Line Impedance of a Transmission Line
Line Impedance of a Transmission Line
Z0=R+jωLG+jωCZ0=G+jωCR+jωL
where:
Simplified Cases:
Z0=LCZ0=CL
This is the most common approximation for high-frequency signals (e.g., RF,
microwave).
1. Coaxial Cable:
Z0=60ϵrln(Dd)Z0=ϵr60ln(dD)
where:
where:
Z0≈87ϵr+1.41ln(5.98h0.8w+t)Z0≈ϵr+1.4187ln(0.8w+t5.98h)
where:
ww = Trace width
hh = Substrate height
tt = Trace thickness
ϵrϵr = Relative permittivity
Measurement:
The given values are positive sequence resistance and reactance also zero sequence
resistance and reactance .how do we calculate the impedance of the protected line
show me with example
Key Formulas:
Example Calculation:
Given:
ZL−L=Z1=5+j25 ΩZL−L=Z1=5+j25Ω
∣ZL−L∣=52+252=650≈25.5 Ω∣ZL−L∣=52+252=650≈25.5Ω
∣ZL−G∣=8.332+41.672≈42.5 Ω∣ZL−G∣=8.332+41.672≈42.5Ω
Conclusion:
Would you like help with relay settings (mho circle, quadrilateral characteristics)?
Phase-Phase (XPhXPh):
XPh=X1=25 Ω(or slightly higher for security)XPh=X1=25Ω(or slightly higher for sec
urity)
Phase-Ground (XGndXGnd):
XGnd=2X1+X03=2(25)+753=41.67 ΩXGnd=32X1+X0=32(25)+75=41.67Ω
ZRev=0.1×ZFwd=0.1×(4+j20)=0.4+j2 ΩZRev=0.1×ZFwd=0.1×(4+j20)=0.4+j2Ω
Phase-Phase (L-
Parameter Phase-Ground (L-G)
L)
Forward Reach
(ZFwdZFwd)
4+j20 Ω 6.66+j33.33Ω
Graphical Representation
Copy
Download
X (Reactance)
|
|________
/ \
/ \
/ \
/ \
------------------- R (Resistance)
5. Summary
1. Zone 1 (Primary Protection): 80% of Z1Z1 (L-L) and 2Z1+Z0332Z1+Z0 (L-G).
2. Resistive Reach: Covers arc/tower footing resistance.
3. Reactance Reach: Matches line reactance.
4. Load Avoidance: Ensure relay does not trip under normal load.
Would you like help with coordination with neighboring relays or testing
procedures?
Given Data:
Line 1 (Protected by R1):
o Z1=5+j25 Ω
o Z0=15+j75 Ω
Line 2 (Protected by R2):
o Z1=4+j20 Ω
o Z0=12+j60 Ω
Z1(R1)=0.8×(5+j25)=4+j20 ΩZ1(R1)=0.8×(5+j25)=4+j20Ω
Z2(R1)=ZLine1+0.5×ZLine2Z2(R1)=ZLine1+0.5×ZLine2=(5+j25)+0.5×(4+j20)=7+j35
Ω=(5+j25)+0.5×(4+j20)=7+j35Ω
o Time Delay: Typically 0.3–0.5 sec (to allow R2’s Zone 1 to trip first).
Relay R2 (Bus B):
Z2(R2)=ZLine2+0.5×ZNextLineZ2(R2)=ZLine2+0.5×ZNextLine
Z3(R1)=ZLine1+ZLine2=9+j45 ΩZ3(R1)=ZLine1+ZLine2=9+j45Ω
Zone
Relay Zone 2 (Delay) Zone 3 (Backup)
1 (Instant)
4. Key Considerations
1. Load Encroachment Avoidance
o Ensure Zone 3 does not overlap with minimum load impedance.
2. Communication-Assisted Schemes (POTT, DCB)
o Use Pilot Protection (e.g., Permissive Overreach Transfer Trip) for faster
fault clearance.
3. Fault Resistance Coverage
o Adjust resistive reaches (RPh,RGndRPh,RGnd) to avoid underreach.
5. Summary of Coordination Rules
✅ Zone 1: 80% of the protected line (instantaneous).
✅ Zone 2: 100% of protected line + 50% of next line (delayed).
✅ Zone 3: 100% of protected line + 100% of next line (backup).
✅ Time Grading: Zone 2 (0.3–0.5s), Zone 3 (0.8–1.2s).
✅ Directional Supervision: Prevent reverse faults from tripping.
Would you like help with communication-assisted schemes (e.g., POTT, DCB)
or testing procedures?
Settings Example
Permissive
Send if Zone 2 picks up Trip if Zone 1 + receive signal
Logic
Advantages
✅ Faster than time-graded schemes (no intentional delay).
✅ Secure (requires confirmation from both ends).
Disadvantages
❌ Requires reliable communication channel.
Settings Example
Forward
7 + j35 Ω (Zone 2) 6 + j30 Ω (Zone 2)
Reach
Advantages
✅ Works even with weak infeed conditions.
✅ No permissive signal needed (only blocking).
Disadvantages
❌ Slower than POTT (blocking signal must time out).
PUTT (Permissive Zone 1 (underreaching) sends trip Short lines with low fault
Underreach) signal resistance
6. Summary
POTT: Best for most applications (fast + secure).
DCB: Best for weak-infeed/multi-terminal lines.
PUTT/DUTT: Used for ultra-high-speed requirements.
Would you like help with relay settings files (SEL, GE, Siemens) or fault studies for
coordination?
GROUP "Zone2"
Z2F = 7.0 + j35.0 // Zone 2 Reach
T2 = 0.4s // Zone 2 Delay
END
GROUP "POTT"
POTT_MODE = ON // Enable POTT
POTT_T = 100ms // Signal Delay
END
POTT=ENABL POTT_MODE=O
POTT Enable E
<Enabled>True
N
Would you like a sample settings file for a specific relay model?
Here’s a complete sample settings file for the Siemens 7SA6 relay in DIGSI format,
configured for quadrilateral distance protection with POTT:
// 1. SYSTEM PARAMETERS
GROUP "SYSTEM"
VNOM = 132.0 // Nominal voltage (kV)
FNOM = 50.0 // Frequency (Hz)
CT_PRIMARY = 800 // CT ratio (800:1)
VT_PRIMARY = 132000 // VT ratio (132kV:110V)
END
// Resistive Reach
RFPP = 10.0 // Phase-Phase (Ω)
RFPG = 20.0 // Phase-Ground (Ω)
// Quadrilateral Angles
PHI_LINE = 80 // Line angle (degrees)
THETA_FWD = 75 // Forward tilt angle
THETA_REV = 105 // Reverse tilt angle
END
// 4. DIRECTIONAL ELEMENTS
GROUP "DIRECTIONAL"
POLARITY = +90 // Forward direction = +90°
MEMORY_POL = ON // Enable polarization memory
END
// 5. OUTPUT CONTACTS
GROUP "OUTPUTS"
TRIP_CMD = 1 // Trip command to CB
SIGNAL_CMD = 2 // Alarm contact
END
// 6. MONITORING
GROUP "MONITORING"
DIST_LOG = ON // Fault recording
EVENT_LOG = ON // Event logging
END
4.0+j20.0, 6.66+j
Z1F, Z1GF Zone 1 reach (80% of line impedance).
33.33
THETA_FWD/
75°, 105° Defines the quadrilateral’s reactance boundaries.
REV
Testing Recommendations
1. End-to-End POTT Test:
o Simulate a fault in Zone 2 and verify both relays trip within 100ms.
2. Load Encroachment Test:
o Apply 95% of load impedance and confirm no maloperation.
3. Directionality Test:
o Reverse faults should not trigger POTT.
plaintext
Copy
Download
GROUP "DCB"
DCB_MODE = ON
BLOCK_LOGIC = Z2_REV
END
For PUTT (Permissive Underreach), use Z1F instead of Z2F in POTT logic.
Let me know if you need adaptations for specific fault scenarios or coordination
studies!