HDF_M_C_EN_2021_08_R10
HDF_M_C_EN_2021_08_R10
CENTRIFUGAL FANS
SERIES:
AXIAL FAN
SERIE:
AX../ , AXHP../
LAYOUTS
4 - 5 - 7 - 8 - 9 - 10 - 12 - 13 :
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden
TABLE OF CONTENTS
1 GENERAL INFORMATION AND EQUIPMENT DESCRIPTION ................................................. 5
1.0 SOME NOTES ON THE USER’S MANUAL ................................................................................................ 5
1.1 CONVENTIONAL SYMBOLS AND THEIR DEFINITION....................................................................... 6
1.2 RECIPIENTS OF THE MANUAL ................................................................................................................. 7
1.3 SCOPE OF THE MANUAL ............................................................................................................................ 7
1.4 LIMITATIONS ON USE OF THE MANUAL .............................................................................................. 7
1.5 WARRANTY CONDITIONS .......................................................................................................................... 8
1.6 GENERAL PROVISIONS ............................................................................................................................... 8
1.7 REPRODUCTION LIMITATIONS AND COPYRIGHT ............................................................................ 8
1.8 CHARACTERISTICS OF OPERATORS AND LANGUAGE USED ........................................................ 9
1.9 HOW TO STORE THE MANUAL ................................................................................................................. 9
1.10 HOW TO UPDATE THE MANUAL .............................................................................................................. 9
1.11 PRELIMINARY ARRANGEMENTS THAT MUST BE PROVIDED BY THE CLIENT (AS
STIPULATED IN THE CONTRACT) ..................................................................................................................... 10
1.12 GENERAL DELIVERY NOTES .................................................................................................................. 10
1.13 RESPONSIBILITY OF HDF......................................................................................................................... 10
2 SAFETY PROVISIONS ........................................................................................................................ 13
2.1 PERSONAL PROTECTION (PPE) .............................................................................................................. 13
2.2 SAFETY LABELS, PROHIBITIONS AND OBLIGATIONS.................................................................... 14
2.3 RESIDUAL RISKS ......................................................................................................................................... 15
2.3.1 LIST OF RESIDUAL RISKS ..................................................................................................................... 15
2.3.2 LABELS SHOWING RESIDUAL RISKS, RESTRICTIONS AND OBLIGATIONS ................................... 16
2.4 GENERAL SAFETY PROVISIONS ............................................................................................................ 17
2.5 SPARE PARTS ............................................................................................................................................... 22
2.6 SAFETY DEVICES INSTALLED ON THE FAN ...................................................................................... 22
2.7 NOISE LEVEL ............................................................................................................................................... 23
2.8 INTENDED USE............................................................................................................................................. 23
2.9 UNINTENDED USE ....................................................................................................................................... 23
2.10 WHAT YOU SHOULD ALWAYS DO! ....................................................................................................... 23
2.11 WHAT YOU SHOULD NEVER DO! ........................................................................................................... 24
2.12 FINAL PART .................................................................................................................................................. 25
3 TECHNICAL DESCRIPTION AND SPECIFICATIONS ................................................................ 26
3.1 TECHNICAL DESCRIPTION...................................................................................................................... 26
3.2 TECHNICAL DATA NOMENCLATURE .................................................................................................. 26
3.3.A. TYPE OF IMPELLERS FOR CENTRIFUGAL FAN ............................................................................ 27
3.3.B TYPE OF IMPELLER FOR AXIAL FAN ............................................................................................... 27
3.4 ARRANGEMENTS ........................................................................................................................................ 28
3.5 DISCHARGE POSITION (FAN OUTLET POSITION) ............................................................................ 29
4 LIFTING AND INSTALLATION INSTRUCTIONS ........................................................................ 31
4.1 FOREWORD .................................................................................................................................................. 31
4.2 HANDLING OF THE PACKED FAN AND ITS PARTS........................................................................... 34
4.2.1 HANDLING OF PACKING CASES AND PALLETS WITH A FORKLIFT TRUCK................................. 35
4.2.2 HANDLING OF PACKING CASES AND PALLETS WITH OVERHEAD CRANE AND CABLES .......... 36
4.2.3 HANDLING FROM A CONTAINER ........................................................................................................ 37
4.3 UNPACKING .................................................................................................................................................. 38
4.4 STORAGE ....................................................................................................................................................... 39
4.5 DISPOSING OF THE PACKAGE ................................................................................................................ 40
4.6 HANDLING OF THE UNPACKED FAN .................................................................................................... 40
4.7 HANDLING OF LOOSE OR LIGHT PARTS ............................................................................................ 42
4.8 FOUNDATIONS ............................................................................................................................................. 42
4.8.1 REINFORCED CONCRETE FOUNDATION .......................................................................................... 42
4.8.2 FOUNDATION WITH STEEL FRAMES .................................................................................................. 43
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 2 of 96
4.8.3 ANTI-VIBRATION MOUNTINGS............................................................................................................. 43
4.9 INLET AND OUTLET DUCTS .................................................................................................................... 44
4.10 POSITIONING AND INSTALLATION OF THE FAN ............................................................................. 45
4.10.1 INSTALLATION METHODS (UNI EN ISO 13349).................................................................................. 45
4.10.2 CHECKS BEFORE THE ASSEMBLY ....................................................................................................... 46
4.10.3 PRELIMINARY OPERATIONS BEFORE FAN FIXING .......................................................................... 46
4.11 INDICATIONS FOR THE CONNECTION TO THE MACHINE............................................................ 47
4.11.1 CONNECTION OF THE PNEUMATIC EQUIPMENT (AIR) .................................................................. 47
4.11.2 CONNECTION OF THE MOTOR AND/OR ELECTRICAL EQUIPMENT ............................................. 48
4.11.3 CONNECTION TO THE EXTRACTION SYSTEM ................................................................................... 48
5. COMMISSIONING ............................................................................................................................... 49
5.1 FIRST START-UP AND TESTING ............................................................................................................. 49
5.2 PRELIMINARY CHECKS............................................................................................................................ 49
5.3 START-UP PROCEDURES .......................................................................................................................... 50
5.4 CHECKS DURING START-UP ................................................................................................................... 50
6. USE AND OPERATION ....................................................................................................................... 51
6.1 CHECKS BEFORE SWITCH-ON................................................................................................................ 51
6.2 SWITCHING ON THE FAN ......................................................................................................................... 51
6.3 CHECKS AFTER SWITCH-ON .................................................................................................................. 52
6.4 SWITCHING OFF THE FAN ....................................................................................................................... 52
6.5 EMERGENCY STOP..................................................................................................................................... 53
7. MAINTENANCE, CLEANING AND LUBRICATION .................................................................... 54
7.1 FOREWORD .................................................................................................................................................. 54
7.2 SCHEDULED MAINTENANCE .................................................................................................................. 57
7.2.1 FAN CASING CLEANING ........................................................................................................................ 59
7.2.2 IMPELLER CLEANING (FOR CLEAN FLUIDS) .................................................................................... 59
7.2.3 IMPELLER CLEANING (FOR DUSTY FLUIDS) .................................................................................... 60
7.2.4 IMPELLER CONDITION CHECK ........................................................................................................... 60
7.2.5 DAMPERS’ CLEANING ........................................................................................................................... 61
7.2.6 BEARINGS AND HOUSINGS .................................................................................................................. 61
7.2.6.1 ANTIFRICTION BEARING LUBRICATION WITH GREASE (SEPARATED BEARINGS) ..................... 62
7.2.6.2 BEARING HOUSING (MONOBLOCK) LUBRICATION WITH GREASE........................................... 64
7.2.6.3 ANTIFRICTION BEARING LUBRICATION WITH OIL ...................................................................... 65
7.2.6.4 LUBRIFICANT TYPES AND MAINTENANCE NOTES ....................................................................... 66
7.2.7 FASTENING OF ALL FIXED PARTS ...................................................................................................... 69
7.2.8 TOOTHED BELTS .................................................................................................................................... 70
7.2.9 V-BELTS ................................................................................................................................................... 71
7.2.10 FAN VIBRATION CHECK ....................................................................................................................... 73
7.2.11 IMPELLER ASSEMBLY............................................................................................................................ 74
7.2.12 IMPELLER DISASSEMBLY ..................................................................................................................... 74
7.2.13 MOTOR REVISION .................................................................................................................................. 75
7.2.14 COUPLING REPLACEMENT .................................................................................................................. 76
7.2.14.1 LUBRICATION OF STANDARD GEAR COUPLING “MAINA” – GO-A ........................................... 77
7.2.14.2 LUBRICATION OF LAMELLAR COUPLINGS ................................................................................... 78
7.2.15 CHECK OF ALL THE ELECTRICAL SYSTEM COMPONENTS ............................................................ 79
7.2.16 CHECK OF THE LEGIBILITY OF THE WARNING LABELS FOR RESIDUAL RISKS, RESTRICTIONS
AND OBLIGATIONS ................................................................................................................................................ 79
7.2.17 INSTALLATION OF THE INLET CONTROL DAMPER.......................................................................... 79
7.2.18 SEALS MAINTENANCE AND START UP ................................................................................................ 81
7.2.19 THERMOCOUPLE MAINTENANCE AND REGULATION – PT100 ...................................................... 84
8. TECHNICAL SUPPORT INFORMATION ....................................................................................... 86
9. DISMANTLING AND DISPOSAL...................................................................................................... 87
10. SPARE PARTS ...................................................................................................................................... 88
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 3 of 96
11. TROUBLESHOOTING ........................................................................................................................ 89
12. ATEX ...................................................................................................................................................... 92
12.1 WARNINGS .................................................................................................................................................... 92
12.2 CONSTRUCTION FEATURES .................................................................................................................... 93
12.3 INTERNAL AND EXTERNAL ZONES ...................................................................................................... 93
12.3 ATEX MARKING – NAME PLATE ............................................................................................................ 94
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 4 of 96
1 GENERAL INFORMATION AND EQUIPMENT DESCRIPTION
The USER’S MANUAL supplied is not an accessory of the Fan, and is an INTEGRAL PART of the Fan
and is a SAFETY PROVISION.
For this reason, you need to keep it in good condition, near the Fan and give it to any operator,
user or subsequent owner, so they can always have all the necessary information available for
which it was manufactured and also because it is a support for system use in maximum SAFETY.
To make its consultation simpler, the manual was sub-divided into chapters, to facilitate use per
employee type and to ensure each phase is well articulated.
Each topic was further subdivided into numbered points, which are sometimes referenced with
drawings.
The passages requiring greater attention are highlighted with conventional symbols on the left
of the page.
HDF S.r.l. uses this convention to draw the reader’s attention to ATTENTIONS, WARNINGS
AND DANGERS that concern him.
Please note that the illustrations in this Manual, included in order to facilitate the identification
of the described parts, might not be completely similar to the Fan you have purchased for
obvious reasons of generalisation.
HDF S.r.l.
Servizi Generali Qualità
Via Nazionale 5/C
Zona Industriale
23030 Chiuro (SO)
specifying the serial number that can be found on the plate affixed to the fan.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden
1.1 Conventional symbols and their definition
The Use and Maintenance Manual contains certain symbols: they are listed below together with
their meaning.
GENERAL DANGER
It signals to relevant staff that the operation described, if not carried out in compliance with the
safety standards, can be a source of possible injury or harm to people.
ELECTRIC SHOCK HAZARD
It signals to relevant staff that the operation described, if not carried out in compliance with
the safety standards, can be a source of possible injury or harm to people due to electric
shock.
EX HAZARD
It indicates the risk of explosion.
NOTE
It signals to relevant staff information of major importance and, if not complied with, can
cause damage to various parts of the Fan.
WARNING
It signals to relevant staff information that, if not complied with, can cause serious injury to
people
ADVICE
It refers to a working method tested in the factory, knowing well that each Operator will further
develop his/her own way of working.
OPERATOR OR DRIVER OF THE MACHINE
It identifies qualified, professionally trained staff authorised in compliance with the
regulations in force in the country of use to start, use, fine tune (with the guards enabled
and the machine off) and shut-down the machine following the instructions in this manual
and using the required personal protective equipment (PPE)
It is therefore prohibited for the operator to perform operations that are the
responsibility of the Maintenance Technician.
OPERATOR RESPONSIBLE FOR MOVEMENT
Qualified, professionally trained operator authorised in compliance with the regulations in force
in the country of use to operate forklifts, overhead cranes or cranes to safely transport, handle
and unpack the Fan and/or parts of it using the required personal protective equipment (PPE).
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 6 of 96
Qualified technician of HDF S.r.l. authorised to provide technical assistance and to
carry out routine and non-routine maintenance works and/or operations not described
in this manual and that require specific knowledge of the Fan, using the required
personal protective equipment (PPE)
The changes made will be documented and a copy of the documentation will be issued to the
Client.
DEPARTMENT MANAGER OR SAFETY MANAGER
See Legislative Decree no. 81/2008 dated 9.04.2008.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 7 of 96
Reading the manual does not relieve the manufacturer from the obligation to carry out general
training and coordinate the staff in a safe manner.
It is assumed that the intended users of this document have suitable ability and professional
preparation for the correct interpretation of the instructions, the indications and illustrations it
contains. Given the characteristics of the Partly Completed Machinery, the training provided by
this Manual cannot disregard adequate professionalism and experience, which is gradually
achieved in the field.
In relation to reading this Use and Maintenance Manual in its entirety, it may not suffice to know,
operate and manage the Fan at its best. It should be considered unless proven to the contrary,
an introduction necessary for all the indicated intended users, so that each can acquire minimum
training necessary to operate the Fan, in relation to personal competence, in an adequate
manner and especially in safe conditions.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 8 of 96
express permission of HDF S.r.l..
It is also forbidden to copy it on any support (magnetic, magnetic-optical, optical, micro-film,
photocopies, etc.) or transfer it to third parties.
The Operator, the staff responsible for maintenance and cleaning, etc., must strictly comply with
the Safety standards in the destination Country of the Fan.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 9 of 96
1.11 Preliminary arrangements that must be provided by the Client (as
stipulated in the contract)
The Client (user) must prepare, under his responsibility, the installation site and the auxiliary system
works necessary for the operation of the Fan as listed below:
preparation of premises;
any lifting devices suitable for moving the Fan;
any safety devices installed upstream/downstream of the power supply lines (required
by the legislation in force;
preparation of the auxiliary services suitable for Fan operation;
any tools and consumable materials necessary for assembly and installation.
In the event of damage or missing parts, immediately inform and provide details/photos to HDF
S.r.l., the carrier and/or the insurance company.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 10 of 96
1.14 Identification of the Fan and Manual number
The job number and abbreviation of the Fan model were outlined on the identification
plate.
The number of this Manual is found on the cover and on the title page of the Manual.
Write the serial number, the abbreviation of the fan model and the Manual number in
a safe place, to request a copy if lost.
type: CN - STD
CENTRIFUGAL
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 11 of 96
The documentation was prepared in compliance with harmonised standard
UNI-EN ISO 12100:2010 paragraph 6.4.5.
The Fan was designed and built in compliance with the Machinery Directive 2006/42/CE.
The side guards required by the Directive must be provided by the end user if not included in
the scope of supply.
It is strictly forbidden to start the Fan without installing the guards.
WARNING
It is forbidden to remove the identification plate on the Fan and/or exchange it with other plates
on the machine.
Reference directives
• Machinery Directive 2006/42/CE of the European Parliament and of the Council of 17
May 2006 on machinery and amending Directive 95/16/CE (recast)
• Directive 2014/30/UE of the European Parliament and of the Council of 26 February
2014 on the harmonisation of the laws of the Member States relating to electromagnetic
compatibility (recast)
• Directive 2014/35/EU of the European Parliament and the Council of 26 February 2014
concerning the harmonisation of laws of the Member States relating to the making
available on the market of electrical equipment designed for use within certain voltage
limits (recast)
• Directive 2009/125/CE of the European Parliament and of the Council of 21 October
2009 establishing a framework for the setting of ecodesign requirements for energy-
related products (recast).
• Directive 2014/34/UE of the European Parliament and of the Council of 26 February
2014 on the harmonisation of the laws of Member States relating to equipment and
protective systems intended for use in potentially explosive atmospheres (recast)
Reference standards
• UNI EN ISO 12499: 2009 Industrial fans - Mechanical safety of fans - Guards.
• UNI EN ISO 12100: 2010 Safety of machinery – General principles for design – Risk
assessment and risk reduction.
• UNI EN ISO 14120:2015 Safety of machinery - Guards - General requirements for the
design and construction of fixed and movable guards
• UNI EN 349:2008 Safety of machinery - Minimum gaps to avoid crushing of parts of the
human body.
• UNI EN ISO 13857:2008 Safety of machinery. Safety distances to prevent hazard zones
being reached by upper and lower limbs.
• ISO 1940-1: 2003 Mechanical vibration -- Balance quality requirements for rotors in a
constant (rigid) state -- Part 1: Specification and verification of balance tolerances
• ISO 14694:2003 Industrial fans -Specifications for balance quality and vibration levels
• CEI EN 60204-1: 2006 Safety of machinery - Electrical equipment of machines - Part 1:
General requirements.
• UNI10893: 2000 Technical documentation of product Instructions for use Structure and
order of content.
• UNI ISO 10015 Guidelines for training.
• UNI EN ISO 7010:2012 Graphical symbols Safety colours and safety signs. Registered
safety signs
• UNI11394: 2011 Technical information - Evaluation system for instructions for use of
technical goods”
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 12 of 96
2 SAFETY PROVISIONS
2.1 Personal protection (PPE)
The presence of a symbol from those indicated below on the Fan or on the Manual requires
compulsory use of the protection devices by the operator, due to an implicit risk of an accident.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 13 of 96
2.2 Safety labels, prohibitions and obligations
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 14 of 96
2.3 Residual Risks
2.3.1 List of residual risks
When the Fan is working, it must be completely isolated and safe for the users.
During TUNING, CLEANING, LUBRICATION and MAINTENANCE, dangerous situations may arise
since you are in a danger zone.
Although HDF S.r.l. provided additional safety systems to prevent access to danger zones, some
parts that require fine tuning, cleaning, lubrication and maintenance operations still present
residual risks.
Danger of burns
The fan poses a risk of scalding by accidental contact with the electric motor or with the fixed
guard of the bearing (due to prolonged use of the fan): they can reach high temperatures
>65°C.
Danger of crushing
If the operators fail to observe the instructions reported in this manual, especially during
maintenance operations, there is a danger of injury by contact with moving parts even if the fan
is in a zero energy state.
Danger of crushing
If the operator fails to observe the instructions reported in this manual, he might get dragged
against the inlet protection grid by the air taken in.
Observe the procedures reported herein and avoid going near the fan inlet while in motion.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 15 of 96
2.3.2 Labels showing residual risks, restrictions and obligations
HDF has placed danger, restriction and specification signs near the relevant zones, repeated
throughout the Manual.
These signs or instructions must be complied with, followed and, in the event of wear or if in any
way illegible, must be immediately replaced.
Only technicians and qualified staff can carry out these operations.
The table below indicates the type of sign, in addition to the generic and electric shock hazards,
its meaning and where it is placed.
DANGER OF CRUSHING
COMPULSORY RESTORATION OF
GUARDS
IT IS FORBIDDEN TO CARRY OUT
MAINTENANCE OPERATIONS ON
MOVING PARTS
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 16 of 96
DANGER OF ELECTRIC SHOCK AT THE MOTOR/
ELECTRICAL PARTS
For cleaning, lubrication and maintenance operations in dark places, you should use portable lamps.
The installer must check that the electrical system where the
Fan will be installed is provided with good earthing, sufficient
for the rated power consumption and, otherwise, adjust said
system. The system which will connect the fan to the mains
must be CE marked.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 17 of 96
For handling of parts of the unpacked Fan, please refer to
Chapter 4 “Lifting and installation instructions” of this
Manual.
Never lift the components using their casings or protruding
parts as connection points.
Only use the lifting devices listed in Chapter 4 of this Manual.
During:
Transport
Positioning
Installation
Fine tuning for production
Maintenance, lubrication and cleaning
pay utmost attention to protruding parts
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 18 of 96
For any problems that may arise during fine tuning and during
the manufacturing cycle, press the EMERGENCY-STOP button
Never rest or sit on any part of the Fan, neither when the parts
are moving nor when the same are at a standstill. It is
forbidden to climb on the fan. Use a ladder, an adequate
scaffolding and a man basket to access the top side of the
machine.
For any problems that may arise during fine tuning and
during the manufacturing cycle, press the OFF button.
Where possible, always wear goggles, adequate gloves, safety footwear, and use the same
as needed.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 19 of 96
In any case, do not wear objects and/or clothing that is loose and/or with ties (collar, watches, rings, bracele
foulard, ties, etc.); it is forbidden to wear objects that may get entangled in the parts of the fans.
WARNING
DANGER OF CRUSHING/SHEARING:
If intervention is necessary, always wait for the impeller
to stop. IT TAKES SEVERAL MINUTES. FOR THE
IMPELLER TO STOP DO NOT remove the railing or the
duct.
WARNING
PROJECTION HAZARD
Balance weight detachment or impeller breakage due to foreign
objects sucked into the fan may pose a risk of projection of
material fragments.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 20 of 96
WARNING
DANGER OF CRUSHING
Wear protective gloves.
During fan operation, do not:
- remove the guards
- touch the drive belts.
WARNING
DANGER OF BURNS:
The operator must take care of the space and the floor around
the Fan ensuring it is always clean, to avoid slipping and as a
result impacts and/or falls.
The floor, other than being clean, must be dry.
Do not tamper or disable or disconnect, for any reason, the safety micro-switches or any other
safety devices (fixed and movable guards), do not create by-passes and do not use safety
devices for purposes other than those set out and for which they were installed. Periodically
check their efficiency
Never reach into the guards during the manufacturing cycle.
In particular:
a) it is strictly forbidden to remove the side guards;
b) do not remove the guard of the drive belt.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 21 of 96
2.5 Spare parts
Only use HDF original spare parts if worn and/or broken pieces must be
replaced.
To search and proceed to order, refer to the Spare Parts List or contact
HDF srl – Sales Department. HDF S.r.l. shall not be held liable for any
machine malfunction in case of use of non-original spare parts.
This will also void the warranty and render the EC declaration of
conformity null.
If not present, do not start the fan and immediately inform HDF srl
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 22 of 96
2.7 Noise level
The Fan does not require the constant presence of an operator during
operation.
The Fan is noisy.
The noise level may exceed 80 dB(A), therefore you are advised to use earmuffs or earplugs for
any exposure to noise, either slight or continuous.
Produce a stream of air, gases or vapours by increasing its pressure, with variable flow
rate and head depending on the model.
Vapours or gases shall conform to the characteristics of the model.
Any application other than described above must be assessed by HDF technical department.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 23 of 96
strictly follow the procedures in this Manual described for activation and disabling;
check that performance complies with the intended service (work cycles, usage times);
ensure that the Fan can operate under the ambient conditions stated in the offer.
comply with the signs highlighted. Compliance with the above also has an accident-
prevention function; these signs must always be perfectly legible;
ensure adequate preservation (cleaning, lubrication) and maintenance of the Fan and all
its parts;
check the correct anchorage of the guards, the Fan, the mechanical and electrical limit
switches;
check that the stop/emergency buttons are working;
check that the control panel is intact and working properly;
cut power supply to the Fan in the event of inspection, repair, and routine maintenance
interventions. Disable the transmission mechanically;
for all operations, use the personal protective equipment (PPE) suitable for the activity to
perform, in compliance with the safety standards at workplace;
notify the Department Manager of any anomalies (faulty behaviour, suspected breakage,
improper movements and irregular noise) and put the Fan out of service;
respect the frequency of the maintenance and adjustment operations and fill out the
maintenance record upon every intervention, also including any relevant comments;
check the functional efficiency of the safety devices of the guards;
check the correct anchorage of the guards;
DANGER!
*NEVER:
allow people to pass through the lifting and moving area of the Fan and its parts;
try to lift parts of the Fan if they or the fan are unbalanced or if the lifting equipment is not
correctly connected in relation to the centre of gravity of the load;
put your hands in the vicinity of the lifting cables during lifting; put your hands in the areas
of contact with the hook of the hoist during “tensioning”;
leave parts of the Fan suspended or unattended during lifting;
swing the Fan or its parts during lifting and handling;
change the driving direction suddenly during handling;
never heat the frame of the Fan or its parts with a blowtorch or other heat sources;
allow unqualified staff or people under 16 years of age to use the Fan;
use the Fan if not physically-mentally suitable;
weld the Fan, or carry out any welding filling operations;
work in areas in which use of spark-proof parts is specified or in the presence of strong
electromagnetic fields;
change its functional/performance characteristics;
carry out temporary repairs or resets not complying with the specifications in the
Instructions Manual;
change, decalibrate, tamper with the Fan;
use non-original spare parts or parts not recommended by HDF S.r.l.;
entrust maintenance and repair operations to staff not trained by HDF S.r.l.;
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 24 of 96
abandon the Fan at the end of work without implementing the relevant safety procedures;
use the Fan for services other than its intended use and avoid using it as a resting point
for ladders or as a base to replace lamps, etc.;
use its frame as a grounding for welders;
use the Fan in potentially explosive atmospheres
use the Fan in improper ambient conditions.
Respect the temperature range, from -10°C to +45°C, and the humidity range, from 30%
to 80% (unless otherwise specified by HDF S.r.l.);
carry out ordinary maintenance operations, inspections or repairs without having placed
the Fan out of service and having activated the relevant safety procedure.
during the maintenance phases:
- use unsuitable devices;
- work without personal protective equipment;
- work without locking the disconnect switch and use adequate lighting in the
operating zone;
clean with aggressive liquids or that can damage its parts;
expose the Fan to the action of sprayed liquids;
disconnect components.
carry out cleaning operations with compressed air inside the electric box;
grease the drive belts;
disconnect pneumatic system components before closing the outlet and releasing the residual
pressure.
remove the guards completely or partially or loosen their fasteners
keep the fan running with closet inlet/outlet for more than 15 minutes.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 25 of 96
3 TECHNICAL DESCRIPTION AND SPECIFICATIONS
3.1 Technical description
The industrial fan (hereinafter referred to as fan) is a turbomachine that receives mechanical energy
and utilises it by means of an impeller fitted with blades to maintain a continuous flow of air or
other gas passing through it and whose work per unit mass does not exceed 25 kJ/kg (UNI EN ISO
13349).
Radial flow fan (centrifugal): fan in which the air enters the impeller with an essentially axial
direction and leaves it in a direction perpendicular to this axis.
The blades:
negative where the fluid is processed by the back, convex side;
positive where the fluid is processed by the front, concave side; radial or straight where
the fluid is processed either with the back or the front side of the blade if there are no
stiffeners on either side.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 26 of 96
3.3.A. Type of impellers for centrifugal fan
3) – radial
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 27 of 96
3.4 Arrangements
Arrangement 4
Arrangement 5
Single-inlet fan for direct drive.
Arrangement 7
Arrangement 8
Arrangement 9
Arrangement 10
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 28 of 96
Arrangement 12
Arrangement 13
Note: other executions can be performed. This does not change the requirements
and/or the indications included in this manual.
Direction of rotation
LG Rotation RD Rotation
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 29 of 96
The discharge positions RD, LG 180 and 225 are possible only after making adequate
adjustments
Axial fans are mounted in the same way as centrifugal fans, taking into account that the air flow is
always axial
The direction of rotation is defined for an observer on the side of the transmission (motor).
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 30 of 96
4 LIFTING AND INSTALLATION INSTRUCTIONS
WARNING
DANGER OF CRUSHING, KNOCKING, ABRASION AND CUTTING
The staff responsible for Fan handling must have read the Safety Provisions at the beginning of
this Manual (Chapter 2), must wear overalls, gloves, safety footwear and a helmet.
ATTENTION
THE CENTRE OF GRAVITY OF THE FAN IS LOCATED AT THE CENTRE OF THE FRAME.
THEREFORE, THE FAN IS BALANCED
4.1 Foreword
Upon package delivery, the staff in charge with handling must follow the instructions outlined
in this Chapter, step by step.
The HDF technician (where present) is the person who dismantled or assisted the dismantling
process in the factory after testing and is the contact person and the person who will assemble
the Fan.
The instructions in the entire Chapter 4 are used as a memo if handling of the Fan, unpacking
and handling of parts of the Fan is carried out without the supervision of the Technician in
question.
Before proceeding with the positioning of the Fan, ensure that the support surface and all the
connections comply with the specifications provided beforehand and with the civil works’ layout.
A copy of these specifications is given in Chapter 8 “Diagrams and Attachments”.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 31 of 96
WARNING
Lift the fans with due care and caution during transport,
paying utmost attention to protect the impeller and the
shaft against shocks and collisions using wood or rags.
ATTENTION
DANGER OF FALLING AND/OR TRIPPING AND
CRUSHING
Cordon off, or in any way, prevent access to staff not
unauthorised to carry out handling operations or those
unaware of the dangers related to this phase.
DO NOT REMOVE THE BARRIERS UNTIL THE FAN
POSITIONING AND FIXING OPERATIONS ARE
COMPLETED.
WARNING
DANGER OF CRUSHING
The various parts are tied and spaced with wood shims inside the packing case, for transport
reasons.
These ties (iron wires and supports) and shims must not be removed when taking off the lid of
the packing cases. There is a danger of crushing due to moved loads.
These ties are to be removed when picking up the component.
For this reason, the person in charge of picking up and slinging the components must wear
safety footwear, protective gloves and a helmet and must proceed with due care.
The Fan is intended for use in industrial environments.
The workplaces must be equipped with devices that provide adequate artificial lighting to
ensure the safety and health of the Operators.
Workplace lighting must comply with the Laws in force in the Country where the Fan is
installed and must be even and ensure good visibility from every point, without causing
dangerous glare effects.
The lighting must allow for the safe execution of the maintenance operations covered in this
Manual.
The floor must be level and able to support the Machine (especially if it is not installed on the
ground floor).
There must be sufficient space for maintenance (minimum 1 meter).
The Fan must be installed according to the layout in Chapter 8 “Diagrams and Attachments”.
WARNING
The work area must always be kept clear so that NOTHING AND NOBODY interferes with
the free movement of the operator.
In the event of an emergency, immediate access must be guaranteed to the control devices of
the Fan by the responsible staff.
Access to the work area is forbidden to those not directly responsible for Fan operation.
This restriction is necessary to avoid danger due to lack of attention or negligence when
performing tasks.
The operator should therefore always keep the work area clear of any Equipment and deny
access to unauthorised persons in order to have the ideal safety conditions to work with the
Fan.
IF THESE CONDITIONS ARE NOT MET, PROVIDE FOR THEM BEFORE INSTALLING
THE FAN.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 32 of 96
‐ do not roll the impeller if you can move it with
cables.
If you have to roll the impeller, place it on a smooth
surface and proceed with due care
‐ never place the impeller on the ground with its
weight leaning on the shaft; place wood shims
beneath the shaft close to the impeller (any shaft
deformation will cause vibrations).
‐ Coated impellers must be handled with due care and
should never be moved by rolling.
Road transport
Road transport takes place by truck.
Depending on the requirements, the various parts of the Fan can be:
- fixed to a load bearing platform (or crate). The various parts can also be covered with
cellophane, shrink wrap or bubble wrap to protect them from atmospheric agents.
- fixed on wooden or metal feet. The various parts can also be covered with cellophane, shrink
wrap or bubble wrap to protect them from atmospheric agents.
The Customer must dispose of the packaging in compliance with the Standards in force in his
Country (refer to Chapter 10 “Dismantling and Disposal”).
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 33 of 96
4.2 Handling of the packed Fan and its parts
The Fan and its parts may be shipped in a packing case, a crate or on a pallet.
Whatever the case, the Fan is always delivered assembled in a single pack
NOTE
IF THE COMPONENTS ARE NOT TO BE UNPACKED IMMEDIATELY UPON RECEIPT,
STORE THEM IN A DRY, COVERED ENVIRONMENT WITHOUT REMOVING THEIR
PACKAGING
For handling:
of packing cases and pallets with a forklift truck > section 4.2.1;
of packing cases and pallets with overhead crane and cables > section 4.2.2.
On the outside of the packaging are specified all the instructions necessary for handling as
well as the name of the Customer, order, gross and net weight.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 34 of 96
4.2.1 Handling of packing cases and pallets with a forklift truck
• Follow the indications on the packing case or on the pallet (especially the position of forks
and centre of gravity): be reminded that the position of the forks is the widest possible (a);
• use a forklift truck of suitable capacity; the forks must protrude out of the packing case or
pallet by at least 15 cm. (b);
• slowly move the packing case or the pallet, at minimum height from the ground (max. 20
cm) supported by an assistant if view is obstructed (c);
• lay it gently on the ground (d);
• to open the packing case, use an appropriate mean (such as a crowbar); start from the
cover (e).
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 35 of 96
4.2.2 Handling of packing cases and pallets with overhead crane and cables
Take two cables or straps with minimum length 4 m and minimum capacity adequate for
the load to be lifted, with eyelets at the ends in good condition (a);
harness the packing case or the pallet by following the indications on it (position of the
cables, centre of gravity and weight) (b);
slowly move the packing case or the pallet, at minimum height from the ground (max. 20
cm) supported by an assistant if view is obstructed (c);
lay it gently on the ground;
to open the packing case, use an appropriate mean (such as a crowbar); start from the
cover (e).
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 36 of 96
4.2.3 Handling from a container
Once the container is prepared and opened, handle the Machine as indicated in paragraph “4.3
HANDLING OF THE UNPACKED MACHINE”.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 37 of 96
4.3 Unpacking
WARNING
The carts should be positioned next to the uprights,
NEVER ONLY ON THE CROSSBARS.
HDF S.r.l. RECOMMENDS, IN CASE THE MACHINE PARTS ARE TO BE PACKED BACK,
TO STORE IN A DRY PLACE THE ENTIRE STRUCTURE OF THE PACKAGE AND ITS
LOCKING COMPONENTS
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 38 of 96
4.4 Storage
If the machine is not installed immediately upon receipt and is fitted with antifriction bearings,
rotate the shaft of the fan manually or in a similar manner for several turns, once every 2 or 3
weeks.
This way, the grease inside the bearings will cover any less protected parts of the bearing,
also preventing condensation.
Lock the impeller to prevent any accidental rotation due to air draughts
If the Fan is fitted with drive belts, we recommend reducing the belt tension by slightly
loosening the turnbuckles.
The belts must be tensioned properly shortly before starting the machine.
Periodically, check the condition of the parts to avoid surface oxidation.
After long periods of inactivity, the machine must be commissioned by HDF S.r.l. technical staff
or by technical staff authorised by HDF S.r.l., ensuring that:
the conditions and characteristics of the Fan before storage have been kept
unchanged;
there are no signs of corrosion on the frames;
here are no signs of breakage due to improper storage;
the electrical connections are efficient and there are no damaged cables;
the pneumatic connections are efficient and there are no broken pipes;
that all safety devices installed, tested manually are efficient.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 39 of 96
4.5 Disposing of the package
The disposal of waste materials must be made in compliance
with the regulations in force in the Country of use, taking
into account the nature of the materials:
straps, nails and metal parts;
wood and plywood planks;
plastic materials (protective film and barrier bag).
WARNING
DANGER OF SUSPENDED LOADS
BE VERY CAREFUL.
WARNING
Handling must be performed according to the specifications in
this Chapter only; never harness the various elements on their
protruding parts.
For the handling operations, you can use a forklift truck, an overhead crane or a crane
Handling with a forklift truck
When handling the machine with a forklift, always comply with
the following principles:
a) the forklift must have a capacity suitable for the load
to be transported;
b) observe the centre of gravity;
c) observe the input position of the forks;
d) if the position of the forks is not indicated, keep the
distance between them as great as possible;
e) the forks must be longer than the body to move and
protrude by at least 10 cm.;
f) handling must be done at minimum height above the
ground (max. 20 cm);
g) if visibility is hampered, get help from an assistant;
h) lay it gently on the ground.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 40 of 96
Handling with a crane or overhead crane
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 41 of 96
4.7 Handling of loose or light parts
The lighter parts refer to:
boxes containing small parts;
technical documentation;
parts of the pneumatic system;
cables and electrical connectors;
other small accessories
Due to their nature and their small size, all lightweight parts are placed on the base in separate
packing cases, some of them tied up to the fan, others simply placed next to it.
This is why before handling the fan, YOU SHOULD REMOVE the lightweight parts first.
Place them close to the place of installation, so that they do not fall and do not impede the
movement of the other parts.
4.8 Foundations
A rigid and level foundation is essential for the stability of the fan and prevents the formation of
vibrations.
The most suitable foundations for fans, motors, etc. are those made of reinforced concrete. Suitably
reinforced steel frames can also be used.
Reinforced concrete foundations must be sized considering the static and dynamic loads of the
fans.
The foundation bolts must be cemented into metal tubes; the diameter of said tubes must be
two and a half times larger than the diameter of the bolt to ensure better adjustment during
concrete consolidation (between 24 and 48 hours depending on the case).
The number of foundation bolts or chemical plugs must match the number of holes in the base
of the fan.
Leave a small space of about 10÷15 mm between the concrete surface of the foundation and
the bottom wire of the metal base that will be filled with shims and levelling materials.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 42 of 96
4.8.2 Foundation with steel frames
The fan fixture must be rigid enough to block any vibrations to the fan.
The first natural frequency at any point on the frame should be 50% greater than the frequency
corresponding to the speed of the fan and of the motor.
The frame must be reinforced with adequate stiffeners to ensure and maintain its proper alignment.
Suitable anti-vibration mountings must be bolted to the frame before mounting the fan.
ATTENTION!
The Engineer and the Manufacturer are responsible for the proper sizing and selection of the
materials used to build the foundation.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 43 of 96
4.9 Inlet and outlet ducts
After installing the fan, you can connect the inlet and outlet ducts.
The connections should not force the position of the fan because any deformation of the casing
may cause the fixed and mobile inlet cones to touch, may result in misalignments, etc.
The ducts must be connected in such a way as to prevent any static loads, vibrations and thermal
growths from affecting the fan.
To meet this requirement, particularly when the temperature of the conveyed fluid exceeds 100°
C, you might have to fit the inlet and outlet ducts with an expansion joint made of a suitable
material (evaluation to be conducted upon express request, with adequate analysis of
temperatures).
These joints must be installed between the fan and the duct, upstream of any inlet dampers or
downstream of any outlet dampers (where applicable).
In particular, the fan must be fitted with this kind of flexible connections if installed on anti-vibration
mountings.
When installing the flexible connections:
ATTENTION!
Any openings not connected to ducts must be provided with adequate protection grids in
compliance with standard ISO – 12499/1999.
According to standard ISO – 5801/5802, for the openings connected to ducts, in case of fans with
installation type “B”, “C”, “D”, special precautions must be taken to prevent the ingress of foreign
bodies inside the fan through the conveyed fluid.
In order to ensure consistent fan performance, the ducts must be connected in such a way that
the fluid flow is as even as possible, avoiding the formation of vortices.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 44 of 96
4.10 Positioning and installation of the Fan
WARNING
DANGER OF SUSPENDED LOADS, CRUSHING, IMPACT, ABRASION AND CUTTING
The staff responsible for Fan positioning and installation must have read the Safety Provisions
at the beginning of this Manual (Chapter 2), must wear overalls, gloves, safety footwear and a
helmet.
The fan is usually supplied completely assembled but since it can also be supplied disassembled
and during its service life you might have to replace different components, this section described
the assembly procedure for each component of the fan.
All fans undergo inspections before shipment to check the correct assembly and the conditions
of all the components and accessories installed; therefore, if the fan is supplied already
assembled, make sure it does not present any visible signs of damage due to transport and/or
handling and proceed with its installation.
Should you notice any signs of damage, suspend the installation and follow the instructions in
par. 2.2
If the fan was supplied disassembled, check the condition of the various parts and/or accessories
and proceed with their assembly following the procedures below.
Said procedures must be followed whenever you need to disassemble and re-assemble the fan
or parts of it (for maintenance, components’ replacement, etc.).
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 45 of 96
4.10.2 Checks before the assembly
1 Make sure that the fan has not been damaged during transport.
2 Make sure that the casing and the impeller match the type of fan requested.
3 For models supplied assembled, check the discharge position of the casing (0°, 45°, 90°...)
and the direction of rotation of the impeller (LG = counter clockwise or RD = clockwise)
identified by an adhesive label (arrow) applied on its outside.
N.B. The correct discharge position of the casing must be checked referring to the “discharge
position table” in the “catalogues”.
The direction of rotation of the impeller must be identified from the side of the electric motor.
For axial fans, check the direction of rotation and orientation: motor - revolutions or motor
impeller
4 Make sure that the electric motor (to be provided by the customer) to be installed on the fan
has the same technical, construction and performance characteristics as those specified in
the order.
5 Make sure that the electric motor mounting holes on the pedestal base match the electric
motor mounting holes on the fan (see the manual of the electric motor attached).
6 Make sure that the fixing bolts of the electric motor are tightened to the fan.
7 Make sure that the diameter of the hole of the impeller matches the electric motor shaft and
that the diameter of the shaft matches that of the coupling/pulley.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 46 of 96
there must be a minimum clearance of 1.5 m around the machine for maintenance,
passage of forklift trucks;
the Customer is responsible for the verification and/or sizing of the supporting
structure.
IF THESE CONDITIONS ARE NOT MET, PROVIDE FOR THEM BEFORE INSTALLING THE FAN.
NOTE
The Fan must be fixed to the Machine ONLY:
by HDF S.r.l. staff (if specified in the contract);
by the Customer's Technical staff trained for this type of activity.
WARNING
GENERAL HAZARDS AND RISK OF
ELECTRIC SHOCK
These operations must be carried out by a single professionally
qualified Technician, NEVER BY MORE THAN ONE PERSON.
The Technician must have read and understood the Safety Provisions (Chapter 2) at the
beginning of this Manual.
He also needs to ensure that, while performing the connections, no other person is present
in the designated Fan area or its energy source areas.
Any pneumatic equipment installed on the fan must be connected following the instructions
provided by the manufacturer of said equipment and attached to this Manual.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 47 of 96
4.11.2 Connection of the motor and/or electrical equipment
Refer to the wiring diagrams of the Fan and/or electrical motor before making any connection
and make sure that both motor and fan earthing bosses are connected to the main earthing
system. Also check the efficiency of the earthing system and check the continuity of the
protection circuit installed on the Fan
CAUTION!
If the fan is installed at a distance from the panel and/or control station,
provide an omnipolar service switch next to the fan.
THE FANS THAT COMPLY WITH THE ATEX DIRECTIVE 2014/34/UE MUST BE
INSTALLED BY A QUALIFIED TECHNICIAN FOLLOWING THE APPLICABLE
REGULATIONS IN FORCE.
CAUTION
Do not use air pipes (extensions) and transition pieces unsuitable or that do not
comply with the regulations in force.
Do not commission the fan before connecting it correctly to the extraction system
available at the site of installation.
Do not commission the fan if the extraction system in which it is to be installed has
not been declared compliant with the provisions of the applied directive.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 48 of 96
5. COMMISSIONING
5.1 First start-up and testing
Before shipment, the Fan undergoes a pre-testing at the HDF S.r.L. premises.
This pre-testing phase includes all the adjustment and calibration operations required by the
mechanical parts and the electrical devices
It is the responsibility of the HDF technician in collaboration with the Customer’s technician to
optimise the fan’s performance for the operations specified in the order confirmation.
In standard version, the Fan is not equipped with a lighting system.
The light level must ensure safe operation at all times.
If you need to perform maintenance operations in poorly illuminated areas, please use portable
lighting systems paying attention to avoid any shadows that may reduce the visibility of the
point concerned by the maintenance work or of the surrounding areas
For the first seals set up and maintenance please refers to the dedicated section at chapter 7
(Maintenance, cleaning and lubrication).
CAUTION!
NEVER start the fan if there are any free, unprotected openings.
If the fan is not fitted with the necessary guards, the installed must provide them in compliance
with standards UNI EN 14120:2015 and UNI EN 13857:2008.
For fans with belt drive delivered assembled, the alignment was performed at the HDF premises.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 49 of 96
5.3 Start-up procedures
1. The start-up procedure must be carried out with the damper or the flow regulator (where applicable)
completely closed to decrease the time and therefore the overload of the motor upon start-up.
2. Start the motor.
3. Check if the direction of rotation of the impeller is correct: if the impeller should rotate in the
opposite direction, interchange the connections of two phases pf the power supply line (for
three-phase motors).
4. Check that the motor rotates in the correct direction of rotation according to the manufacturer's
instructions.
5. Once the fan reaches the operating speed, open the dampers at least partially (where
applicable) to prevent the overheating of the fan.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 50 of 96
6. USE AND OPERATION
6.1 Checks before switch-on
The operations to be carried out by the HDF Technician before start-up are as follows:
make sure that you have all the manuals necessary for the correct use of the fan and its
accessories and components (eg electric motor, actuator, sensors, etc);
visual inspection of the area where the Fan is installed;
make sure that the fan is correctly positioned;
make sure there are no unauthorised persons in the vicinity of the fan;
make sure that the safety devices are in good condition, correctly installed and working
properly;
Make sure that the bearings are lubricated;
make sure the machine is level;
make sure the bolts of the impeller, of the bearings and of the electric motor are tightened properly;
connect the system to the mains;
check the direction of rotation of the fan impeller;
make sure that all parts can rotate freely;
make sure to read and understand this “Use and maintenance manual” in its entirety.
To prevent any electric motor overload, we recommend switching on the radial-flow fans with
the damper or the flow regulator closed.
If the valves are controlled automatically, we recommend checking the opening time (in the case
of high-pressure, if this setting is too low it may lead to vibrations and “water hammer” effects
that are dangerous for the mechanics of the fan).
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 51 of 96
6.3 Checks after switch-on
Make sure that the direction of rotation of the impeller matches the direction indicated by the
arrow (nameplate affixed to the outside of the fan)
Recommended measuring points: at the fan mountings, perpendicular to the axis of rotation on
the horizontal or vertical plane (near the bearings).
We recommend installing vibration sensors.
Make sure the temperature of the bearings when the fan is running at full capacity is normal
At an ambient temperature of 20 ° C, the optimal temperature of the substrates must be less
than about 90 ° C.
Attention, during the first hours of operation the temperature may exceed the indicated value;
it will then stabilise to a lower value.
Measuring point: outer ring of the bearing regardless of the ambient temperature.
We recommend installing temperature sensors.
Make sure the temperature of the bearings when the fan is running at full capacity is normal.
Make sure the bolts are properly tightened after a few hours of operation.
Check the tension of the belts (where applicable)
Use an ammeter to check the absorption on three line conductors (L1, L2, L3).
ALWAYS WAIT FOR THE ELECTRIC MOTOR TO COOL DOWN BEFORE STARTING THE FAN
AGAIN.
1
ALARM: warning signal when the vibration level reaches a certain value or when there is a significant change
in the vibration level that requires a corrective action. The fan operation may proceed until the cause of the
alarm is identified and the corrective action is taken.
2
STOP: it indicates the vibration limit beyond which the machine might get damaged. The machine stops as
soon as this value is exceeded.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 52 of 96
6.5 Emergency stop
WARNING
DANGER OF CRUSHING/SHEARING:
Do NOT approach the rotor area.
Wait for the impeller to stop.
Before accessing the area, place all necessary maintenance signs and take all the required
measures described in Chap. 2
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 53 of 96
7. MAINTENANCE, CLEANING AND LUBRICATION
7.1 Foreword
All maintenance, cleaning and lubrication operations must be carried out with the Fan in a zero
energy state, using all necessary PPE.
Therefore, the staff responsible for maintenance of the Fan must have fully read Chapter 2
“Safety Provisions”, in particular:
the FUNCTION OF THE MAIN SWITCH AND OF THE EMERGENCY BUTTONS: keep in
mind that it must be set to “OFF” or pressed in case of emergency;
the FUNCTION OF THE CONTROLS;
the SYSTEM IN A ZERO ENERGY STATE;
the OPERATOR;
the MECHANICAL MAINTENANCE TECHNICIAN;
the ELECTRICAL MAINTENANCE TECHNICIAN OR QUALIFIED PERSON;
the DEPARTMENT MANAGER OR SAFETY MANAGER;
the WARNING LABELS INDICATING THE PRESENCE OF RESIDUAL RISKS,
RESTRICTIONS AND OBLIGATIONS;
the PERSONAL PROTECTIVE EQUIPMENT.
In particular, how to bring the Fan to a ZERO ENERGY STATE, essential for carrying out all the
operations safely, and the required Personal Protective Equipment (PPE).
The maintenance operations described here reflect the way in which the HDF technician
behaves, phase by phase.
They are therefore the procedures to which the technician adheres if future tuning or
maintenance has to be carried out.
Fence off the area and place a sign that indicates works in
progress on the mains switch and on the fence:
“MAINTENANCE IN PROGRESS”.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 54 of 96
NOTE:
IF THE DEVICE IS KEPT CONSTANTLY ADJUSTED, AS DESCRIBED IN THIS MANUAL, THERE IS
NO NEED FOR OTHER MAINTENANCE, OTHER THAN THOSE INDICATED HERE.
CAUTION
Following intervention that involved dismantling and re-assembly of important parts, always
check the continuity of the earthing circuit.
General information:
WARNING
To correctly carry out cleaning, use a bag for equipment
and detergents authorised in the Country where the
Fan is installed and use them as needed. Only use
equipment suitable for cleaning operations.
NEVER use equipment with sharp edges that could
damage the mechanical elements.
If the work must be done at height, use an adequate
safety ladder.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 55 of 96
Check that the amount and/or type of lubricants used match the indications. Never mix
lubricants of different quality or brand.
Long periods of storage will reduce the efficiency of the oil or grease even if stored
properly; therefore, they must be replaced every two years.
During long storage period, lubricated rotating parts should be rotated every
month, even by hand where possible, to restore the lubrication (for ex. Rotate the
bearings by hand to re-establish the protection of rotating elements)
Do NOT use wire sponges or cleaning products that may pollute or alter the characteristics of
the lubricants.
The product must be cleaned with adequate means and detergents that do not
affect the painting or the gaskets; it is strictly forbidden to clean or wash the
product with water jets.
HDF disclaims any liability in case of failure to comply with the maintenance intervals
reported in this manual and in the documentation attached to it, or if the maintenance
works are assigned to incompetent staff or that adopts procedures or uses lubricants
with other characteristics than those indicated herein.
When ordering spare parts, please order only original spare parts.
Based on the hours of operation, the maintenance works can be classified under:
scheduled maintenance:
maintenance works carried out at pre-set intervals (example lubrication or replacement
of worn parts);
occasional maintenance:
works carried out in the event of an accidental malfunction and/or fault (example
replacement of a fuse or a light bulb).
Based on the technical/economic importance or the frequency of intervention, the following types
can be distinguished:
routine maintenance:
works involving simple execution and low technical/economic value;
non-routine maintenance:
repair and/or replacement intervals of significant technical and/or economic importance;
normally, they are necessary following rare or unexpected faults and require the use of
qualified HDF S.r.l. or Client staff.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 56 of 96
7.2 Scheduled maintenance
To guarantee the complete efficiency of the fan, you need to comply with the times and methods
indicated below.
The checks related to maintenance operations are:
• general visual inspections;
• functional tests;
• checking the efficiency of the safety devices;
• checking the guards are intact, efficient and fastened;
• checking the noise generated by the bearings;
• restoration of any calibration;
• replacement of pneumatic components;
• replacement of mechanical components in general;
• checking the proper tensioning of the drive belts;
• checking the correct balancing of the impeller.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 57 of 96
MAINTENANCE INTERVALS
NOTES:
For the points marked with:
(*) the tripping time value is only indicative.
(**) to consider dusty fluid if dust content is ≥ 100 mg/Nm³.
(***) intervention and related intervals shall be in accordance with Motor manufacturer manual
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 58 of 96
7.2.1 Fan casing cleaning
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 59 of 96
7.2.3 Impeller Cleaning (for dusty fluids)
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 60 of 96
7.2.5 Dampers’ cleaning
WARNING
CUTTING HAZARD
WEAR PROTECTIVE GLOVES
Do not use compressed air, but a vacuum cleaner, to remove all dust or any other residues.
If there are small lumps, use a cloth (or sponge) slightly dampened with water.
Once you have completed the cleaning, DRY PROPERLY with the moistened cloth.
Proceed to dampers’ cleaning based on the dust accumulated.
For machines servicing rooms classified as "clean" (dampers with servocontrol), provide for a
periodic inspection.
Attention: it is not possible to define a standard maintenance interval for fans working in a
dusty / abrasive environment. Define the interval of cleaning, checking and maintenance
according to the conditions of use of the machine. After a certain period of monitoring, define
the most suitable interval for the use of the machine. Frequently check the condition of the
dampers and its operating mechanisms to avoid any damage to the machine.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 61 of 96
7.2.6.1 Antifriction bearing lubrication with grease (SEPARATED BEARINGS)
The bearings of the fans shipped already assembled have been lubricated at the HDF, premises
but their lubrication condition should be checked prior to start-up.
The bearings of the fans shipped unassembled or those shipped as replacement or spare parts
are not usually greased.
Before greasing the bearing, clean it thoroughly.
Remove any trace of rust preventative or dirt using clean oil.
Then dry the bearing carefully with air or clean rags.
Remove any trace of rust from the shaft, the bearings and their housings before proceeding
(use wire wool without removing material from the shaft as this would damage its shape and
finishing).
For best results, we recommend using the same grease throughout the entire lifespan of the
part because nor all greases are chemically compatible.
If you have to use a different lubricant, remove any trace of the old lubricant before applying
the new one.
Use a pneumatic grease gun.
Fill the bearing housing up to about 1/3.
Any excess grease may cause bearing overheating.
For standard machines the LGMT 2 (relatively low rotation speed and standard temperatures) is
installed, while LGHP 2 is installed for fast machines and / or working with high temperature
fluid.
LGMT 2 grease is a grease composed of mineral oil and lithium soap (thickener), NLGI 2
consistency class, with dripping point> 180 ° C (DIN ISO 2176), penetration 265/295 mm / 10
(DIN ISO 2137 ), maximum temperature 120 ° C.
LGHP 2 grease is a grease composed of mineral oil and Di-urea (thickener), consistency class
NLGI 2-3, with dripping point> 240 ° C (DIN ISO 2176), penetration 245/275 mm / 10 (DIN ISO
2137), maximum temperature 150 ° C.
Depending on the type of bearing, the quantity of grease relative to the initial filling is shown
below.
For smooth long lasting operation, we recommend checking the lubrication of the bearings
frequently.
For antifriction bearings is usually intended a maximum temperature of 75/85 °C (measured at
the outer ring) when used in a regular workshop environment, even though higher temperatures
are acceptable (see Chapter 6.3).
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 62 of 96
The lubrication intervals shown in the table below refer to the aforementioned conditions and
are indicated according to the different types of bearings and their rotational speed N.
Shaft Grease
diameter Support quantity Bearing 750 1000 1250 1500 1750 2000 2250 2500 2750 3000
[mm] [gr]
22207 EK 3380 2510 1990 1650 1400 1220 1060 930 830 740
30 507 50
2207 EK 33800 25100 19900 16500 14000 12200 10600 9300 8300 7400
22208 EK 3010 2230 1760 1450 1240 1080 920 810 710 640
35 508 60
2208 EK 30100 22300 17600 14500 12400 10800 9200 8100 7100 6400
22209 EK 2640 1940 1530 1260 1070 930 790 690 600 540
40 509 65
2209 EK 26400 19400 15300 12600 10700 9300 7900 6900 6000 5400
22210 EK 2510 1840 1440 1170 990 850 730 630 550 490
45 510 75
2210 EK 25100 18400 14400 11700 9900 8500 7300 6300 5500 4900
22211 EK 2380 1750 1340 1090 910 780 660 580 510 450
50 511 100
2211 EK 23800 17500 13400 10900 9100 7800 6600 5800 5100 4500
22212 EK 2250 1650 1250 1000 830 700 600 520 460 410
55 512 150
2212 EK 22500 16500 12500 10000 8300 7000 6000 5200 4600 4100
22213 EK 2120 1550 1160 910 740 620 530 470 410 -
60 513 180
2213 EK 21200 15500 11600 9100 7400 6200 5300 4700 4100 3700
22215 EK 2020 1480 1090 860 690 580 490 420 - -
65 515 230
2213 EK 20200 14800 10900 8600 6900 5800 4900 4200 3700 3200
22216 EK 1920 1400 1030 800 650 540 450 - - -
70 516 280
2216 EK 19200 14000 10300 8000 6500 5400 4500 3800 3200 2800
22217 EK 1810 1320 960 740 600 490 400 - - -
75 517 330
2217 K 18100 13200 9600 7400 6000 4900 4000 3300 2800 2400
22218 EK 1710 1250 900 690 550 450 - - - -
80 518 430
2218 K 17100 12500 9000 6900 5500 4500 3600 2900 2400 2000
22220 EK 1700 1130 790 590 460 - - - - -
90 520 630
2220 K 17000 11300 7900 5900 4600 3700 2700 2100 1700 1300
22222 EK 1680 1020 690 500 - - - - - -
100 522 850
2222 K 16800 10200 6900 5000 3700 2900 1900 1300 900 700
22224 EK 1410 890 610 430 - - - - - -
110 524 1000
The color of the cells indicates the type of first filling grease depending on the size of the
bearing and the speed:
SKF – LGMT2
SKF – LGHP2
For temperatures at the outer ring of the bearing between 90 °C and 110 °C, the lubrication
interval must be halved for each ΔT= 15° C. Also, if used in dusty, humid, hot or corrosive
environments, the interval indicated in the table must be reduced accordingly.
If used under normal conditions, i.e. without being affected by external heat sources, the
amount of oil to be added can be determined using the formula:
= 0.005 · ·
where:
GP = amount of grease to be added in grammes
D = bearing outer diameter in mm.
B = total bearing width in mm.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 63 of 96
7.2.6.2 BEARING HOUSING (MONOBLOCK) lubrication with grease
For smooth long lasting operation, we recommend checking the lubrication of the bearings
frequently.
For antifriction bearings is usually intended a maximum temperature of 75/85 °C (measured at
the outer ring) when used in a regular workshop environment, even though higher temperatures
are acceptable (see chapter 6.3).
The lubrication intervals shown in the table below refer to the aforementioned conditions and
are indicated according to the different types of bearings and their rotational speed N.
The table below shows the re-lubrication intervals and the amount of grease necessary for each
bearing.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 64 of 96
7.2.6.3 Antifriction bearing lubrication with oil
HDF S.r.l. recommends oil lubrication for high-speed or high-temperature applications that
exclude the use of grease.
To avoid losses during transport and installation, bearing house and pillow blocks lubricated
with oil are NOT pre-lubricated. It is necessary to fill with oil before running the fan.
If the indicator is "by eye", the level represents the centerline of the indicator, whereas if is
"pipette" the level must be between the minimum and maximum mark. All levels are to be
considered in a static condition, i.e. with the fan off. It is necessary to wait for the right time for
the oil level stabilization.
The oil lubrication methods used for both pillow block bearings and separated bearings are oil
baths or ring oilers.
The oil should be changed once every 6 months. If used in particularly adverse conditions (very
dusty environments or that lead to premature oil oxidation) we recommend shortening the
period.
We recommend the use of MOLIGUARD GEAR SINT EP 68, a synthetic additive EP with viscosity
ISO VG 68 and flash point> 200 ° C.
In the case of bearings mounted on separated bearings in oil bath, in addition to check the level
of the indicator, it is also necessary to check the level with respect to the support plane of the
support.
Below is indicated the level reported in the filling schedule for separated bearings with oil-bath
lubrication.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 65 of 96
Oil level indicator
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 66 of 96
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 67 of 96
The following table shows the compatibility of the greases indicated by HDF S.r.l.
SKF – LGMT 2 + + -
SKF – LGHP2 + + -
ROL OIL – LITEX EP 2 - - +
+ = compatible
- = NOT compatible
Warning: the compatibility does not indicate that the performance remains the same. To maintain
the performance, operating temperature and bearing life, it is necessary to use exactly the indicated
products. Compatibility is only an indication of the chemical / physical affinity of lubricants, ie they
will continue to perform the lubricating function, not chemically untying, totally losing the
lubricating properties, but with different performances.
Warning: Absolutely forbidden to use greases containing Graphite, Molybdenum Disulphide and
other elements / additives not suitable for use with rolling bearings.
OIL
Different is when we are in the presence of oil lubrication. NEVER mix different oils regardless of
compatibility. If necessary replace the oil with another, completely empty the oil inside the bearing
house / pillow blocks and replace with the new one.
When replacing, pay attention to the oil replaced. If there are anomalies or particles, it may indicate
excessive bearing wear or contamination. In these cases, before the system is restarted, evaluate
the cause and intervene.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 68 of 96
7.2.7 Fastening of all fixed parts
Check the tightening torque of the Fan screws.
Cl. 8.8
To fix the bearing housing to the carpentry follow the values the screws tightening torque shown
in the following table:
Cl. 8.8
Tightening
Screw Step Preloading
Torque
M [mm] N Nm
10 1.5 25742 50
12 1.75 26273 60
16 2 34044 100
20 2.5 35910 130
For all commercial elements (e.g. bearing supports, electric motors, etc.) refer to what is indicated
by the manufacturer.
The following table shows the correspondence between the fan holes and the screws.
Notes:
use only cl. 8.8 screws for all the couplings;
the minimum length of the screw is equal to tightening thickness + overall dimensions of the lockwasher
and nut + d/2;
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 69 of 96
7.2.8 Toothed belts
Fan control motor belt tensioning and pulley alignment check
if necessary, tighten correctly using the adjustment system (2) (arrow of about 2 cm, working
on the intermediate point of the belt between the pulleys).
Pay utmost attention not to overtighten the belt.
Excess tightening may damage the bearings.
Check the correct alignment of the pulleys every 2500 hours.
Use a template to check the correct alignment and if necessary, adjust the pulley to obtain it;
Make sure that:
the belts are positioned correctly in their compartments
the toothed compartments are not worn.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 70 of 96
7.2.9 V-belts
To mount a V-belt drive system:
clean the fan and motor shafts. Make sure they present no signs of corrosion;
clean the pulley hubs and cover them in lubricating oil to facilitate shaft insertion;
remove any traces of oil, grease, rust or burrs from the pulleys;
install the fan pulley on the fan shaft and the motor pulley on the motor shaft.
Do not use a hammer to fit the pulleys in because you may damage the bearings.
Fix the pulleys.
Alignment check
Make sure that each pulley is as close as possible to its mounting; the pulley and the belts should
not touch the mounting.
Move the motor so that you can remove the belts effortlessly.
Do not force the belts and do not insert tools in the grooves of the pulleys
use a rigid ruler or a tightrope to adjust the motor and fan shafts so that they are
parallel. The belts should be at a straight angle with the shafts.
Incorrect alignment may lead to excessive belt wear.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 71 of 96
Use a dynamometer and a torque wrench.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 72 of 96
Check the correct positioning of the belts in their seat.
Make sure the belts are in perfect condition and do not present signs of wear or frayed sections.
For machines with antifriction bearings, where the most important aspect is to check the
condition of the bearings, we recommend using special monitoring equipment, able to define
the acceleration spectrum over a field of frequencies that allows you to readily identify any
abnormal values that may indicate a bearing fault
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 73 of 96
Any accumulation of the conveyed materials may result in excessive vibrations, leading
to malfunctions.
For impeller cleaning, see par. 7.2.2 / 7.2.3.
b) Structural resonance
Such phenomenon must be removed by changing (usually increasing) the stiffness of
the resonant structure or component so that the fan works below the lowest resonant
frequency.
c) Thermal growths
They may occur on fans that operate with hot gases.
The temperature gradients should be kept as low as possible over time, within the
limits allowed by the process, because they are directly proportional to the stress
applied to the materials.
Therefore, you should avoid as far as possible any thermal shocks because they may
cause cracks and breakages in the impeller and deformation in the shafts.
Particularly long shafts exposed to hot gases at a standstill for long periods of time
may suffer permanent deformations.
d) Rigid connections between fans and ducts
The fan should not withstand the weight of any external load.
Flexible connections must be provided between ducts and fan inlet/outlet.
For impellers installed directly on the shaft, the head screw is tightened on the shaft of the fan
in such a way that the extractor presses against the end of the shaft.
The impeller hub is connected to the extractor by means of n° 02 screws.
ATTENTION!
THE IMPELLER CAN BE VERY HEAVY!
To lift the impeller, follow the instructions in Chapter 4 LIFTING AND INSTALLATION
INSTRUCTIONS.
Remove the impeller
Remove the extractor (3) and the screw (4)
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 74 of 96
7.2.13 Motor revision
Please refer to motor manufacturer manual for the maintenance intervention and related
intervals.
WARNING
DANGER SUSPENDED LOADS
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 75 of 96
7.2.14 Coupling replacement
On some Fans, you need to install the coupling that connects the electric motor shaft to the
impeller bearing.
Angular centring
Important:
For installation instructions, assembly tolerances and lubrication specifications, refer to the
manual provided by the Manufacturer of the coupling.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 76 of 96
7.2.14.1 Lubrication of standard gear coupling “MAINA” – GO-A
If a standard MAINA gear coupling, GO-A series, is installed, below instructions shall be followed:
1. After the hubs shrinkfitting and the positioning of the gear sleeves and side flanges, fill
with grease all the spaces between hubs and sleeves using a spatula. After closing the
gear coupling, spread a slight mastic flim on the flange connection surfaces.
2. Close the jcoupling and tighten all the screws according to the tightening torques
indicated (table below), then complete lubrication using all the grease nipples and / or
plugs (N ° 2 for half-coupling).
0 OR 68 18
1 OR 85 36
2 OR 107 36
3 OR 133 65
4 OR 152 65
5 OR 177 150
6 OR 209 150
7 OR 234 150
8 OR 253 220
9 OR 279 400
10 OR 304 400
11 OR 355 520
3. Lubricate through the grease nipples, verify that the grease is really filling the gear
coupling; should the grease enter the coupling with difficulty, open a breather by
removing a plug or a grease nipple.
4. At the end of the lubrication, make sure that the couplings are completely filled with
grease, then reassemble the plugs and / or greasers, checking their tightening.
5. Gear coupling must be lubricated regularly every 3-4 months.
This initial interval is recommended for integral seals, industrial applications, non-
aggressive environments, medium and heavy duty services and ambient temperatures
between 0°C and 70°C. After the first year of use and observation and after verifying
the results, the time intervals can be extended up to 6 months. A certain amount of
grease must be created in the coupling during lubrication. To let all the old grease out,
remove a plug or a grease nipple at 180° from the new grease filling point and pump
the new grease until this comes out from the breather. At the end of the operation,
insert the plugs and/or grease nipples, making sure that they are properly tightened.
6. During lubrication operations, always check that the floating part is axially free. If the
movement is blocked, open the coupling and check the gear teeth.
7. Completely replace the grease every 8000 operating hours or at the latest every two
years. For this activity you will have to open the coupling, clean the flange surfaces,
remove all the old grease, clean the interstices, check the gear teeth condition and then
perform the operations indicated in points 1 and 4. Never use contaminated grease, or
grease which is not suitable to the working conditions.. Do not use tools to separate the
two flanges of the toothed sleeves that could damage the integrity of the sealing
surfaces.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 77 of 96
To lubricate coupling and gear teeth, must be used lithium soap lubricating greases,
with EP additives, resistant to centrifugation, non-hygroscopic and antioxidants .
For the first lubrication HDF S.r.l. uses VANGUARD LIPLEX EP 2 grease, NLGI 2 classification,
with Complex Lithium soap thickener.
If you need to use other grease you must completely remove the grease and lubricate as a first
filling.
The indications are to be considered summarized. It is essential to refer to the manufacturer's
instructions.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 78 of 96
7.2.15 Check of all the electrical system components
NOTE
This operation must only be done by the ELECTRICAL MAINTENANCE TECHNICIAN
7.2.16 Check of the legibility of the warning labels for residual risks, restrictions and
obligations
Note
The new parts replacing faulty ones must have the same technical characteristics and the same
performance; if they are safety components, they must be certified and belong to the same class
as those replaced.
Circular control dampers (dapò) are used, just like the parallel blade dampers, to control the
air intake and reduce the consumption in applications where it is necessary to adjust the fan
capacity based on the operating conditions. Follow the same installation recommendations
indicated for the parallel blade dampers. Just like all control dampers, the dapò dampers should
also be installed according to the discharge position shown below; when the dampers are
engaged, the air flow should create an air vortex in the direction of rotation of the impeller. The
maintenance, check and repair intervals match those of the fan impeller.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 79 of 96
Note
Possible fan damages and faults if the control dampers (parallel blade or dapò dampers) are
kept open to 30% constantly or for long periods of time. The 30% setting should be used only
at start-up or for limited periods of time; it should not be used in a continuous manner.
Do not keep the fan running with closed inlet/outlet for more than 15 minutes, unless it is
explicitly authorized by HDF S.r.l.
WARNING
CRUSHING/CUTTING HAZARD
Keep objects and hands away from the blades and/or moving parts of the dampers.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 80 of 96
7.2.18 Seals Maintenance and start up
All the maintenance operations described above shall be performed when the fan is switched off
following the safety rules described in chapter 2.
The following indications on startup procedures, set up, dismounting and assembly are mandatory
and form an integral part of the Chapter 5. 6 and 7 of this manual.
SIMPLE SEAL
The Simple Seal does not require any particular kind of maintenance. It will be substituted when
the leakage exceeds the allowable value, to be determined by the User on the basis of the
application, or when the seal is damaged.
FLOATING SEAL
The Floating Seal does not require any particular kind of maintenance. The rings will be
substituted when the leakage exceeds the allowable value, to be determined by the User on the
basis of the application, or when the seal is damaged.
LABYRINTH SEAL
The Labyrinth Seal does not require any particular kind of maintenance. It will be substituted
when the leakage exceeds the allowable value, to be determined by the User on the basis of the
application, or when the seal is damaged.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 81 of 96
STUFFING BOX
If the fan is switched off for more than 2 calendar months, prior to start of the fan, it is suggested
to verify and replace the stuffing box sealing material.
On the fans with Stuffing Box sealing system, during the first start up, the gland bolting shall not
by tighten (just put in position by hand). DO NOT tighten the gland bolting before start. If
possible, prior to first start-up, maintain the fan switched on for 30 minutes . This will allow the
bearings, the stuffing box or the seal and the other parts to rotate which will reduce any eventual
problems which may occur during future start-ups.
During the first startup of the fan, it is very important that the seal is not too much tighten. Refer
to the Section A.1 - Start up with a new Stuffing Box for further information.
During the first start up, the seal should have a little leakage to guarantee the correct seal
functionality in the future.
Attention: The Stuffing Box seal does not guarantee a 100% sealing.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 82 of 96
If the fan is working with an aggressive , dangerous, toxic, hot, etc. fluid, the seal regulation shall
be performed with the fan not connected to the plant; during this operation, the fluid shall be not
dangerous and at ambient temperature.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 83 of 96
7.2.19 Thermocouple Maintenance and Regulation – Pt100
All the maintenance operations described above shall be performed when the fan is switched
off following the safety rules described in chapter 2.
The following are the steps to follow for the correct fitting of the thermocouple, commonly
called RTD.
As part of the HDF applications, is used Pt100 - platinum resistance thermometers (Pt), in
which, the resistance at 0 ° C is 100 Ω (ISOIEC 60751) and the temperature coefficient equal to
α = 0.003851 ° C ^ -1.
Always consult the manufacturer's manual.
ADJUSTABLE THERMOCOUPLE
For the assembly of the adjustable thermocouple is necessary:
1. Make sure that the locking nut "B", which is used to lock the compression ring, is loosened.
2. Verify that the temperature probe can slide freely on the nipple "A".
3. Verify that the length of the threaded part of the nipple "A" is less than the depth of the hole
that passes through the wall of the bearing housing. During the next tightening, the nipple
should not come into contact with the outer ring of the bearing. If the wall thickness is
insufficient to accommodate the nipple, provide for shims between this and the monoblock.
4. Secure the nipple “A” to the bearing housing without touching on the bearing outer ring. We
recommend the use of a suitable sealing system between the bearing housing and nipple “A”
(gasket or PTFE tape).
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 84 of 96
5. Slide the temperature probe until it reaches the bearing surface; make sure that the sensor is
simply leaned and does not force on the outer ring.
6. Tighten locking nut "B".
FIXED THERMOCOUPLE
For the assembly of the fixed thermocouple is necessary:
1. Verify that the length of the threaded part of the nipple "A" is less than the depth of the hole
that passes through the wall of the support / monobloc. During the next tightening, the nipple
should not come into contact with the outer ring of the bearing. If the wall thickness is
insufficient to accommodate the nipple, provide for shims between this and the monoblock.
2. Verify that the length of the probe rod "U" (from the head to the bottom of the nipple "A"
thread or of the fixing flange "B") is correct. Once tightened, the probe must not press but only
lean against the bearing.
The probe must not generate additional stress on the mechanical components of the fan.
If necessary, provide adequate shims / spacers.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 85 of 96
8. TECHNICAL SUPPORT INFORMATION
(+39) 0342 48 30 59
www.hdfans.it
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 86 of 96
9. DISMANTLING AND DISPOSAL
Once the Fan has reached the end of its service life, it must be put out of service so it cannot be
used for other purposes than those it was intended for and make possible the reuse of the parts
and materials it is made from.
The Fan must be disabled and demolished in a safe manner, to avoid the risk of impact due to the
presence of moving parts or stored energy.
In particular, disconnection operations of the pneumatic and electrical systems must be carried out
according to the indications and warnings in Chapter 4 “Lifting and installation instructions”.
HDF S.r.l. cannot be held in any way liable for damage to people or property due to re-use of the
parts of the Fan for functions other than those initially intended by HDF S.r.l..
CAUTION
Before proceeding with any dismantling operations, the employees must have read and clearly
understood the Safety Provisions (Chapter 2) at the beginning of this manual and wear the Personal
Protective Equipment (protective gloves, safety shoes, overalls, goggles, etc.).
DO NOT DISPOSE OF POLLUTANTS SUCH AS OIL, GREASE, RAW MATERIAL WASTE, ETC.
INTO THE ENVIRONMENT.
To carry out dismantling, follow the procedure indicated below, with EXTREME CAUTION.
WARNING
DANGER OF CUTTING, CRUSHING, IMPACT AND ABRASION.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 87 of 96
10. SPARE PARTS
The HDF Fan is designed, built and uses suitably sized components to ensure high reliability over
time.
Failure to comply with the maintenance schedule and incorrect use of the Fan (as indicated in this
manual) may cause damages to the components.
When replacing parts, always use original spare parts that can be ordered directly from HDF
S.r.l.
The use of non-original spare parts will render the warranty void and can also affect the proper
operation of the Fan.
The parts are to be replaced only by HDF technicians or by qualified maintenance staff.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 88 of 96
11. TROUBLESHOOTING
Problem Causes Solution
Start-up failure Excessive power absorption Check the power absorption.
Reduced power supply voltage Check the mains voltage
MAX. relay unsuitable for the Replace the max. relay with a
start-up conditions. suitable one.
Electric motor fault that lower Replace the electric motor.
its inrush characteristics
Inadequate assessment of the Install an electric motor with
moment of inertia of the higher capacity or check the
rotating parts of the fan in friction on the mechanical
connection with the selected parts.
electric motor and its type of
starter.
Starting voltage too low. Check the mains voltage.
Vibrations Impeller imbalance. Make sure there are no dust
deposits or other materials on
the rotating parts. Check the
impeller for erosion or
corrosion signs.
If the impeller is seriously
damaged, have it replaced
Unsuitable foundation. Reinforce the structure or
decrease the natural resonant
frequency by increasing the
masses
Loosen the foundation bolts or Tighten the screws completely
the fixing bolts of the bearings
and their covers
The head screw locks the loose Tighten and check that the
impeller. impeller is in the correct position
The impeller rotates backwards Check that the direction of
rotation of the impeller is
correct, as indicated on the
nameplate
Vibrations transmitted to the Check the system in which the fan
fan from the system, other is installed. If necessary, install
machines or structures of the expansion joints between the fan
building. and the ducts.
Air pulses. The fan is mechanically sized
Using the fan at rotational for a rotational speed 1.1 times
speeds higher than the higher than the
intended one Intended speed: this limit must
not be exceeded if allowed by
the electric motor.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 89 of 96
Problem Causes Solution
Air pulses (pumping) Fan running at reduced or zero Provide adequate systems to
capacity, usually at full prevent the dampers from
pressure. closing completely.
The fan works in the stall Check the system.
region of the performance
curve.
This may be due to many
causes including:
Accidental closing of the
dampers installed on the
system or on the fan
Circuit resistance different
than that intended
Obstruction or incorrect
inlet connection resulting
in inconsistent air intake
Repeated
detachment/reattachment
of the confined fluid
from/to the walls of a
divergent duct
Noise Foreign materials in the fan Check the impeller and the fan
casing. casing: clean and remove any
foreign bodies.
Friction between static and Check the clearances and the
rotating parts tolerances between static and
rotating parts and bolts’
tightening periodically (every 6
months).
Wrong choice of bearings. Replace the bearings.
Performance with Fan power unexpectedly high. Make sure that the fan speed is
excessive capacity not too high.
Correct one or more of the
following conditions:
the fan is treating ambient
air while it was designed
for hot or less dense air;
excessive pressure drop
assessments (slow down
the rotational speed of the
fan or close the dampers
partially).
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 90 of 96
Problem Causes Solution
Insufficient air flow Incorrect fan rotation Check the direction of rotation
as shown on the nameplate
Sudden changes of direction in Assess System Effect.
the duct near the fan drain or
pre-rotation of the fluid due to
the elbow duct at the inlet.
Inlet flow regulator installed Make sure the flow regulator is
incorrectly installed with the air intake in
the direction of rotation of the
impeller when partially closed
(see 7.2.17)
Fan power unexpectedly low Correct one or more of the
following conditions:
pre-rotation of the fluid at
the fan inlet;
resistance to fluid passage
higher than calculated
(caused for example by a
closed damper).
Performance with Fan power unexpectedly high. Make sure that the fan speed
excessive capacity is not too high. Correct one or
more of the following
conditions:
the fan is treating ambient
air while it was designed
for hot or less dense air;
excessive pressure drop
assessments (slow down
the rotational speed of the
fan or close the dampers
partially).
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 91 of 96
12. ATEX
12.1 Warnings
DANGER
Zones 0, 1 and 2 refer to gas while zones 20, 21 and 22 refer to dust.
Zone 0 A place in which an explosive atmosphere consisting of a mixture with air of
flammable substances in the form of gas, vapour or mist is present continuously or
for long periods or frequently.
Zone 1 A place in which an explosive atmosphere consisting of a mixture with air of
flammable substances in the form of gas, vapour or mist is likely to occur in normal
operation occasionally.
Zone 2 A place in which an explosive atmosphere consisting of a mixture with air of
flammable substances in the form of gas, vapour or mist is not likely to occur in
normal operation but, if it does occur, will persist for a short period only.
Zone 20 A place in which an explosive atmosphere in the form of a cloud of combustible dust
in air is present continuously, or for long periods or frequently.
Zone 21 A place in which an explosive atmosphere in the form of a cloud of combustible dust
in air is likely to occur in normal operation occasionally.
Zone 22 A place in which an explosive atmosphere in the form of a cloud of combustible dust
in air is not likely to occur in normal operation but, if it does occur, will persist for a
short period only.
ATTENTION: CHOOSING TO INSTALL A FAN THAT COMPLIES OR DOES NOT COMPLY WITH THE ATEX
DIRECTIVE 2014/34/UE IS AT THE DISCRETION OF THE END USER, WHO WILL ASSUME
FULL RESPONSIBILITY.
Before installing the fan, you must:
1) Perform a risk assessment of the environment in which it will be installed;
2) identify the type of hazardous atmosphere present in the environment (gas or dust);
3 define the zones (see):
• for atmospheres subject to the presence of gases, refer to zones from 0 to 2 (from
high to low risk of explosion);
• for atmospheres subject to the presence of dust, refer to zones from 20 to 22 (from
high to low risk of explosion);
4) define the product category (1-2-3) (see Directive 99/92/EC);
5) check the correspondence of data shown on the nameplate affixed to the fan.
Protection
ZONE Atmosphere Group Category Temperature Class
Method
ZONE 1 Gas II 2G c T1 - T6
ZONE 2 Gas II 3G c T1 - T6
ZONE 21 Dust II 2D c T 125 or >
ZONE 22 Dust II 3D c T 125 or >
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 92 of 96
12.2 Construction features
The fans that comply with Directives 2014/34/UE are designed to prevent the formation of sparks
as a result of the friction between the rotating and fixed parts.
The features below must be checked before installing the fan:
1) Copper/brass/aluminium plates between the inlet cone and the impeller;
2) Copper/brass/aluminium rings:
• Between the casing and the electric motor shaft;
• (On indirect drive fans only) Between the pulleys and the guard;
3) (On indirect drive fans only) Adequate belts;
4) (For fan with kW>11 only) Welded casing;
5) Grounding (loose parts). It is necessary to check the connection of the fan with a
grounding system.
Note: If motor is operated by inverter, it is necessary to provide and install PTC or PT100.
INTERNAL EXTERNAL
CLASSIFICATION APPLICATION CLASSIFICATION APPLICATION
ZONE GROUP ZONE GROUP
ZONE 1 2G
ZONE 1 2G
ZONE 2 3G
GAS
NO-ZONE
ZONE 2 3G ZONE 2 3G
ZONE 1 2G
NO ZONE ZONE 2 3G
ZONE 21 2D
ZONE 21 2D
ZONE 22 3D
NO-ZONE
DUST
ZONE 22 3D ZONE 22 3D
ZONE 21 2D
NO ZONE ZONE 22 3D
The HDF S.r.l. Fan is designed, built and uses suitably sized components to ensure high reliability
over time.
Failure to comply with the maintenance schedule and incorrect use of the Fan (as indicated in this
manual) may cause damages to the components.
When replacing parts, always use original spare parts that can be ordered directly from HDF
S.r.l.
The use of non-original spare parts will render the warranty void and can also affect the proper
operation of the Fan.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 93 of 96
12.3 Atex Marking – Name plate
Below is an example of ATEX marking adopted by HDF.
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 94 of 96
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 95 of 96
HDF S.r.l.
FACTORY
Via Nazionale 5/C
Zona Industriale
23030 Chiuro (SO)
ITALY
Code: HDF_M_C_EN_2021_08_R10
This document is the exclusive property of HDF S.r.l. Any reproduction thereof, either whole or in part, is forbidden Page 96 of 96