control 2
control 2
PART 2
That is, the transfer function of the system multiplied by the input function
gives the output function of the system.
The transfer function of a control system is defined as the ratio of the
Laplace transform of the output variable to Laplace transform of the input
variable assuming all initial conditions to be zero.
TRANSFER FUNCTION OF CONTROL SYSTEM
The transient response will be zero for large values of ‘t’. Ideally, this value of ‘t’
is infinity and practically, it is five times constant.
The part of the time response that remains even after the transient response has
zero value for large values of ‘t’ is known as steady state response. This means, the
transient response will be zero even during the steady state.
TIME RESPONSE
TIME RESPONSE
TIME RESPONSE
Peak Resonance:
The peak resonance Mp is defined as being the maximum value of the magnitude
A large value of the peak resonance corresponds to a large value of the maximum
overshoot of a system.
Bandwidth:
The bandwidth is defined as the frequency band between which the magnitude
does not fall below 23 dB, the frequencies at which this occurs being termed the
cut-off frequencies.
TRANSIENT AND STEADY STATE RESPONSE IN A
CONTROL SYSTEM
Standard Input Signals : These are also known as test input signals. The input
signal is very complex in nature, it is complex because it may be a combination
of various other signals.
Now there are various types of standard input signals and they are written below:
Fig 1: Time dependence of the system behavior on the value of the damping ratio ζ,
for undamped (blue), under-damped (green), critically damped (red), and over-damped (cyan)
cases, for zero-velocity initial condition.
SYSTEM BEHAVIOR (CONT.)
• Over-damping (ζ > 1)
--When ζ > 1, the system is over-damped and there are two different real roots. An over-
damped door-closer takes longer to close than a critically damped door does.
• Critical damping (ζ = 1)
--When ζ = 1, the system is said to be critically damped. A critically damped system
converges to zero as fast as possible without oscillating (although overshoot can occur).
--An example of critical damping is the door closer seen on many hinged doors in public
buildings. The recoil mechanisms in most guns are also critically damped so that they return
to their original position, after the recoil due to firing, in the least possible time.
SYSTEM BEHAVIOR (CONT.)
• Under-damping (0 ≤ ζ < 1)
--Finally, when 0 < ζ < 1, γ is comples, and the system is under-
damped. In this situation, the system will oscillate at the natural
damped frequency ωd, which is a function of the natural frequency and
the damping ratio.
• https://www.youtube.com/watch?v=T4y85568XvY
FREQUENCY RESPONSE
Advantages of frequency response:
• It includes simple calculations.
• The frequency response method is easy to implement in the designs of the control
system. It also helps us to find the stability of the system.
• It provides the stability analysis of the system without the need for any complex and
time-consuming processes.
• The frequency response and the step response of the system are closely related. One
known parameter gives us the idea of the other parameter.
• We can obtain the frequency response of the given control system without the knowledge
of the transfer function.
• The stability analysis of the system can be performed even if it incorporates moderate
degree of non-linearity.
FREQUENCY RESPONSE
Disadvantages of frequency response
• The frequency response method works better with the linear system. The
result in the cases of non-linear systems or the system with moderate non-
linearity does not show the exact results. Hence, it is generally applied only
to linear systems.
• The practical method to obtain the frequency response is time-consuming.
• There is a relation between the frequency response and the step response,
but it is not exact as expected. But the exact relation is possible if we use
the Fourier transformation to describe it, which is difficult to apply due to
complex calculations.
FREQUENCY RESPONSE CURVE OF ELEVATOR
SYSTEM
For example, consider an elevator.
When the fourth-floor button is
pressed on the first floor, the
elevator rises to the fourth floor
with a speed and floor-leveling
accuracy designed for passenger
comfort. The push of the fourth-
floor button is an input that
represents our desired output,
shown as a step function in Figure.
The performance of the elevator
can be seen from the elevator
response curve in the figure.
FORCE VOLTAGE ANALOGY
Two systems are said to be analogous to each other when they
respond to inputs and disturbances in a mathematically equivalent
way, even though the underlying physical processes or components
are completely different. The systems can be modeled by the same
differential equations and exhibit similar transient responses, steady-
state behavior, and stability characteristics. For example, both
systems might show exponential decay, sinusoidal behavior, or other
recognizable responses. The core idea of the Force-Voltage analogy
in control systems engineering is to relate mechanical systems with
their electrical counterparts, by assuming Force in a mechanical
system to be analogous to the Voltage in an electrical system
RELATIONSHIPS FOR CAPACITOR, RESISTOR AND
INDUCTOR
TRANSLATIONAL MECHANICAL SYSTEM:
TRANSLATIONAL MECHANICAL SYSTEM: