were in good working condition.
first made to flow out of the tap and run to waste before
samples were then taken. The electrode gap was set to IV. SUMMARY & CONCLUSION
2.5mm. The SANMI Oil Tester, No.JIS C2101, Range 0 –
60kVdc was used. The test voltage (dc) was applied A. Summary
gradually each time within 1 minute. From the physical inspection report as detailed in Table
Test Results: I(a), the transformer was satisfactory in terms of external
Results of the exercise were as presented in Table XVI. facility and surrounding conditions. The thirteen test
Table XVI: Results of the Oil Dielectric Strength (DS) exercises covered in this paper include: (1) core &
Tests winding dielectric property test (2) turns ratio test (3)
SAMPLES 1 2 3 4 5 voltage vector relationship test (4) dissipation factor test
B.D.V (kV) 55 55 58 58 58 (5) transformer winding resistance test (6) auxiliary-
AVERAGE B.D.V(kV) 56.8kV circuit insulation resistance test (7) bushing current
56.8/2.5 = 22.72kV/mm transformer insulation resistance test (8) bushing current
D.S.
transformer polarity test (9) bushing current transformer
(NB: B.D.V – Breakdown Voltage; D.S. – Dielectric Strength) resistance test (10) bushing current transformer
magnetization test (11) buchholz relay functional test (12)
Analysis: transformer oil dielectric strength test and (13) dial
The breakdown voltage (B.D.V) should not be less than temperature thermometer test.
30kV for transformers rated 287.5kV and above, and B. Conclusion
25kV for those rated below 287.5kV [5]. If the B.D.V falls From the test results as provided in this work and the
below these values, the oil should be reclaimed. It follows analysis as presented, the generator transformer yielded
that a transformer oil D.S should not be lower than acceptable pre-commissioning test results, excepting (of
10kV/mm at an electrode gap of 2.5mm or 6.25kV/mm at course) the HV winding resistance test results which were
a gap of 4mm. Here, only the B.D.V test was carried out. over 1.5times the factory reference resistance on each tap.
Although a significant test, this was grossly inadequate for The apparatus was, however, commissioned; but not
the transformer oil property evaluation, because moisture without the strong recommendation for an effective
in combination with oxygen and heat will have cellulose cooling measure to avoid over-heating due to substantial
insulation destroyed in a transformer long before the additional copper losses (of over 50%). Effective use of
B.D.V or D.S of the oil gives a clue that anything was the transformer cooling fans was thus the near solution.
going wrong [20]. However, with average B.D.V of
56.8kV and D.S of 22.72kV/mm the oil proved