Technical Specifications for 10 Kva on-line Ups Systems
Technical Specifications for 10 Kva on-line Ups Systems
Vendor has to duly fill the Technical Specification, attach their catalogue and mark the model in the catalogue.
14 Rated KVA 10KVA; The UPS should be capable to deliver rated KVA
at 0.8 P.F. i.e 10 KVA UPS should be capable to deliver 8
KW load at 0.8 p.p. (output)
15 Operating Temperature should be designed for delivering rated KVA at ambient
temperature from 0 to 40 Degree Celsius.
It should also be capable to deliver approx. 80% of rated
output at 50 degree Celsius ambient temperature.
16 Relative Humidity Upto 95% at 35 degree Celsius non-condensing
17 Noise level At 1 meter from the UPS.
< 65 decibels
(On demand Proto-type test certificate be submitted).
18 Charger Built in IGBT based solid state float-cum-boost charger
with automatic boost/trickle charge modes with current
limiting features. The charger characteristics shall be such
as to match the float/boost charging of the batteries as per
battery characteristic, for enhancing the life of batteries.
The charger should be designed for 2 hours back up period
at rated KVA
19 Crest factor >3
20 Interface facility The UPS system should have necessary hardware and
software with RS-232 port to work on DOS/SCO Unix
(open screen) Novell / Network/ Current & advanced
window operating system. It should be compatible for
connecting to Building Management System.
(B) Remote manageability through SNMP facility. There is
a facility to monitor and broad cast to server wherever
necessary condition such as :
i) Power failure, back up time, low battery warming & auto
file closure.
ii) The software should be capable of automatically closing
the files (auto closure feature) in the server so that the data /
program files on the server are not lost/ corrupted.
Batter Details:
Vendor to specify, the make of battery they propose to use, they have to submit detailed literature of battery and battery manufacturers capability
etc.
27. Testing:
i). The supplier shall have facilities to carry out all the tests at factory center, and tests have to be satisfactorily carried out before acceptance.
ii) Tests shall be carried out and certified by the manufacturer confirming the offered specification.
(iii) If the UPS does not conform to specifications either during factory test or at site, the Bank reserves the right to reject the same. The
successful tenderer shall then have to remove the same at his cost from site and supply a new piece conforming to the specifications.
iv). The Bank reserves the right to randomly decide to carry out testing of UPS systems at site after installation at the cost of UPS vendor, who
will be required to arrange for all the requisite variacs, maters, loads etc. and carry out the tests through vendor’s personnel in the presence of
Bank’s Officials.
I/We hereby declare that I/we have read and understood the above specification.
Date: Stamp: