GET 202 LESSON NOTE
GET 202 LESSON NOTE
Polyphase Circuits or systems in which the ac sources operate at the same frequency but
different phases are known as polyphase
Figure (c) shows a two-phase three-wire system, and Fig. (d) shows a three-phase four wire
system
1
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
3. The instantaneous power in a three-phase system can be constant (not pulsating), which
results in uniform power transmission and less vibration of three-phase machines.
4. The three-phase system is more economical than the single-phase for the same amount of
power. The amount of wire required for a three-phase system is less than that required for
an equivalent single-phase system.
2
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
Phase Sequence
The phase sequence is the time order in which the voltages pass through their respective
maximum values. The phase sequence is determined by the order in which the phasors pass through
a fixed point in the phase diagram.
There are two possible phase sequences when three-phase voltages are 120𝑜 out of phase with
each other:
Positive Phase Sequence Negative Phase Sequence
The positive sequence is known as the abc sequence, which can be mathematically
expressed as:
𝑉𝑎𝑛 = 𝑉𝑝 ∠0𝑜 , 𝑉𝑏𝑛 = 𝑉𝑝 ∠ − 120𝑜 , 𝑉𝑐𝑛 = 𝑉𝑝 ∠−240𝑜 = 𝑉𝑝 ∠ + 120𝑜 . (3)
𝑉𝑝 is the effective or rms value. In this phase sequence, 𝑉𝑎𝑛 leads 𝑉𝑏𝑛 , which in turn leads 𝑉𝑐𝑛 .
This sequence is produced when the rotor in rotates counter clockwise.
While the Negative sequence is known as the acb sequence, which can be mathematically
expressed as:
𝑉𝑎𝑛 = 𝑉𝑝 ∠0𝑜 , 𝑉𝑐𝑛 = 𝑉𝑝 ∠ − 120𝑜 , 𝑉𝑏𝑛 = 𝑉𝑝 ∠−240𝑜 = 𝑉𝑝 ∠ + 120𝑜 . (4)
For this phase sequence, 𝑉𝑎𝑛 leads 𝑉𝑐𝑛 , which in turn leads 𝑉𝑏𝑛 . The acb sequence is produced
when the rotor rotates in the clockwise direction.
Thus, it can be shown that the voltages in equation (3) and (4) satisfy equation (1) and (2).
𝑽𝒂𝒏 + 𝑽𝒃𝒏 + 𝑽𝒄𝒏 = 𝑉𝑝 ∠0𝑜 + 𝑉𝑝 ∠ − 120𝑜 + 𝑉𝑝 ∠ + 120𝑜
3
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
Balanced Load
• A balanced load is one in which the phase impedances are equal in magnitude and in phase.
• Like the generator connections, a three-phase load can be either wye-connected or delta-
connected, depending on the end application.
• Figure (a) shows a wye-connected load, and Fig. (b) shows a delta-connected load. The
neutral line in Fig. (a) may or may not be there, depending on whether the system is four-
or three-wire.
• A neutral connection is topologically impossible for a delta connection. A wye- or delta-
connected load is said to be unbalanced if the phase impedances are not equal in magnitude
or phase.
• Thus, a Y-connected load consists of three impedances connected to a neutral node, while a
∆-connected load consists of three impedances connected around a loop. The load is
balanced when the three impedances are equal in either case.
4
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
➢ It is appropriate to mention here that a balanced ∆ -connected load is more common than a
balanced wye-connected load. This is due to the ease with which loads may be added or
removed from each phase of a delta-connected load. This is very difficult with a wye-
connected load because the neutral may not be accessible.
➢ On the other hand, ∆-connected sources are not common in practice because of the
circulating current that will result in the delta-mesh if the three-phase voltages are slightly
unbalanced.
• The impedance 𝑍𝑌 is the total load impedance per phase, it may also be regarded as the sum
of the source impedance 𝑍𝑆 , line impedance 𝑍ℓ , and load impedance 𝑍𝐿 for each phase,
since these impedances are in series.
• As illustrated in Fig.(a), 𝑍𝑆 denotes the internal impedance of the phase winding of the
generator; 𝑍ℓ is the impedance of the line joining a phase of the source with a phase of the
load; 𝑍𝐿 is the impedance of each phase of the load; and 𝑍𝑛 is the impedance of the neutral
line.
Thus; 𝒁𝒀 = 𝒁𝑺 + 𝒁𝓵 + 𝒁𝑳 (𝟗)
• 𝑍ℓ and 𝑍𝐿 are often very small compared with 𝑍𝐿 It is assumed that 𝑍𝑌 = 𝑍𝐿 if no source or
line impedance is given.
• In any event, by lumping the impedances together, the Y-Y system in Fig. (a) can be
simplified to that shown in Fig. (b).
5
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
Assuming the positive sequence, the phase voltages (or line-to-neutral voltages) are:
𝑉𝑎𝑛 = 𝑉𝑝 ∠0𝑜 ,
𝑉𝑏𝑛 = 𝑉𝑝 ∠ − 120𝑜 (10)
𝑉𝑐𝑛 = 𝑉𝑝 ∠ + 120𝑜
The line-to-line voltages or simply line voltages 𝑉𝑎𝑏 , 𝑉𝑏𝑐 , and 𝑉𝑐𝑎 are related to the phase
voltages. For example,
𝑉𝑎𝑏 = 𝑉𝑎𝑛 + 𝑉𝑛𝑏 = 𝑉𝑎𝑛 − 𝑉𝑏𝑛 = 𝑉𝑝 ∠0𝑜 − 𝑉𝑝 ∠ − 120𝑜
1 √3
= 𝑉𝑃 (1 + + 𝑗 ) = √3𝑉𝑃 ∠30𝑜 (11a)
2 2
(e) (e)
Figure: Phasor diagrams illustrating the relationship between line voltages and phase voltages.
Applying KVL to each phase in Fig. (d), we obtain the line currents as
𝑉𝑎𝑛 𝑉𝑏𝑛 𝑉𝑎𝑛 ∠−120𝑜
𝐼𝑎 = , 𝐼𝑏 = = = 𝐼𝑎 ∠ − 120𝑜 (15)
𝑍𝑌 𝑍𝑌 𝑍𝑌
6
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
𝐼𝑎 + 𝐼𝑏 + 𝐼𝑐 = 0 (16)
So that, 𝐼𝑛 = −(𝐼𝑎 + 𝐼𝑏 + 𝐼𝑐 ) = 0 (17a)
Or 𝑉𝑛𝑁 = 𝑍𝑛 𝐼𝑛 = 0 (17b)
• This mean, the voltage across the neutral wire is zero. The neutral line can thus be removed
without affecting the system.
• In a long-distance power transmission, conductors in multiples of three are used with the
earth itself acting as the neutral conductor. Power systems designed in this way are well
grounded at all critical points to ensure safety.
• While the line current is the current in each line, the phase current is the current in each
phase of the source or load.
• In the Y-Y system, the line current is the same as the phase current
(e)
𝑉𝑎𝑛
𝐼𝑎 = (18)
𝑍𝑌
• From 𝐼𝑎 , we use the phase sequence to obtain other line currents. Thus, as long as the
system is balanced, we need to only analyse one phase. This can also be done even if the
neutral line is absent, as in the three-wire system.
BALANCED WYE-DELTA CONNECTION
A balanced Y-Δ system consists of a balanced Y-connected source feeding a balanced
connected load.
(a)
𝑉𝑎𝑛 = 𝑉𝑝 ∠0𝑜 ,
7
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
• showing that the line voltages are equal to the voltages across the load impedances for this
system configuration. From these voltages, we can obtain the phase currents as:
𝑉𝐴𝐵 𝑉𝐵𝐶 𝑉𝐶𝐴
𝐼𝐴𝐵 = , 𝐼𝐵𝐶 = , 𝐼𝐶𝐴 = (23)
𝑍∆ 𝑍∆ 𝑍∆
❖ Alternative way to get these phase currents is to apply KVL. For example, applying KVL
around loop aABbna gives:
−𝑉𝑎𝑛 + 𝑍∆ 𝐼𝐴𝐵 + 𝑉𝑏𝑛 = 0
𝑉𝑎𝑛 −𝑉𝑏𝑛 𝑉𝑎𝑏 𝑉𝐴𝐵
Or 𝐼𝐴𝐵 = = = same as eqn. (23)
𝑍∆ 𝑍∆ 𝑍∆
❖ This is the more general way of finding the phase currents
• The line currents are obtained from the phase currents by applying KCL at nodes A, B, and
C. Thus, 𝐼𝑎 = 𝐼𝐴𝐵 −𝐼𝐶𝐴 , 𝐼𝑏 = 𝐼𝐵𝐶 −𝐼𝐴𝐵 , 𝐼𝑐 = 𝐼𝐶𝐴 −𝐼𝐵𝐶 (24)
Since 𝐼𝐶𝐴 = 𝐼𝐴𝐵 ∠−240𝑜
𝐼𝑎 = 𝐼𝐴𝐵 −𝐼𝐶𝐴 = 𝐼𝐴𝐵 (1 − 1∠−240𝑜 )
= 𝐼𝐴𝐵 (1 + 0.5 − 𝑗0.866) = 𝐼𝐴𝐵 √3∠−30𝑜 (25)
• showing that the magnitude 𝐼𝐿 of the line current is √3 times the magnitude 𝐼𝑃 of the phase
current, or
𝐼𝐿 = √3 𝐼𝑃 (26)
where 𝐼𝐿 = |𝑰𝒂 |= |𝑰𝒃 | = |𝐈𝐜 | (27)
𝐼𝑃 = |𝑰𝑨𝑩 |= |𝑰𝑩𝑪 | = |𝐈𝐂𝐀 | (28)
Also, the line currents lag the corresponding phase currents by 30𝑜 , assuming the positive
sequence. Figure (b) is a phasor diagram illustrating the relationship between the phase and
line currents.
8
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
(b)
(b) Phasor diagram illustrating the relationship between phase and line currents.
An alternative way of analysing the Y-∆ circuit is to transform the ∆-connected load to an
equivalent Y-connected load. Using the ∆-Y transformation formula:
𝑍∆
𝑍𝑌 = (29)
3
The three-phase Y-∆ system in Fig. (a) can be replaced by the single-phase equivalent circuit
in Fig. (c).
(c)
(a)
• The line voltages are the same as the phase voltages. From Fig. 12.17, assuming there is no
line impedances, the phase voltages of the delta connected source are equal to the voltages
across the impedances; that is,
𝑉𝑎𝑏 = 𝑉𝐴𝐵 , 𝑉𝑏𝑐 = 𝑉𝐵𝐶 , 𝑉𝑐𝑎 = 𝑉𝐶𝐴
Hence, the phase currents are
𝑉𝐴𝐵 𝑉𝑎𝑏 𝑉𝐵𝐶 𝑉𝑏𝑐 𝑉𝐶𝐴 𝑉𝑐𝑎
𝐼𝐴𝐵 = = , 𝐼𝐵𝐶 = = , 𝐼𝐶𝐴 = =
𝑍∆ 𝑍∆ 𝑍∆ 𝑍∆ 𝑍∆ 𝑍∆
• Since the load is delta-connected just as in the previous section, some of the formulas
derived there apply here. The line currents are obtained from the phase currents by applying
KCL at nodes A, B, and C.
𝐼𝑎 = 𝐼𝐴𝐵 −𝐼𝐶𝐴 , 𝐼𝑏 = 𝐼𝐵𝐶 −𝐼𝐴𝐵 , 𝐼𝑐 = 𝐼𝐶𝐴 −𝐼𝐵𝐶
9
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
Also, as shown in the last section, each line current lags the corresponding phase current by
30𝑜 ; the magnitude 𝐼𝐿 of the line current is √3 times the magnitude 𝐼𝑃 of the phase current,
𝐼𝐿 = √3 𝐼𝑃
An alternative way of analysing the ∆ − ∆ circuit is to convert both the source and the load to
𝑍
their Y equivalents since 𝑍𝑌 = 3∆
(a)
The line currents can be obtained in many ways. One way is to apply KVL to loop aANBba in
Fig. (a) writing
−𝑉𝑎𝑏 + 𝑍𝑌 𝐼𝑎 − 𝑍𝑌 𝐼𝑏 = 0
𝑍𝑌 (𝐼𝑎 − 𝐼𝑏 ) = 𝑉𝑎𝑏 = 𝑉𝑝 ∠0𝑜
𝑉𝑝 ∠0𝑜
Thus, 𝐼𝑎 − 𝐼𝑏 = (35)
𝑍𝑌
But 𝐼𝑏 lags 𝐼𝑎 by 120𝑜 , since we assumed the abc sequence, that is:
𝐼𝑏 = 𝐼𝑎 ∠−120𝑜
𝐼𝑎 − 𝐼𝑏 = 𝐼𝑎 (1 − 1∠−120𝑜 )
1 √3
= 𝐼𝑎 (1 + + 𝑗 ) = 𝐼𝑎 √3 ∠30𝑜 (36)
2 2
Substituting Eq. (36) into Eq. (35) gives
𝑉𝑃 ⁄√3∠ − 30𝑜
𝐼𝑎 = (37)
𝑍𝑌
From this, we obtain the other line currents 𝐼𝑏 and 𝐼𝑐 using the positive phase sequence, i.e.,
10
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
𝐼𝑏 = 𝐼𝑎 ∠−120𝑜 , 𝐼𝑐 = 𝐼𝑎 ∠+120𝑜 . The phase currents are equal to the line currents.
• Another way to obtain the line currents is to replace the delta connected source with its
equivalent wye-connected source, as shown in Fig (b)
• It was found that the line-to-line voltages of a wye-connected source lead their
corresponding phase voltages by 30◦. Therefore, we obtain each phase voltage of the
equivalent wye-connected source by dividing the corresponding line voltage of the delta-
connected source by √3 and shifting its phase by −30◦. Thus, the equivalent wye connected
source has the phase voltages.
• If the delta-connected source has source impedance 𝑍𝑆 per phase, the equivalent wye-
connected source will have a source impedance of 𝑍𝑆 /3
• Once the source is transformed to wye, the circuit becomes a Y-Y system. Therefore, we
can use the equivalent single-phase circuit shown in Fig. (c), from which the line current for
phase a is:
𝑉𝑃 ⁄√3∠ − 30𝑜
𝐼𝑎 =
𝑍𝑌
• Alternatively, we may transform the wye-connected load to an equivalent delta-connected
load. This results in a delta-delta system, which can be analysed
𝑉𝑃
𝑉𝐴𝑁 = 𝐼𝑎 𝑍𝑌 = ∠ − 30𝑜
√3
𝑉𝐵𝑁 = 𝑉𝐴𝑁 ∠ − 120𝑜 , 𝑉𝐶𝑁 = 𝑉𝐴𝑁 ∠ + 120𝑜
NOTE
The delta-connected load is more desirable than the wye-connected load. It is easier to alter the loads
in any one phase of the delta-connected loads, as the individual loads are connected directly across the
lines. However, the delta-connected source is hardly used in practice, because any slight imbalance in
the phase voltages will result in unwanted circulating currents.
11
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
MUTUAL INDUCTANCE
When two inductors (or coils) are in a close proximity to each other, the magnetic flux caused
by current in one coil links with the other coil, thereby inducing voltage in the latter. This
phenomenon is known as mutual inductance.
Consider a single inductor, a coil with N turns. When current i flows through the coil, a
magnetic flux φ is produced around it as shown in Fig.(a).
12
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
Fig (b)
Consider two coils with self-inductances 𝐿1 and 𝐿2 that are in close proximity with each other
(Fig. 2). Coil 1 has 𝑁1 turns, while coil 2 has 𝑁2 turns
For the sake of simplicity, assume that the second inductor carries no current. The magnetic
flux ∅1 emanating from coil 1 has two components: one component ∅11 e links only coil 1, and
another component ∅12 links both coils. Hence,
∅1 = ∅11 + ∅12 (5)
Although the two coils are physically separated, they are said to be magnetically coupled.
Since the entire flux ∅1 links coil 1, the voltage induced in coil 1 is
𝑑∅1
𝑣1 = 𝑁1 (6)
𝑑𝑡
Only flux ∅12 links coil 2, so the voltage induced in coil 2 is
𝑑∅12
𝑣2 = 𝑁2 (7)
𝑑𝑡
Again, as the fluxes are caused by the current 𝑖1 flowing in coil 1 Eq. (6) can be written as
𝑑∅1 𝑑𝑖1 𝑑𝑖1
𝑣1 = 𝑁1 = 𝐿1
𝑑𝑖1 𝑑𝑡 𝑑𝑡
𝑑∅1
𝐿1 = 𝑁1
𝑑𝑖1
Is the self-inductance of coil 1. Similarly, Eq. (7) can be rewritten as:
𝑑∅12 𝑑𝑖1 𝑑𝑖1
𝑣1 = 𝑁2 = 𝑀21 (10)
𝑑𝑖1 𝑑𝑡 𝑑𝑡
𝑑∅12
𝑀21 = 𝑁2
𝑑𝑖1
Where 𝑀21 is known as the mutual inductance of coil 2 with respect to coil 1.
Subscript 21 indicates that the inductance 𝑀21 relates the voltage induced in coil 2 to the current
in coil 1. Thus, the open-circuit mutual voltage (or induced voltage) across coil 2 is
𝑑𝑖1
𝑣2 = 𝑀21 (11)
𝑑𝑡
Suppose we now let current 𝑖2 flow in coil 2, while coil 1 carries no current (Fig.c). The
magnetic flux ∅2 emanating from coil 2 comprises flux ∅22 that links only coil 2 and flux ∅21
that links both coils. Hence,
(c)
∅2 = ∅21 + ∅22
13
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
DOT CONVENTION
The polarity of mutual voltage M di/dt is not easy to determine, because four terminals are
involved. The choice of the correct polarity for M di/dt is made by examining the orientation
or particular way in which both coils are physically wound and applying Lenz’s law in
conjunction with the right-hand rule. Since it is inconvenient to show the construction details
of coils on a circuit schematic, we apply the dot convention in circuit analysis.
By this convention, a dot is placed in the circuit at one end of each of the two magnetically
coupled coils to indicate the direction of the magnetic flux if current enters that dotted terminal
of the coil.
The dots are used along with the dot convention to determine the polarity of the mutual voltage
as shown in Fig (a)
14
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
(a) If a current enters the dotted terminal of one coil, the reference polarity of the mutual
voltage in the second coil is positive at the dotted terminal of the second coil.
Alternatively,
(b) If a current leaves the dotted terminal of one coil, the reference polarity of the mutual
voltage in the second coil is negative at the dotted terminal of the second coil.
Application of dot convention is illustrated in the following Figures
`
(2a) (2b) (2c)
(2d)
Dot convention for coupled coils in series. For the coils in Fig. (3a), the total inductance is
𝑳 = 𝑳𝟏 + 𝑳𝟐 + 𝟐𝑴 Series aiding connection
For the coils in Fig. (3a), the total inductance is
𝑳 = 𝑳𝟏 + 𝑳𝟐 − 𝟐𝑴 Series -opposing connection
LINEAR TRANSFORMERS
A transformer is generally a four-terminal device comprising two (or more) magnetically
coupled coils.
15
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
(1)
By matrix inversion, this can be written as:
(2)
The goal is to match Eqs. (1) and (2) with the corresponding equations for the T and 𝜋 networks.
16
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
(3)
If the circuits in Figs. (b) and (c) are equivalents, Eqs. (1) and (3) must be identical. Equating
terms in the impedance matrices of Eqs. (1) and (3) leads to
(4)
For the 𝜋 (or ∆) network in Fig. (d), nodal analysis gives the terminal equations as:
(5)
Equating terms in admittance matrices of Eqs. (2) and (5), we obtain
IDEAL TRANSFORMERS
An ideal transformer is one with perfect coupling (k = 1). It consists of two (or more) coils with
a large number of turns wound on a common core of high permeability.
Because of this high permeability of the core, the flux links all the turns of both coils, thereby
resulting in a perfect coupling.
A transformer is said to be ideal if it has the following properties:
1. Coils have very large reactances (𝐿1 , 𝐿2 , M →∞).
2. Coupling coefficient is equal to unity (k = 1).
3. Primary and secondary coils are lossless (𝑅1 = 0 = 𝑅2 ).
Thus, an ideal transformer is a unity-coupled, lossless transformer in which the primary
and secondary coils have infinite self-inductances.
Iron-core transformers are close approximations to ideal transformers. These are used in
power systems and electronics.
Figure (a) shows a typical ideal transformer; the circuit symbol is in Fig. (b). The vertical lines
between the coils indicate an iron core as distinct from the air core used in linear transformers.
The primary winding has 𝑁1 turns; the secondary winding has 𝑁2 turns.
17
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
When a sinusoidal voltage is applied to the primary winding as shown in Fig.(c), the same
magnetic flux φ goes through both windings. According to Faraday’s law, the voltage across
the primary winding is:
Fig (c)
𝑑∅1
𝑣1 = 𝑁1 (1)
𝑑𝑡
while that across the secondary winding is:
𝑑∅1
𝑣2 = 𝑁2 (2)
𝑑𝑡
Dividing Eq. (2) by Eq. (1), we get
𝑣2 𝑁2
= = 𝑛 (3)
𝑣1 𝑁1
where n is, again, the turns ratio or transformation ratio. We can use the phasor voltages 𝑉1
and 𝑉2 rather than the instantaneous values 𝑣1 and 𝑣2 . Thus, Eq. (3) may be written as
𝑉2 𝑁2
= = 𝑛 (4)
𝑉1 𝑁1
For the reason of power conservation, the energy supplied to the primary must equal the energy
absorbed by the secondary, since there are no losses in an ideal transformer. This implies that:
𝑣1 𝑖1 = 𝑣2 𝑖2 (5)
In phasor form, Eq. (5) in conjunction with Eq. (4) becomes
𝐼1 𝑉2
= = 𝑛 (6)
𝐼2 𝑉1
showing that the primary and secondary currents are related to the turns ratio in the inverse
manner as the voltages. Thus,
𝐼2 𝑁1 1
= = (7)
𝐼1 𝑁2 𝑛
When n = 1, we generally call the transformer an isolation transformer. If n > 1, we have a
step-up transformer, as the voltage is increased from primary to secondary (V2 > V1 ). On the
other hand, if n < 1, the transformer is a step-down transformer, since the voltage is decreased
from primary to secondary (V2 <V1 ).
A step-down transformer is one whose secondary voltage is less than its primary voltage.
A step-up transformer is one whose secondary voltage is greater than its primary voltage.
Polarity of the Voltages and the Direction of the Currents for the Transformer
Consider figure (c) below:
18
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
1. If 𝑽𝟏 and 𝑽𝟐 are both positive or both negative at the dotted terminals, use +n in Eq. (4).
Otherwise, use −n.
2. If 𝑰𝟏 and 𝑰𝟐 both enter into or both leave the dotted terminals, use −n in Eq. (7). Otherwise,
use +n
The rules are demonstrated with the four circuits in Fig. 1-4
(1) (2)
(3) (4)
Fig 1-4: Typical circuits illustrating proper voltage polarities and current directions in an
ideal transformer.
Rotating Machine
In the rotating electrical machine, an electromechanical energy conversion takes place. In all
the rotating electrical machines, a change in flux is closely associated with the mechanical
motion to cause electromechanical energy conversion.
When mechanical input energy is converted to an electrical energy, the machine is called
Generator. The electrical energy is produced in the form of a generated voltage or emf. If the
emf is constant, the machine is called d.c. Generator, while if the emf is alternating the machine
is called a.c Generator or an Alternator.
When electrical input energy is converted to a mechanical energy, the machine is called Motor.
If the input electrical energy is in the form of d.c., voltage is called d.c. Motor, and if it is in
the form of a.c voltage, it is called a.c Motor.
Thus, various electrical rotating machine are classified as a.c. machines and d.c. machines.
Many features of all these rotating machines are same. The various general expression such as
torque, generated voltage etc are applicable to all these rotating machines. Thus, all these
machine work on the same basic principle.
carrying conductor is placed in a magnetic field then it experiences a mechanical force, which
is the principle of a Motor. Hence every rotating machine must possess the following
Mechanical parts/features:
• Stationary member called Stator
• Rotating member called Rotor
• Shaft
• Slip Ring, brush assembly
• Bearings
In addition to these, a machine has:
Field winding: An arrangement of winding/conductor which is used as a primary source of
flux when current is passed through it.
Armature winding: An arrangement of winding/conductor to form a winding in which emf.
is induced.
The current flowing through the field winding, used to produce main flux is called magnetizing
current, exciting current or field current.
The current flowing through the armature winding varies as the load on the machine varies, so
it is called a load current or an armature current.
There is an appropriate air gap between a stator and a rotor of the machine. In most of the
machines, armature winding is placed on the stator, while the field winding is placed on the
rotor for practical point of view
20
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
ends are called the pole shoes. The exposed surface of a pole shoe is called a pole face, and the
distance between the pole face and the rotor is the air gap.
Yoke: The outer frame of a dc machine is called as yoke.
Function
• It serves as the purpose of outermost cover of the d.c. machine. So that insulating materials
get protected from harmful atmospheric element like moisture, dust and various gasses like
SO2 , acidic fumes etc.
• It not only provides mechanical strength to the whole assembly but also carries the magnetic
flux produced by the field winding.
• It provides mechanical support for the pole
• It forms a part of magnetic circuit. It provides a path of low reluctance for magnetic flux.
The low reluctance part is important to avoid wastage of power to provide same flux. Large
current and hence power is necessary if the part has high reluctance, to provide same flux.]
Choice of material
To provide low reluctance path, it is must be made up some magnetic material. It is prepared
by using cast iron because it is cheapest. For large machines rolled steel, cast steel, silicon steel
is used which provides high permeability low reluctance and gives good mechanical strength.
of cast iron or steel.
Poles
Each pole is divided into two parts namely: (1) Pole core (2) Pole Shoe
• Pole shoes enlarges the area of armature core to come across the flux, which is necessary to
produce larger induced emf. To achieve this, pole shoe has been given a particular shape.
• Pole shoe support field coils, and also spread out the flux in air gap uniformly
Choice of material:
• It is made up of magnetic material like cast iron or steel
• As it is required a definite shape and size, laminated construction is used. The lamination of
required size and shape are stamped together to get a pole which is bolted to the yoke
21
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
Choice of Material
• Aluminium or Copper is the choice because it has to carry current, hence obviously made
of some conducting material.
• Field coils are required to take any kind of shape and bend about pole core and copper has
good pliability i.e., it can be easily bend. So copper is the proper choice
NOTE Field winding is divided into various coils called field coils. These are connected in
series with each other and wound in such a direction around pole cores, such that alternate
‘N’ and ‘S’ poles are formed.
Armature core is cylindrical in shape mounted on the shaft. It consists of slot on its periphery
and the air duct to permit the air flow through armature which serve as cooling purpose.
Armature winding
It is the interconnection of the conductors, placed in the slot provided on the armature
periphery. When the armature is rotated, in case of generator, magnetic flux get cut by the
armature conductors and emf gets induced in them.
22
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
Armature Winding
Function
• Generation of e.mf. takes place in the armature winding in case of Generators
• To carry the current supplied in case of d.c. Motors
• To do the useful work in the external circuit
Choice of Material
It is made with copper, as armature winding carries entire current which depends on external
load, it has to be made up of conducting material.
It is usually a former wound copper coil which rests in armature slots. The armature conductors
are insulated from each other and also from the armature core. Armature winding can be wound
by one of the two methods; lap winding or wave winding. Double layer lap or wave windings
are generally used. A double layer winding means that each armature slot will carry two
different coils.
Commutator
The basic nature of emf induced in the armature conductors is alternating. This needs
rectification in case of d.c. generator, which is possibly by a device call commutator.
Choice of Material
• It is made up of copper segment, as it collects current from armature.
• It is cylindrical in shape and it is made up of wedge-shaped copper segments of hard drawn,
these segments are insulated from each other by thin layer of mica. The number of segments
is equal to the number of armature coils.
23
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
• Each commutator segment is connected to an armature coil by means copper lug and the
commutator is keyed to the shaft
Function
To collect current from commutator and make it available to the stationary external circuit.
Choice of material
• Brushes are normally made up of soft material like Carbon
• Brushes are rectangular in shape. They are housed in brush holders, which are usually of
box type. The brushes are made to press on the commutator surface by means of a spring,
whose tension can be adjusted by the help of lever.
• A flexible copper conductor called pig tail is used to connect the brush to the external circuit.
• Lap winding may be simplex (single) or multiplex (duplex or triplex) winding. In simplex
lap winding the connection of the winding is that there are as many parallel paths as there
are number of poles.
• Whereas for duplex, the number of parallel paths is equal to twice that of the number of
poles and for triplex it is thrice. For this reason, the lap winding is called multiple or parallel
winding.
24
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
Wave winding
If after passing once around the armature the winding falls in a slot to the left of its starting
point then winding is said to be retrogressive. If it fails one slot to the right it is progressive.
25
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
• If Ia is the total armature current, then current per parallel path is Ia /P.
• Lap winding is used for low voltage and high current machines.
Wave winding
• Number of parallel paths are equal to 2m, where m is the multiplicity
• The number of brushes required are two irrespective of the number of poles
• If Ia is the total armature current then current carried by each path or conductor is Ia/2.
• Since a wave winding is a series winding, it is used for high voltage and low current machine
ω = 𝟐𝝅𝑵⁄𝟔𝟎
27
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
Thus, it is clear that the induced emf is directly proportional to the speed and flux per pole. The
polarity of induced emf depends upon the direction of the magnetic field and the direction of
rotation. If either of the two is reverse the polarity changes, but if two are reversed the polarity
remains unchanged.
This induced emf is a fundamental phenomenon for all the DC Machines whether they are
working as a generator or motor.
If the DC Machine is working as a Generator, the induced emf is given by the equation shown
below.
PZ𝛟𝐧
𝑬𝒈 = 𝒗𝒐𝒍𝒕
𝑨
Where 𝑬𝒈 is the Generated Emf
If the DC Machine is working as a Motor, the induced emf is given by the equation shown
below.
PZ𝛟𝐧
𝑬𝒃 = 𝒗𝒐𝒍𝒕
𝑨
In a motor, the induced emf is called Back Emf (𝑬𝒃 ) because it acts opposite to the supply
voltage.
WORKING PRINCIPLE OF A DC MOTOR
The DC motor is the device which converts the direct current into the mechanical work. It
works on the principle of Lorentz Law, which states that “the current carrying conductor placed
in a magnetic and electric field experience a force”. And that force is called the Lorentz force.
The Fleming left-hand rule gives the direction of the force.
Fleming Left Hand Rule
If the thumb, middle finger and the index finger of the left hand are displaced from each other
by an angle of 90°, the middle finger represents the direction of the magnetic field. The index
finger represents the direction of the current, and the thumb shows the direction of forces acting
on the conductor
For simplicity, consider that the armature has only one coil which is placed between the
magnetic field shown below in the figure A. When the DC supply is given to the armature coil
the current starts flowing through it. This current develops their own field around the coil.
Figure B shows the field induces around the coil.
Figure A Figure B
Fig: magnetic field induces around the coil
By the interaction of the fields (produces by the coil and the magnet), resultant field develops
across the conductor. The resultant field tends to regain its original position, i.e., in the axis of
the main field. The field exerts the force at the ends of the conductor, and thus the coil starts
rotating.
Let the field produces by the main field be 𝐹𝑚 , and this field rotates in the clockwise direction.
When the current flows in the coil, they produce their own magnetic field says Fr. The field 𝐹𝑟
tries to come in the direction of the main field. Thereby, the torque act on the armature coil.
29
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
the north pole and move outwards through the south pole. When the coil moves from one brush
to another, at the same time the polarity of the coil also changes. Thus, the direction of the force
or torque acting on the coil remains same.
The torque induces in the coil become zero when the armature coil is perpendicular to the main
field. The zero torque means the motor stops rotating. For solving this problem, the number of
armature coil is used in the rotor. So, if one of their coils is perpendicular to the field, then the
other coils induce the torque. And the rotor moves continuously.
Also, for obtaining the continuous torque, the arrangement is kept in such a way that whenever
the coils cut the Magnetic Neutral Axis (MNA) of the magnet the direction of current in the
coils become reversed. This can be done with the help of the commutator.
• Back emf makes dc motor a self-regulating motor i.e., 𝑬𝒃 makes motor to adjust 𝑰𝒂 automatically
as per the load torque requirement. Let’s see how.
𝑽 − 𝑬𝒃
𝑰𝒂 =
𝑹𝒂
V and 𝑹𝒂 are fixed, therefore, armature current 𝑰𝒂 dpends on back emf, which in turn depends
on speed of the motor.
30
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
• when the motor is running at no-load, small torque (Ta=K𝑰𝒂 ) is required by the motor to
overcome friction and windage. Therefore, a small current is drawn by the motor armature
and the back emf is almost equal to the supply voltage.
• If the motor is suddenly loaded, the load torque becomes greater than the armature torque
and the motor starts to slow down. As motor speed decreases, back emf decreases and
therefore, armature current starts increasing. With increasing 𝑰𝒂 , armature torque increases
and at some point, it becomes equal to the load torque. At that moment, motor stops slowing
down and keeps running at this new speed.
• If the load on the motor is suddenly reduced, the driving torque becomes more than the load
torque and the motor starts accelerating. As the motor speed increases, back emf increases
and therefore, armature current decreases. Due to this reducing armature current, armature
developed torque decreases and at some point, becomes equal to the load torque. That point
onwards, motor will stop accelerating and will start rotating uniformly at this new slightly
increased speed.
Power Equation of a D.C. Motor
The voltage equation of a d.c. motor is given by,
𝑉 = 𝐸𝑏 + 𝐼𝑎 𝑅𝑎
Multiplying both sides of the above equation by 𝐼𝑎 we get:
𝑉𝐼𝑎 = 𝐸𝑏 𝐼𝑎 + 𝐼𝑎2 𝑅𝑎
This equation is called power equation of a d.c. motor
𝑉𝐼𝑎 is Net electrical power input to the armature measured in watts.
𝐼𝑎2 𝑅𝑎 is Power loss due the resistance of the armature called armature copper loss.
So, difference between 𝑉𝐼𝑎 and 𝐼𝑎2 𝑅𝑎 i.e., input - losses gives the output of the armature.
So, 𝐸𝑏 𝐼𝑎 is called electrical equivalent of gross mechanical power developed by the armature.
This is denoted as 𝑃𝑚 . Therefore:
Power input to the armature - Armature copper loss = Gross mechanical power developed in the armature\
SYNCHRONOUS MACHINES
Introduction:
The most commonly used machine for generation of electrical power for commercial
applications is the synchronous generator. Such a synchronous generator is also called an
alternator since it generates alternating voltage. A Synchronous Machine has two main parts,
viz. the stator and the rotor just like a DC Machine or an Induction Machine
31
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
(a)
(b)
Figure 1: (a) Stationary field and rotating armature system as in a DC machine
(b) Rotating field and stationary armature system as in an alternator
The main reasons why a stationary armature and rotating field construction for three-phase
synchronous machines is employed in all commercial applications are as follows:
32
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
1. Alternators are used to produce high voltage in the range of kV. This gets induced in
armature. So stationary armature helps to provide large space to accommodate large number
of conductors.
2. It is better to keep high voltage winding stationary and away from centrifugal forces caused
due to rotation.
3. It is easy to collect large currents from the stationary member
4. The voltage level required to supply field winding is low, of the order of 110V or 220V d.c.
This can be easily supplied to a rotating part through slipring and brush assembly without
any problems of sparking.
5. Armature requires more insulation while field requires less insulation. Less insulation means
low inertia hence easy from rotation point of view
6. Ventilation for high voltage can be improved if it is kept stationary
Therefore, overall rotating field construction is simple. The stationary armature has a core and
the slots to hold the armature winding. It uses laminated construction to keep eddy current
losses to a minimum value, while the high-grade magnetic materials is used to keep down the
hysteresis losses
SYNCHRONOUS MOTORS
Theory of operation:
The basic concept of a synchronous motor is explained with the help of the figure below which
shows a two-pole Synchronous Motor. The field current 𝐼𝐹 of the motor produces a steady-
state magnetic field 𝐵𝑅 . A three-phase set of voltages is applied to the stator, which produces
a three-phase current flow in the armature windings. This current flow produces a uniform
rotating magnetic field 𝐵𝑆
So, there are now two magnetic fields present in the machine, and the rotor field will tend to
line up with the stator field. Since the stator magnetic field is rotating, the rotor magnetic field
(and the rotor itself) will constantly try to catch up with the rotating stator magnetic field. The
larger the angle between the two magnetic fields (up to a certain maximum value), the greater
the torque on the rotor of the machine. The basic principle of synchronous motor operation is
that the rotor "chases" the rotating stator magnetic field around in a circle, never quite catching
up with it but with the same speed.
Since a Synchronous Motor is the same physical machine as a Synchronous Generator, all the
basic speed, power, and torque equations of synchronous Generators apply to Synchronous
Motors also.
33
APPLIED ELECTRICITY II (GET 202) BY ENGR. ADELEKE HAFIZ ADESUPO (EEED, AFIT, KADUNA)
34