Scpsd Manual
Scpsd Manual
SCPSD Features
• Stainless Steel or Ceramic Diaphragms
• UL Listed and CE Marked
• Pressure Ranges
-14.7 to 250 PSI................... 0 to 3000 PSI
0 to 1000 PSI....................... 0 to 5000 PSI
0 to 2000 PSI....................... 0 to 9000 PSI
• Sensor Outputs
2 PNP Open Collector Transistor
Output, 30 VDC, 100mA
Optional Additional Current, 4 to 20mA
• Selectable Units of Measure
PSI, bar, Mpa
• Output Response Time Less than 5.0ms
• Error Message
• Polarity Protected
• Short Circuit Protected
• 4 Digit LED
SCPSD-1000P-1727 • Display Swivels 290o
Specifications
Pressure Code 0100 0250 016 1000 3000 5000 9000 250 600
Units of Measure PSI ,bar, MPA
Measure Range ( PSI, bar ) -14.7 to 100 -14.7 to 250 -1 to 16 0 to 1000 0 to 3000 0 to 5000 0 to 9000 0 to 250 0 to 600
Overload Pressure ( PSI, bar ) 360 725 40 2900 7250 11600 21750 500 1200
Burst Pressure ( PSI, bar ) 360 725 50 11600 17400 24650 31900 1200 2200
Sensing Element Ceramic Stainless Steel
Stainless Steel 1.4404
Stainless Steel 1.4404, 1.4542, NBR*
Parts in Contact with Media Ceramic AL203, NBR*
*FPDM, EPDM Special Request
Switch Cycles >100 Million
Output Response Time < 10ms
Power Supply 15 to 30VDC, Class 2 Power Supply
Short Circuit Protection Yes, 2.4 Amp / Open Collector Output
Reverse Polarity Protection Yes
Overload Protection Yes
Current Consumption < 100mA
Output Circuit 2 PNP (Sourcing) Open Collector Transistor
Analog Output 0/4…20mA, Programmable, freely scaleable
Output Functions Hysteresis, Window Comparator
Switching Voltage -1.5VDC
Maximum Current Output 1A with 2 Open Collector Outputs, .5A per Output
Accuracy ± 0.5% F.S. Typ., ± 1% Max.
Repeatability ± 0.25% F.S.
Display Accuracy ± 0.5% F.S. Typ., ± 1 Digit
Thermal Error Max. ±0.03% F.S. at -4 to 185°F (-20 to 85°C)
Material Pressure Die-cast Zinc Z 410: Surface-finishing
Display Material Polyester
General Protection IP 67, EN60529, UL, CE Marked, EMC-EN50082-2 Class B, EN 50081-2
Temperature Range of Media -4 to 185°F (-20 to 85°C)
Ambiant Temperature Range -4 to 185°F (-20 to 85°C)
Storage Temperature -40 to 212°F (-40 to 100°C)
Display 4-Digit, 7-Segment LED, Red, 9mm Height
Tightening Torque 35Nm
Vibration Resistance 20G, 10 to 500Hz, IEC60068-2-6
Shock Resistance 50 G, XYZ, 11ms, IEC60068-2-29
Mass 10.6 oz. (300g)
Internal Circuit
M12, 4-Pin, (2) PNP Outputs M12, 5-Pin, (2) PNP Outputs with 4 to 20mA Analog
1 Brown
1 Brown +Ub (24VDC)
+Ub (24VDC) 4 Black S1
(Sensor Socket) 4 Black S1 (Sensor Socket)
2 White S2
2 White S2
5 Gray Analog Out
3 Blue
0V / Gnd 3 Blue
4 3 4 3 0V / Gnd
1 2 1 2
M12, 4-Pin, (1) PNP Output with 4 to 20mA Analog Note: M12, 5-Pin Female Cable Connector will fit on both M12,
1 Brown 4-Pin and 5-Pin Male Sensor Connector.
+Ub (24VDC)
(Sensor Socket) 4 Black S1
2 White Analog Out
3 Blue
0V / Gnd
4 3
1 2
Installation
Mechanical:
! CAUTION: Install and de-install the SCPSD only Avoid static and dynamic over-pressures which exceed
when there is no pressure present. the specified overload pressure. Even when the overload
Attach the SCPSD to the appropriate process connection. pressure is exceeded only for a short time the SCPSD may
Installation should be undertaken only with a 22mm, across be damaged. Parker SensoControl diagnostic systems are
flats spanner. Ensure that the digital display is placed in recommended for measuring pressure peaks exactly.
the best viewing position by using the rotational housing If there is a danger of excessively high pressure peaks, it is
adjustment. Turn the SCPSD manually to the required recommended to:
position. Maximum 290°.
• use an SCPSD with a higher nominal instrument pressure
Excessive turning beyond the easily detectable end stop will (analog output can then be correspondingly matched)
lead to damage.
• install a standard throttling device upstream from the
The housing can be attached: SCPSD
• with self-tapping screws into two blind holes at the back of
the housing
• with the mounting plate provided
• with cable ties
Electrical:
! CAUTION: The SCPSD may be installed only by a
qualified electrician in accordance with the
respective national and international regulations. Error Messages
Protect the SCPSD from electromagnetic influences and Display Description
over-voltages. The set value is lower than the other respective
Optional installation tips which are shown by experience to Att parameters. When Enter is activated, the smaller value
is matched up.
reduce the influence of interference:
Err1 System Error (Internal)
• Use shorter cables
Nominal instrument pressure range was exceeded by
• Avoid short distances between connecting leads and Err2
10%. Please check system pressure.
power consuming devices and interference generating Nominal instrument pressure range has been exceeded
electrical and electronic equipment Err3 Error in analog electronics. Please check system
• Use free running diodes pressure.
4 5 3 4 3
3 5 4 3 4
1 2 1 2
2 1 2 1
Dimensions
Switch Output 2 Switch Output 2
Switch Output 1 Switch Output 1
(Also Error Output) (Also Error Output)
1.56 1.82 1.56 1.82
(39.5) (46.3) (39.5) (46.3)
I II I II
SensoControl SensoControl
2.89 2.89
(73.4) (73.4)
UNIT
4.13
UNIT
3.89
(105) (98.5)
.55 .55
(14) (14)
.98
1.24 (25)
(31)
1.06
7/16-20 UNF-2B (SAE-4) (26.8)
1.26
1/4 BSPP (32) 1.26
(32)
( ) or ( )
Pass- Yes
word
Menu
Right Page
To Program Outputs and Options of SCPSD, press and hold To Review Programed Outputs and Options of SCPSD, press
the (Up Arrow Icon) then press the (Circle Icon) until Pro6 is and hold the (Circle Icon) until Pro6 is displayed. Release the
displayed. Release all buttons and follow menu to program outputs (Circle Icon) and follow menu to program option and status.
and options.
Parameters Shown in
Digital Display
To program switch outputs in menu S1 (S1 = output 1) or S2 (S2 =
output 2), press and hold, then press . Pro6 will be displayed
for 2 seconds.
PRS This is dedicated to a password. Entry into the programming cont Switch output as
mode can be secured only when the correct figures have noPn = closer
been entered nCLS = opener
Menu for programming the switch outputs: Func Selection of switching functions:
S1 S1 = Switch output 1 HySt = Hysteresis function
S2 S2 = Switch output 2 (Menu is not active if S2 is being used FEn = Window function
as an error output) Delay times; input from 0 to 9.99 s.
Switching point (SP): upper limiting value / pressure, at which dSPI dSPI = delay time switching point output 1
the switch output changes its status. drSL drSI = delay time reverse switching point output 1
SP1 SP1 = Switch output 1; input as pressure value (e.g. 400 bar) dSP2 dSP2 = delay time switching point output 2
SP2 SP2 = Switch output 2; input as pressure value (e.g. 430 bar) drS2 drS2 =delay time reverse switching point output 2
Reverse switching point (rSP): lower limiting value/pressure
at which switch output changes its status.
rSP1 rSP1 = Reverse switching point (rSP1) of switch output 1;
input as pressure value (e.g. 390 bar)
rSP2 rSP2 = Reverse switching point (rSP2) of switch output 2;
input as pressure value (e.g. 420 bar)
The reverse switching point is always smaller than its
respective switching point. If the reverse switching point is set
higher than the switching point, the reverse switching point will
be set automatically 0.5% of the instrument nominal pressure
below the switching point. The warning sign Att (attention)
will appear, which can be cleared with Enter. Options Program (See Next Page)
68 Parker Hannifin Corporation
Pneumatic Division
Pneumatic Richland, Michigan
www.parker.com/pneumatic
Catalog 0801-3/USA Pressure Sensor
Programming Features & Accessories SCPSD High Pressure 316 Stainless Steel
Optical
Interface
Device
SCPSD