The RMF-112D is a combined underfrequency and overfrequency relay designed for single and three-phase networks, featuring LED fault indication and timer-controlled tripping. It is suitable for both marine and land-based installations, providing protection by monitoring generator frequency and activating contacts based on set points. The relay includes various technical specifications such as a measuring voltage range, contact ratings, and compliance with major classification societies.

Uploaded by

SuNarto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3 views2 pages

RMF112D

The RMF-112D is a combined underfrequency and overfrequency relay designed for single and three-phase networks, featuring LED fault indication and timer-controlled tripping. It is suitable for both marine and land-based installations, providing protection by monitoring generator frequency and activating contacts based on set points. The relay includes various technical specifications such as a measuring voltage range, contact ratings, and compliance with major classification societies.

Uploaded by

SuNarto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

ANSI code 81 Frequency relays

Type RMF-112D uni-line


4921240223B

• Combined underfrequency/overfrequency

• For single and 3 phase networks

• LED indication of fault condition

• Timer controlled tripping

• LED indication for activated relay

• 35 mm DIN rail or base mounting RMF-112D

Application The contacts may be set to open or to close on


The digital, combined underfrequency and overfrequen- activation.
cy relay type RMF-112D forms part of a complete DEIF
series of relays for protection and control of generators. Normally energised contact
Recommended for land-based installation for warning
The relay is type approved by major classification socie- and alarm purposes.
ties and is applicable to both marine and landbased in-
stallations. In case of an auxiliary supply drop-out, the contact is
immediately activated.
The RMF-112D is applied for protection against under-
frequency and overfrequency by supervising the fre- Normally de-energised contact
quency (of generators) in single phase and 3 phase Recommended for marine installations for regulating
networks. and control purposes.

Measuring principle An auxiliary supply failure will not result in an unwanted


The relay measures the voltage between 2 phases or activation of the contact.
between one phase and the neutral.
Latch circuit
To avoid unwanted underfrequency alarms, the RMF- The contact can then be locked in its warning position,
112D relay is not activated until the measuring voltage even if the input frequency returns to normal (add “L” to
exceeds 60% of Un. contact type in order specifications, if this is required).
If either the underfrequency or overfrequency exceeds The latch circuit is reset by disconnecting the auxiliary
its set point, its associated output is activated. supply.
The set point values are set on the front of the relay by Hysteresis
means of potentiometers. If exceeded, a fault signal is In order to avoid “chatter” on the relay contacts the
generated, and the associated yellow LED is lit. contact functions are provided with a hysteresis, i.e. a
difference of 0.25Hz between energising and de-
Timer functions energising of the relay.
When the set point is exceeded, its associated timer
starts and will run as long as the fault conditions pre-
DEIF A/S

vails. The delay does not depend on the exceeding of Power-up/power-down circuits
the set point. The RMF-112D is provided with a 200 ms power-up
circuit, ensuring the correct function of the relay on
If the fault disappears, the timer is reset. When the ti- connection of the auxiliary voltage.
mer expires, the contact is activated and the associa-
ted red LED is lit.
Note: Normally energised contacts are not activated
(contact does not open/close) until 200 ms after
Relay outputs connection of the auxiliary voltage.
The RMF-112D is provided with 2 outputs:
Likewise, the RMF-112D is provided with a 200 ms
f< a minimum contact power-down circuit, ensuring supervision and mainten-
(normally energised or normally de-energised) ance of any set point exceedings for 200 ms after
f> a maximum contact disconnection of the auxiliary voltage.
(normally energised or normally de-energised)
Type RMF-112D
Technical specifications Settings and indication
Meas. voltage (Un): See supply voltage - AC ranges. Setting of LED/relay
voltage range: 60...120% of Un. Underfrequency “f<” yellow LED is lit when the
set point: frequency has dropped below
overload: 1.2 x Un, continuously, (90...100%) of fn the set point, but the relay not
2 x Un for 10 s. (80...100%) of fn at fn = 55Hz yet activated.
Overfrequency “f>” yellow LED is lit when the
load: 2kΩ/V. set point: set point is exceeded, but the
(100...110%) of fn relay not yet activated.
Frequency range: 40...45...65...70Hz. (100...120%) of fn at fn = 55Hz
Time delay: Contact is activated and red
(0...10 s) in seconds LED lit after the timer has
Nom. frequency (fn): 50Hz, 55Hz or 60Hz. expired.

The relay is furthermore equipped with a green LED marked


Output: 1 min. and 1 max. contact. “POWER” for indication of power ON.

contact type: Relays B + C: Once the relay has been mounted and adjusted, the
normally energised (“NE”), or transparent front cover may be sealed, preventing unwanted
normally de-energised (“ND”) change of the setting.
with or without latch circuit (“L”).
Connections/dimensions (in mm)
relay contacts: 1 change-over switch per relay.

contact ratings: 250V-8A-2000VA (AC).


24V-8A-200W (DC).
3
(200 x 10 change-overs at resistive
load)

contact voltage: Max. 250V (AC). Max. 150V (DC)

Optocoupler output: System status off = failure.

Hysteresis: 0.25Hz.

Response time: <90 ms.

Temperature: -25...70°C (operating).


Shown contact positions: aux. voltage not connected.
Temperature drift: ±0.1Hz per 10°C. See installation instruction for information
about status output (29-30).
Galvanic separation: Between inputs and outputs:
3250V - 50Hz - 1 min.

Supply voltage: 57.7-63.5-100-110-127-200-220-230-


240-380-400-415-440-450-660-690VAC
±20% (max. 4VA)

24-48-110-220V DC -25/+30%
(max. 3.5W).

Climate: HSE, to DIN 40040. Weight: approx. 0.650 kg

EMC: To EN 50081-1/2, EN 50082-1/2, Order specifications


SS4361503 (PL4) and IEC 255-3. Type – Meas. Voltage – Nom. Frequency – Relay B –
Relay C – Supply voltage
Connections: Max. 4 mm² (single-stranded). Example:
Max. 2.5 mm² (multi-stranded). RMF-112D – 380V AC – 50Hz – NE – ND – 24V DC

Materials: All plastic parts are self-extinguishing to


Due to our continous development we reserve the right to
UL94 (V1).
supply equipment which may vary from the described.
Protection: Case: IP40. Terminals: IP20,
to IEC 529 and EN 60529.

Type approval: The uni-line components are approved


by the major classification societies. For DEIF A/S, Frisenborgvej 33
current approvals see www.deif.com or DK-7800 Skive, Denmark
contact DEIF A/S.
Tel.: +45 9614 9614, Fax: +45 9614 9615
E-mail: [email protected], URL: www.deif.com