Mitsubishi Electric's Air-Conditioner Network System
(MELANS) is the leader in building air conditioning
control systems. MELANS provides highly-efficient
control and monitoring for air conditioner networks
and serves as an interlocked interface for air
conditioner related devices ; building control
systems to deliver energy efficient, comfortable air
conditioning area.
Air conditioning equipment and measurement The system is able to set up each floor unit
devices network in order to control humidity simplifying test runs and local adjustments
and ventilation, maintaining optimum air
quality over the building space. Air conditioning units are set up individually in
order to avoid any troublesome cases.
For example, should the main building
Able to connect with building management
management system fail, the air conditioning
systems by using an interface.
units are able to continue operating
The layout system is flexible, ie. could be Enables simple operation through an effectively
changed depending on the tenants requirements maintained centralized controller
Connectable Models
3 4
VRF Air-conditioner VRF Air-condiyztioner
Outdoor Unit Indoor Unit
VRF Air-conditioner
AE-200E
EW-50E
AT-50B
PAC-YT40ANRA
BAC-HD150
Mr.SLIM Outdoor Unit Mr.SLIM Indoor Unit
LMAP04-E
Mr.SLIM Packaged Air-conditioner
LMAP04-E, BAC-HD150
Transmission booster
Room Air-conditioner
Mr.SLIM Indoor Unit
The above diagram shows an image of the system. Some units cannot be connected or
some functions cannot be used depending on the system configuration or model.
Depending on the case, some units cannot be connected simultaneously, or some units
may not be required.
Some models require adapters for connection. In some cases, said units cannot be
connected with the adapters.
LONWORKS® is global registered trademark of Echelon Corporation (U.S.).
Ethernet® is a registered trademark of the Xerox Corporation (U.S.).
BAC-net® is a registered trademark of ASHRAE (U.S.) in each country.
5 6
The secret to the unmatched comfort
provided by Lossnay core is the
VRF Air-conditioner (CITY MULTI series) cross-flow, plate-fin structure off the
The CITY MULTI system has versatile heat-exchange unit. Its design
applications for air conditioning. effectively removes sale air exhaust
Features: Each unit is individually while reducing thermal loss with the ability
controlled. Indoor and outdoor units can to connect to MELANS via the M-NET
be connected together to enhance control network.
performance.
Large capacity floor standing PAC (PFD, PFAV series) The transmission method for K-control is broadcasting. Specifica-
C-PAC (PFV,PEV series) tions: transmission speed = 200 b/s, transmission distance = 200 m,
Air conditioning systems for large spaces data transfer size = 2-bytes. With this method, multiple units receive
( business facilities, factories), a valid broadcast in a single transmission, thus reducing the number
CITY MULTI and Mr.SLIM are versatile of transmissions to be sent. However, the method is limited in that
systems which are designed to provide receipt of the confirmation signal is designated for a single unit. ln
air conditioning for people. lts variety of other words, the transmission side cannot ensure whether or not the
transmission has been fully conveyed to the other destination units.
features can be adjusted to be suitable
for many applications. CITY MULTI for Buildings Mr.SLIM for Stores
(KIRIGAMINE, Star MEX,ZEN series) The transmission method for Mr.SLIM for stores feature
M-NET is individual transmissions. "Easy A-control". lt emphasise
The specifications i.e. 9,600 b/s less maintenance and
transmission speed, 500 m construction by utilizing both
transmission distance and 16-byte control and power cables for
The adapter for connecting to the M-NET transmission line data transfer size, all greatly wiring between the automatic
is necessary. exceed those of K-control. address and indoor/outdoor
The adapter cannot be connected in some cases.
Features: high transmission units (Wiring between indoor
reliability, simple interlocking with and outdoor units consists
Lossnay and other related only of a single three-core
equipment. wire).
7 8
MELANS Lineup
Higher
AE-200E
P. 18
AT-50B P. 16
P. 17
PAR-U02MEDA P. 13
PAR-31MAA P. 11
P. 12
9 10
Wired MA remote Controller (PAR-31MAA)
Product Size ● Unit 120(H) × 140(W) × 25(D)mm Product Size ● Unit 120(H) × 70(W) × 14.5(D)mm
● Packaging 166(H) × 220(W) × 60(D)mm ● Packaging 185(H) × 220(W) × 50(D)mm
Unit Color Clear white (Munsell No. 1.0Y9.2/0.2) Unit Color Clear white (Munsell No. 1.0Y9.2/0.2)
Function table Refer to Pg. 24 for an explanation of Function table Refer to Pg. 24 for an explanation of
the function table. the function table.
180 30
Some models will have different display for the air flow direction and fan speed.
Set the air flow direction and fan speed when performing initial setting.
Business explanation
The design is simple, and air conditioning control is as easy
as flicking a light switch Visualization of inefficient operation of air conditioners
through energy management function
The use of the expansion controller enables air conditioner
Instruction Book, Installation manual control in a wide range from small- to medium-scale buildings.
17 18
Centralized controller for web(EW-50E)
Features
● Built-in Web server function
● Expansion controller function
for AE-200E
● Energy management function
● Dual set point
● Notification of trouble via e-mail
● Annual and weekly schedules
provided as standard
19 20
ability
Interlocking
activated
21 22
The operation can be prohibited from an external input.
When an error occurs, the operation LED flashes to alert
the user to the error.
Some functions may be unavailable depending on the
model. (Ex.: Automatic fan speed setting function and
5-stage and automatic air flow direction setting functions)
The LCD touch panels on the AE-200E and AE-50E can
be locked.
100-240
Power supply Coefficient When an expansion controller is provided, it is necessary
to connect the external input and output also to the
expansion controller.
23 24
, Main Sub
sub sub
could
25 26
Set the lowest address for the indoor unit that you would like
CITY MULTI Indoor
to be the base unit for the same group. Also, set the address
(sequentially) of the indoor unit within the same group.
If a sub BC controller exists in an R2 system, the indoor
Main unit and sub unit unit addresses must be set as shown below.
(1) Indoor unit to be connected to the BC controller (Main)
(2) Indoor unit to be connected to the BC controller (No.1 Sub)
(3) Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1) < (2) < (3)
Lossnay and OA processing unit After setting all indoor units, set any number of addresses within range limits.
Main remote controller Set the base unit address of the lowest indoor unit in the same group to +100.
Sub remote controller Set the addresses of the primary remote controller to +50.
(However, if you interlock the two remote controller, you must set
the Main and sub exchange switch.)
Set the address for the lowest indoor unit within the outdoor
unit of the refrigeration system to +50.
CITY MULTI outdoor units 6
Set the address for the outdoor units with the same refrigeration circuitry.
OC, OS1, and OS2 are automatically detected.
Main 7 Set as the refrigerant system's outdoor unit address +1.
BC controller 52 - 100 Set as the [address of the smallest indoor unit connected to a sub BC controller] + [50].
Sub1, Sub2 7 3, 4
Automatic startup is not possible when connected to a sub BC controller.
ON/OFF remote controller The smallest group No. to be managed +200
Advanced Touch controller AT-50B Set the address to any of the addresses within the range shown on the left.
Centralized controller
AE-200E, EW-50E
Set the address to any of the addresses within the range shown on the left.
Expansion controller
AE-50E
BAC-HD150 Set the address to any of the addresses within the range shown on the left.
LMAP04-E Set the address to any of the addresses within the range shown on the left.
When using individual refrigerant systems with CITY MULTI (partial exclusions), The indoor units come in models with two or three control boards for setting addresses.
address setting is not required. (1) Set the address of the control board No.1 to the lowest address, and set the
Also, when the distribution controller handset is used, address setting is not required. address for control board No.2 as the "address of control board No. 1+1".
When setting the addresses of the M-NET remote control to "200", use "00". (2) Be sure to set the address of the No.2 control board to "No.1 board address +1",
When setting the addresses of the indoor and outdoor auxiliary units to “100", use "50". and set the address for board No.3 to "No.1 board address +2".
If the addresses of the outdoor units overlap with other refrigeration systems, set the The OC, OS1, and OS2 of the outdoor units with the same refrigerant circuit are
different available address under this setting condition. automatically detected. If SW1 of the outdoor unit is set to No. 15 (1111000000), OC,
OS1 and OS2 are displayed on the outdoor control LED monitor.
7 The BC controller exists only in the case of the R2 system.
27 28
For each Outdoor unit, the maximum connectable quantity of Indoor units
is specified at its Specifications table.
A) 1 Group of Indoor units can have 1-16 Indoor units;
OA processing unit GUF-RD(H) is considered as an Indoor unit.
B) Maximum 2 remote controllers for 1 Group; (MA/ME remote controllers
cannot be present together in 1group.)
C) 1 LOSSNAY unit can interlock maximum 16 Indoor units; 1 Indoor unit
can interlock with only 1 LOSSNAY unit.
D) Maximum 3 System controllers are connectable to the TB3 of the
Outdoor unit.
Find more details on CITY MULTI Databook.
System controller connection as described in D)
carries the risk would have a risk that the failure of the connected
Outdoor unit would stop power supply to the System controller.
29 30
CITY MULTI and Lossnay Interlocked system CITY MULTI Lossnay
31 32
Mr.SLIM and Lossnay
interlocked system Mr.SLIM Lossnay
AT-50B
Mr.SLIM
Mr.SLIM
33 34
Mr.SLIM with centralized control.
AT-50B AT-50B
whilst
With centralized control for Mr.SLIM, a power source is With centralized control for room air conditioner, a
required for the centralized remote controller power source is required for the centralized remote
(AT-50B,etc.). controller (AT-50B, etc.) and ME remote controller.
When the centralized control is performed only with the
AE-200E and EW-50E, no power supply unit is required.
35 36
What is the wiring distance when using only
the Lossnay, Slim, and room air conditioner?
is
AT-50B AT-50B
37 38
AT-50B
500m
39 40
6 Centralized Control by AE-200E
System Configuration Diagram POWER
M-NET
M-NET M-NET
ON/OFF
adapter
STATUS
Indoor
Intergrated centralized unit
control software
(TG-2000A) or Web browser
of indoor units
POWER
M-NET
ON/OFF
M-NET M-NET
STATUS
adapter
exceeded 51 AE-200
LAN(100BASE-TX)
Switching HUB Outdoor Outdoor
AE-200E unit unit
Power
Up to
M-NET cable 50 units
200 indoor units can be
connected (controlled) by Indoor
unit
using 3 expansion LAN
M-NET
controllers. LAN
M-NET M-NET adapter
EW-50E
Outdoor Outdoor
unit unit
Power
Up to
M-NET cable 50 units
Indoor
unit
LAN
M-NET
M-NET M-NET adapter
EW-50E Outdoor Outdoor
unit unit
Power
Up to
M-NET cable 50 units
Intergrated centralized
control software
(TG-2000A) or Web browser Indoor
unit
LAN
M-NET
M-NET M-NET adapter
EW-50E
Outdoor Outdoor
unit unit
The AE-50E can be used for the EW-50E. Power
Up to
When the power consumption is apportioned by the AE-200E, M-NET cable 50 units
the M-NET of AE-200E cannot be used (all systems are connected
through the expansion controller). Indoor
unit
41 42
1. Energy Management License Pack
Register the AE-200E/AE-50E/EW-50E license No. in order to
enable the following functions.
(1) Energy-saving control
By setting the control content per block, energy saving rotation
operation is carried out in each group.
2. Interlock control
The license is a permit that allows you to access optional features of the Using the AE-200E/AE-50E/EW-50E permits interlocked operation
AE-200E/AE-50E/EW-50E. of DIDO connected general equipment and indoor unit free contacts.
Licenses come in a 24-digit character string with every string of four
characters separated with a hyphen.
This string of characters is referred to as a license number, and there is
only one license for each serial number.
Consequently, when issuing a license number, the manufacturing number
(serial number) itself will always be required.
You can access the features after you register the license number of your
AE-200E/AE-50E/EW-50E.
43 44
When the license for the AE-200E/AE-50E/EW-50E is issued,
you will need the actual serial number (manufacturing number).
Upon ordering the license, contact the sales office to report the serial
number printed on the label of the product box and the one on the back
of the actual product.
<Ver.>
<Ver.> indicate factory defoult versions
21665 - 001
2015
001 The procedure to check the serial number
Year of manufacturing (20 ) +50 or +70
001
after installing the AE-200E and turning it on.
First set up the AE-200E/AE-50E in its location, confirm the serial number
For the month of manufacture, substitute alphabets A, B, C in place of 10, 11, 12
and remove the surface frame from the main unit. The Serial Number:
(October, November, December).
is shown on the outside of the touch panel on the lower
right side. Turn on the power. Press the maintenance button on the
screen and the login screen appears. The manufacturing number
that appears on the lower left portion of the screen will be
the serial number.
The procedure to check the serial number of the
AE-200E/AE-50E/EW-50E centralized controller
TB1 TB3
L/L1 N/L2 A B S
45 46
The CITY MULTI™ system can be monitored or controlled
with signals to/from the outside as every control board of
Demand/low noise
Indoor units or Outdoor units have input/output signal mode
connectors. Using these connectors can carry out
independent control of the individual Indoor or Outdoor
units. When using input/output connectors, a dedicated
adapter (an optional part) and a relay circuit need to be
prepared at the site.
Specification of input/output connector
Outdoor unit
CN52
Indoor unit
Distant control board Relay circuit PAC-SA88HA-E control board
1
Power supply CN52
of relay L1 X Z Y X
2
L2 Y
3
L3 Z 4
(2) PAC-SE55RA-E
Selecting whether in
operation/stop mode is
performed by an external
circuit or remote control ( )
( ) Also includes system
controller (centralized controller).
AE-200E
Removing the key card from the card holder stops the indoor unit.
Never use the interlocking for control for disaster prevention or security.
51 52
AT-50B
AT-50B
AT-50B
AT-50B
53 54
can
PAC-
SF46EPA
AT-50B AE-200E LMAP04-E
AT-50B AT-50B
AE-200E
EW-50E
EW-50E is equivalent to
the system controller.
ME ME
AT-50B AE-200E BAC-HD150
55 56
M-NET line of indoor unit
208-230 V
required
57 58
ln order to ensure proper communication amongst the Outdoor unit,
Indoor unit, LOSSNAY, and OA processing unit GUF-RD(H), and
Controllers, the transmission power situation for the M-NET should
be observed. In some cases, the Transmission booster should be
used assuming the power consumption of Indoor unit sized
P20-P140 is 1, the equivalent power consumption or supply of
others are listed at Table 5-1 and Table 5-2.
59 60
Table 5-1 The equivalent power consumption
Indoor, OA unit Indoor unit LOSSNAY BC PWFY MA RC. ME Remote controller/Adapter
controller
Sized Sized LGH-RX-E CMB P100VM-E-BU P100VM-E1-AU P200VM-E1-AU PAR-31MAA PZ-52SF-E PAR-U02MEDA
P15-P140 P200, P250 P100VM-E2-AU P200VM-E2-AU PAR-21MAA PAC-YG60MCA PAC-IF01AHC-J
GUF-50, 100 PAC-AH250M-J EP100VM-E1-AU PAC-YT52CRA PAC-YG66DCA
PAC-AH125M-J PAC-AH500M-J EP100VM-E2-AU PAR-FA32MA PAC-YG63MCA
PAC-AH140M-J P140VM-E1-AU PZ-60DR-E
P140VM-E2-AU
1 7 0 2 6 1 5 0 0.25 0.5
Transmission booster PAC-SF46EPA has equivalent 5-2-A) Firstly, count from TB3 at TB3 side the total quantity of
transmission power 25. Indoor units, OA processing units and ME remote controller,
and System controllers. If the total quantity reaches 40 3, a
PAC-SF46EPA should be set. In this case, Indoor units
With the equivalent power consumption values in Table
sized P200 and 250 are counted as 2 indoor units, but MA
5-1 and Table 5-2, PAC-SF46EPA can be designed into remote controller(s) and PZ-60DR-E are NOT counted.
the airconditioner system to ensure proper system 3 One AT-50B corresponds to 5 units.
communication according to A, B, C.
5-2-B) Secondly, count from TB7 side to TB3 side the total
transmission power consumption. If the total power
consumption reaches 32, a PAC-SF46EPA should be set.
Yet, if a PAC-SC51KUA or another controller with a built-in
power supply, such as PAC-YG50ECA, is used to supply
power at TB7 side, count from TB3 side only.
5-2-C) Thirdly, count from TB7 at TB7 side the total transmission
power consumption, If the total power consumption
reaches 6, a PAC-SF46EPA should be set.
61 62
the
AT-50B
Select one of the outdoor units to supply power, and change the connector of that
outdoor control board CN-41 to CN-40. This outdoor unit supplies power to M-NET
and System remote controller through wire A, and activates the operation of the
system remote controller. lt is possible to control multiple groups under different
refrigerant systems without using PSU if the power is enough.
63 64
When using the AE-200E When using the AE-200E and AT-50B
LAN LAN
Power supply unit
HUB HUB
LAN LAN
M-NET M-NET
AE-200E AE-200E❋
AT-50B
When AE-200E is used, no power supply unit is required if When the installed AT-50B is supplied with power from an
the centralized control transmission line does not contain outdoor unit, the AT-50B will go down if the breaker of the
power consuming devices, such as system remote outdoor unit trips or its board breaks down. Therefore, it is
controllers. recommended to install a power supply unit.
65 66
6
When using the AE-200E AT-50B
AT-50B
AE-200E
200m
200m
67 68
Restrictions on connection of EW-50E to AE-200E
EW-50E (1)
EW-50E (2)
EW-50E (3)
M-NET
69 70
Case Studies
B
Use the AE-200E to automatically operate and
monitor energy-saving of AC units via web browser
AE-200E
AT-50B
Use with Internet Explorer Ver.8, 9, 10, 11. Use Java Plug-in by Oracle,
Ver.1.8.0_25. or later. Microsoft is a registered trademark or trademark of Microsoft
Corporation in the United States and/or other countries. Oracle and Java are
trademarks or registered trademarks of Oracle Inc. in the United States and/or
other countries.
71 72
Case Studies
the rotational
73 74
Cases Studies
Case Studies
AE-200E
Janitor's room
75 76
Case Studies
AT-50B
AT-50B
AT-50B
AE-200E
AT-50B
77 78
Case Studies
under
controlling
AE-200E
79 80
Case Studies
AE-200E
81 82
Case Studies
Trouble shooting
Control issues
sub
83 84
Case Studies
Billing issues
PI
AE-200E
85 86
Case Studies
87 88
Explanation of symbols Explanation of Technical Terms
IC / AIC / KIC Indoor unit / A-control Indoor unit / K-control Indoor unit
OC • OS Outdoor unit
BC Distribution controller
LC Lossnay
MA MA remote controller
EC Expansion controller
EP Transmissions booster
KA K converter
MC-A AI controller
MC-P PI controller
DC DI / DO controller
ST Schedule timer
89 90
A component for Mitsubishi Electric air
conditioners. The general purpose interface
allows equipment to be turned OFF/ON as
well as error monitoring from the AE-200E
and TG-2000A by linking to other equipment
that can connect to an external contact point.
93 94
The measurement controller takes
information from various sensors
( temperature sensors, etc.) and from power
measurements. There are two types of
measurement controllers, one for AI and
another one for PI. AI controller is connected
to various sensors and comes with a
humidifier/ventilation equipment interlock
function for measurements and setting
values. PI controller, provides power,
gas/water usage information.
Main system
controller
A system controller that controls air
Sub system conditioners by receiving signal from main
controller system controllers of operating system.
95 96
Remote Control cable
and Transmission Lines
(Note 1) MA remote controller refers to MA remote controller, MA simple remote controller, and wireless remote controller
(Note 2) ME remote controller refers to ME remote controller and ME simple remote controller.
(Note 3) The use of cables that are smaller than 0.75 mm2 is recommended for easy handling when
connecting PAR-31MAA, wire it with a sheathed 0.3-mm² cable.
(Note 4) When connected to the terminal block on the simple remote controller, use cables that
meet the cable size specilioations shown in the paranthesis
(Note 5) Pair connection of PAR-31MAA in one group containing other remote controllers is not allowed.
weak between
97 98
There are two indoor units, each unit connected to Would it be a problem if the centralized remote
MA remote controller individually. Can these units control wiring wire is wired together with a refrigerant
be controlled in one group with a centralized pipe ?
controller ?
lt's possible to be done with a refrigerant pipe but
For the group registration can be done by a should not wire power suply cable together with
centralized controller. If the local remote controller control cables. In order to avoid a weak signal keep
and centralized controller group setting are not a distance of at least 50 mm between power supply
the same, it may not operate properly. So, it should cables and control cables.
either be set as individual control or group control.
99 100
Centralized control of system controller Prohibit operating of the AT-50B
connected to indoor/outdoor transmission
lines
Can operation be prohibited from an AT-50B
When performing a test run on a system configuration which is connected in a position subservient to the
consisting of several outdoor units, the indoor units of AE-200E?
other outdoor units and systems cannot be run from
the AT-50B.
Why ? Do I need a power supply unit? It is possible to prohibit AT-50B operation by
AE-200E and will display during centralized control
AT-50B is connected to the M-NET transmission lines of on AT-50B.
the indoor unit for specific outdoor units and systems. Even if the indoor unit is set only cooling operation,
Therefore, supplying power to the M-NET transmission it can set the prohibit mode by centralized remote
lines among the outdoor units is required in order to controller like AE-200E.
communicate between the outdoor units when operating
the outdoor units of other outdoor units systems.
This is the reason why power is not be supplied via M-NET
transmission lines between outdoor units.
The following are two methods to supply power via the Size of remote controller cable
M-NET transmission line.
(1) Connect the power supply unit to the transmission line. I would like to extend cables 7 m from the position of
(2) Supply power from the designated outdoor unit (one only). the remote controller of the indoor unit. What are the
(Change the power supply switch connector from CN41→ cable code sizes?
CN40)
For 2-core cable, use 0.3 to 1.25 mm2. We
recommend 0.75 mm2
Connecting CITY MULTI indoor/outdoor
transmission line.
Can the AE-200E be connected with CITY MULTI
indoor/outdoor transmission line (on the TB3 side of Connecting the temperature sensor
the outdoor unit)?
When connecting the optional temperature sensor
The AE-200E can be connected with CITY MULTI indoor/outdoor
(PAC-SE41TS-E) to CITY MULTI indoor unit, which
transmission line. However, take the followings into consideration. control board connectors offer the best connection?
1. The AE-200E will be disabled if power is disconnected from
the outdoor unit.
2. It must be used within the range of power supply capacity of Connect to CN20 on the indoor unit control board.
the outdoor unit. When shipping, the thermistor for the intake
For the reason stated in 1, when the apportioned electricity charge temperature detection is connected, so replace it with
function and/or the peak-cut control are used, connect the the temperature sensor available as an accessory.
AE-200E not to the indoor/outdoor transmission line, but to the
centralized control transmission line.
When power to the outdoor unit supplying power to the AE-200E is
interrupted for maintenance, the charge function and the peak-cut
control will be stopped, and the customer may be troubled by loss
of the billing data or excessive demand values.
101 102
What if I was to temporarily disconnect the local
remote controller for working inside the controller?
(With the power supply energized) Does doing this
affect the AE-200E billing system? Do I need to
delete the remote controller connection data?
unit?
103 104
Error code list
105 106
107 108
109 110
Communication error No signal reception (communication System error Over unit quantity error ( Expansion controller )
error between A-control indoor/outdoor units) System error Connection locking error ( Expansion controller )
Communication error Resynchronization error System error Unit information error ( Expansion controller )
(communicationerror between A-control indoor/outdoor units) System error System setting error ( Expansion controller )
Communication error Over connection of 5 or more indoor units System error Version error ( Expansion controller )
(communication error between A-control indoor/outdoor units)
Communication error Miss wiring (communication error
between A-control indoor/outdoor units)
Communication error Startup timeout (communication
error between A-control indoor/outdoor units)
Communication error Expansion controller)
Communication error receive frame ID error Expansion controller)
System error
System error Total capacity error
System error Capacity code error
System error Maximum connectable number of units exceeded
System error Pipe length setting error
System error Floor height setting error
System error Address setting error
System error Attribute setting error
System error Port setting error
System error Refrigerant system setting error
System error Connection setting error
System error Refrigerant system/connection information
setting error
System error I/O connection equipment not connected/remote
controller sensor fault
System error I/O type setting error
System error Underfined unit
System error Replace cleaning setting error
System error Model decision no setting error
System error Incompatible unit combination
System error Underfined values
System error Underfined values
System error LONWORKS system error
111 112