AMOUNT
-
-
-
-
BOQ OF HVAC SYSTEM
Lot- Refrigerant line accessories comprising of safety valves, angle valve, liquid line
indications, liquid levelcontrol etc.
Lot- water flow switches at inlet and outlet of condenser & chiller, water drain and air purge
valves wherever required.
Lot- Suction line and chiller insulation with minimum 19 mm thick polyvinyl nitrile
rubber insulation finished with 0.63 mm thick G.S.S. cladding complete as required.
Lot- Frame work for mounting the above condenser, chiller, compressor and motor with
base plate complete with antiviberation pads/ springs.
Lot- Initial/First charge of refrigerant gas and compressor oil.
Unit shall be tested at the factory.
As per IGBC requirement, COP of water cooled Screw chilller should not be less than
6.1
The chiller characteristic shall be as follows:
Cooling Capacity : 190 TR
Water in condenser in/out : 32.2 °C / 37.8°C
Chilled water 'In' : 12.22 °C
Chilled water 'Out' : 6.7 °C
Chiller Fouling Factor : 0.0005
Condenser Fouling Factor : 0.001
Efficiency(kW/TR) : < 0.64
NPLV.IP(kW/TR) : < 0.4
CHW Flow : 456 GPM
CDW Flow : 570 GPM
Quantity : (2W+1S) Nos
2 Pumps
2.1 Primary Chilled Water Pumps
Supply, installation, testing and commissioning of End Suction back pull out centrifugal
chilled water pump set factory assembled and tested for rated efficiency with
mounting, supports etc if required. Controllers and all accessories related to pump
operation shall be incorporated. Each capable of delivering specified flow rate complete
with following as per specifications & schedule of equipments.
a. Pump with IP 55 S1 duty TEFC induction motor with class F insulation, IE-3, PN 12
(Minimum required).
b. Pumps shall be suitable for operation on 415+/- 10% Volts/
3ph / 50 Hz/AC power supply.
c. The pump characteristic shall be as follows:
d. Complete set system to be mounted on a common MS
base frame, all required fittings & accessories including coupling, coupling guard,
vibration isolation arrangement by means of rubber type mounting, foundation nuts,
bolts complete as required & as per specification with
following capacities shall follow following duty.
Supply, installation, testing and commissioning of End Suction back pull out centrifugal
chilled water recirculation pumps each capable of delivering specified flow rate
complete with following as per specifications & schedule
of equipments.
a. Pump with IP 55 S1 duty TEFC induction motor with class F insulation, EFF-1,
PN-12 (Minimum required).
b. Pumps shall be suitable for operation on 415+/- 10% Volts/
3ph / 50 Hz/AC power supply.
c. The price will include sensorless/ with sensor technology controller and all accessories
related to parallel sensorless/with sensor technolgy based operation, necessary
software and networking hardware and software for integration and compatibility with
BMS (BACNET/modbus Protocol).
Nos
a. Pump with IP 55 S1 duty TEFC induction motor with class F insulation, IE3, PN-
12 (Minimum required).
b. Pumps shall be suitable for operation on 415+/- 10% Volts/
3ph / 50 Hz/AC power supply.
c. The pump characteristic shall be as follows:
Complete set system to be mounted on a common MS
base frame, all required fittings & accessories including coupling, coupling guard,
vibration isolation arrangement by means of rubber type mounting, foundation nuts,
d. bolts complete as required & as per specification with following capacities shall follow
following duty.
Nos
4.0 Hot water flow Pumps with Pump mounted VFD and sensorless/ with
sensor technology Pumping System
Supply, installation, testing and commissioning of End Suction back pull out centrifugal
hot water recirculation pumps each capable of delivering specified flow rate
complete with following as per specifications & schedule of equipments.
Pump with IP 55 S1 duty TEFC induction motor with class F insulation, EFF-1, Min. PN-12.
Nos
Capacity : 300 KW
Water flow rate = 229 GPM (868 LPM)
pressure drop across HX not to exceed 20 ft or 6 meters .
Hot Water inlet/Out temp for Primary Side.: 50/45 Deg C
Hot Water inlet/Out temp for Secondary Side.: 40/45 Deg C
(01 Working + 0 Standby) Nos.
Providing and fixing UV stabilized PVC water storage tanks, for 500 lit. capacity, of
the approved quality including making solid supported base as per instructions and making
all connections to the tank as required to make the
tank functioning in all respects .
Nos.
7 Heat Pump
Supply Instalation,Testing, Commissioning of packaged energy efficient Air to Water Heat
Pump made with water resistant materials and capable for outdoor installation.
Supply, Installation, Testing & Commissioning of Micro Processor Controlled, BMS
compatible Air to Water Scroll Heat pump delivering actual capacity as per the
following parameters duly installed at site. The Heat Pump should be complete with
Single/ multiple hermatic scroll compressors , Thermostatic/Electronic Expansion
Valve,recirculation pump, braze plate type (ANSI SS316) primary heat exchanger, CIP
(Clean In Place System), Inbuilt Primary circulation Pump, anitvibration rubber mounts
with factory assembled with Electrical panel mounted on the heat pump including the
disconnect switch suitable for 50 Hz, 3 Phase, 415 volts, AC supply. The vibration
isolators shall be shipped alongwith heat pump from your works. Heat Pump should be
capable of generating Hot Water upto 55ºC.
NOTE
(1) The Air velocity across the filter should not be more then 500 FPM.
(2) CSU- Ceiling Suspended Units | FM- Floor Mounted
(3) All CSU shall be provided with drain Pumps
(4) UV lamps shall be considered for all the AHUs/CSUs.
5) All AHUs shall be with F.A, R.A damper.
6) Chilled water coil should have inlet and outlet temperature as 6°C & 12°C respectively.
7) Hot water coil (wherever required) should have inlet and outlet temperature
as 45°C & 40°C respectively.
8) Suitable Rubber bellow required for chilled water pipes to avoid the direct contact .
9) As per IGBC requirement, Fan power should be equivalent to 0.5 w/cfm or equivalent
to BEE-3 star rating whichever is stringent .
Basement-2:
8.1.2.1 CSU -1000 CFM, 2.5 TR with 80mm S.P. with MERV-7 filters,MERV14 filters withcooling
Coil.
Nos
8.1.2.2 CSU -1850 CFM, 5.0 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling Coil
Nos
Basement-1:
8.1.3.1 CSU -2000 CFM, 4.3 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with cooling
Coil
Nos
8.1.3.2 CSU -1800 CFM, 3.6 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling & Heating Coil.
Nos
8.1.3.3 CSU -1620 CFM, 4.0 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling Coil.
Nos
8.1.3.4 CSU -3000 CFM, 5.6 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling Coil.
Nos
8.1.3.5 CSU -1000 CFM, 2.5 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling Coil.
Nos
8.1.3.6 CSU -800 CFM, 2.0 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with cooling Coil.
Nos
FM AHU -3000 CFM, 7.6 TR with 130mm S.P. with MERV-7 filters,MERV14 filters, UV
lamp, with cooling & Heating Coil.Additional DX coil for 8.5 TR to be provided
Note:(1) The Hepa Filter will be provided at the Terminal by OT Vendor. (2)Separate Dx
8.1.3.7 ODU to be considered as per BOQ specfications for DX coil (Refer BOQ item No. 9.4)
Nos
Ground Floor:
8.1.4.1 CSU -5500 CFM, 14.5 TR with 80mm S.P. with MERV-7 filters,MERV14 filters, UV lamp,with
cooling & Heating Coil.
Nos
8.1.4.2 CSU -1750 CFM, 4.5 TR with 80mm S.P. with MERV-7 filters,MERV14 filters Sulphur
Filters with cooling & Heating Coil.
Nos
8.1.4.3 CSU -2260 CFM, 5.8 TR with 80mm S.P. with MERV-7 filters,MERV14 filters, Sulphur
Filters with cooling & Heating Coil.
Nos
8.1.4.4 CSU -3000 CFM, 7.6 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling Coil.
Nos
8.1.4.5 CSU -3700 CFM, 8.9 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling Coil.
Nos
8.1.4.6 FM AHU -4000 CFM, 9.0 TR with 80mm S.P. with MERV-7 filters,MERV14 filters,
Sulphur Filters with cooling & Heating Coil.
Nos
8.1.4.7 Vertical FM AHU -5500 CFM, 14.5 TR with 80mm S.P. with MERV-7
filters,MERV14 filters with cooling Coil.
Nos
1st Floor:
8.1..5.1 CSU -2800 CFM, 7.0 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling Coil.
Nos
8.1..5.2 CSU -2300 CFM, 6.0 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling Coil.
Nos
8.1..5.3 FM AHU -6600 CFM, 16.5 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling Coil.
Nos
8.1..5.4 FM AHU -4500 CFM, 11.5 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling Coil.
Nos
8.1..5.5 FM AHU -4000 CFM, 10.2 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling Coil.
Nos
2nd Floor:
8.1.6.1 CSU -3000 CFM, 7.5 TR with 80mm S.P. with MERV-7 filters,MERV14 filters, UV lamp, with
cooling Coil.
Nos
8.1.6.2 FM AHU -3100 CFM, 9.7 TR with 80mm S.P. with MERV-7 filters,MERV14 filters, UV
lamp, with cooling & Heating Coil.
Nos
8.1.6.3 FM AHU -4300 CFM, 13.8 TR with 80mm S.P. with MERV-7 filters,MERV14 filters, UV
lamp,with cooling & Heating Coil.
Nos
8.1.6.4 Vertical FM AHU -9050 CFM, 17.0 TR with 80mm S.P. with MERV-7
filters,MERV14 filters, UV lamp, with cooling & Heating Coil.
Nos
3rd Floor:
8.1.7.1 CSU -1450 CFM, 3.6 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling Coil.
Nos
8.1.7.2 CSU -1450 CFM, 3.6 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling & Heating Coil.
Nos
8.1.7.3 CSU -1200 CFM, 3.0 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling & Heating Coil
Nos
8.1.7.4 CSU -2350 CFM, 6.0 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling Coil.
Nos
8.1.7.5 CSU -2400 CFM, 6.0 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling Coil.
Nos
8.1.7.6 FM AHU -3750 CFM, 9.5 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling & Heating Coil.
Nos
Service Floor:
8.1.8.1 CSU -2100 CFM, 5.25 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with cooling
Coil
Nos
FM AHU -5200 CFM, 11.5 TR with 130mm S.P. with MERV-7 filters,MERV14 filters, UV
lamp, with cooling & Heating Coil.Additional DX coil for 11 TR to be provided
Note:(1) The Hepa Filter will be provided at the Terminal by OT Vendor.
8.1.8.2 (2) Separate DX ODU to be considered as per BOQ specfications for DX coil (Refer BOQ
item No.9.3 )
Nos
4th Floor:
8.1.9.1 CSU -3450 CFM, 6.6 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with
cooling Coil.
Nos
5th Floor:
8.1.10 CSU -2000 CFM, 4 TR with 80mm S.P. with MERV-7 filters,MERV14 filters with cooling Coil.
Nos
Ductable Split-Nominal Capacity 2.3 TR ( 1 indoor unit of 2.3 TR & 1 outdoor unit of 2.3 TR )
9.1 including MS stand and Bracket for indoor and outdoor unit
Nos.
HI Wall Split Nominal Capacity 2.0 TR ( 1 indoor unit of 2.0 TR & 1 outdoor unit of 2.0 TR )
9.2 including MS stand and Bracket for indoor and outdoor unit.
Nos.
9.3 Nominal Capacity 11.0 TR ( 1 outdoor unit only of 11.0 TR ) including MS stand and Bracket
for outdoor unit
Nos.
9.4 Nominal Capacity 8.5 TR (1 outdoor unit only of 8.5 TR ) including MS stand and Bracket
for indoor and outdoor unit
Nos.
Basement-3:
10.1.1 Chilled Water FAN COIL UNITS 1.0 TR Nos
10.1.2 Chilled Water FAN COIL UNITS 1.5 TR Nos
Basement-2:
10.2.1 Chilled Water FAN COIL UNITS 1.0 TR Nos
Basement-1:
10.3.1 Chilled Water FAN COIL UNITS 1.0 TR Nos
2nd Floor:
10.4.1 Chilled Water FAN COIL UNITS 1.5 TR (4 Pipe Type) Nos
Service Floor:
10.5.1 Chilled Water FAN COIL UNITS 1.0 TR Nos
10.5.2 Chilled Water FAN COIL UNITS 1.5 TR Nos
10.5.3 Chilled Water FAN COIL UNITS 2.0 TR Nos
10.5.4 Chilled Water FAN COIL UNITS 3.0 TR Nos
4th Floor:
10.6.1 Chilled Water FAN COIL UNITS 1.5 TR Nos
10.6.2 Chilled Water FAN COIL UNITS 3.0 TR Nos
5th Floor:
10.7.1 Chilled Water FAN COIL UNITS 2.0 TR Nos
12 Fan Coil Unit, Chilled water Cassette & Hi Wall Unit Controls
Supply, installation, testing and commissioning of Electronic Pressure
Independant Balancing Cum Two Way Control Valve in a single body equipped
with electronic modulating actuator working on 2-10 V DC, 4- 20 mA electric signal. The
minimum close off Pressure of actuator must be
1.5 times shut off head of pump as per specifications of following range:
13.1 Supply, Installation & Testing of Fan 3 Speed Thermostats with temperatiure control for
FCUs. With wiring complete as required. All Thermostats for Summer/Winter System of
FCUs Shall be Heat Cool with change over.
Nos
13.2 Supply, Installation & Testing Temperature control with Wiring complete as required
for AHU's. All Thermostats for Summer/Winter System of AHUs Shall
be Heat Cool with change over.
Nos
13.3 Supply of Control unit for Temperature and Humidity control with Sensor for OT AHUs
with wiring and complete as required. All Thermostats for Summer/Winter Systme
of AHUs Shall be Heat Cool with change over.
Nos
14 Humidifier
Supply, Installation, Testing & Commissioning of Immersed resistive heater
type of humidification system
b. Steam Hose Pipe of a length of 4m with a Operating temperature range of - 25°C to 105°C.
Hose should be made of thermoplastic rubber with
galvanized steel helix and polyester yarn reinforcement.
i. Each element shall have 1 PTC to detect and protect against overheating;
j. Electric resistances made in titanium with low thermal resistance for fast
response, stability of production and safety against overheating;
k. Must have a Graphic touch display 4.3”
l. Water level sensor for the precise control of the water level on the entire
conductivity range 0…1500µS/cm, without any change or additional board
m. Humidifier shall be suitable for RO / DM Water or all types of water.
n. Intelligent microprocessor controller with algorithm that automatically adapts
operation to the water quality
q. Embedded conductivity meter for the automatic management of the dilution drains and
subsequent fills according to the supply water quality
r. SSR’s (solid-state relays) for precise modulation of the steam production by
dosing the power fed to the water
s. Humidifier should be of IP20 Rating
t. RS485 serial port ready to communicate on Modbus, Bacnet protocol for
supervisory system. Without any additional devices
u. Thermal shock feature, removing lime scale from the heating elements, extends the
cleaning intervals and makes maintenance quicker
v. Metallic housing with cover removable to allow full front access for easy
maintenance
w. The humidifier shall limit the steam production based on a proportional hi- limit probe that
is self-adjusting according to AHU/duct air flow
x. Electrical section separated by a division wall and including the power circuitry
and the control components, manufactured according to state-of-the-art norms
y. Pre-heating to keep the water warm in order to reduce the time to production
(user-editable pre-heating set point
16.1 7750 CFM @ 35 mm wg (For Toilet Ex. Placed on Terrace level) Nos
16.2 1000 CFM @ 25 mm wg Nos
16.3 3060 CFM @ 30 mm wg (For Toilet Ex. Placed on Terrace level) Nos
16.4 800 CFM @ 25 mm wg (For Last Rite Area Placed on Terrace level) Nos
16.5 1200 CFM @ 25 mm wg (For Service floor toilet Ex. Placed on Terrace level) Nos
16.6 500 CFM @ 50 mm wg (For Gr. Floor OT)
Note: additional Hepa Filter to be provided at outlet
Nos
16.7 900 CFM @ 50 mm wg (For 2nd Floor ICU)
Note: additional Hepa Filter to be provided at outlet
Nos
16.8 1000 CFM @ 50 mm wg (For 5th Floor IPD)
Note: additional Hepa Filter to be provided at outlet
Nos
16.9 1100 CFM @ 50 mm wg (For 2nd Floor ICU)
Note: additional Hepa Filter to be provided at outlet
Nos
17 Inline Fans
Supplying, Installing, Testing and Commissioning of Inline fans complete with motor,
supporting frame, gravity louvres,etc. as per drawings and
specifications.
19 VAQ station
VAQ station shall be dynamically calibrated and is capable of receiving demand signal from
CO2 sensors or BMS.Complete with programmable, DDC Advanced Application Controller
that communicates on direct digital control using point 2 point analog controls with CO2
sensors, differential pressure sensor & step down transformer of 24V.
The fan shall be fire rated for minimum 250 Deg C for 2 Hrs, Class-H motors suitable for
415±10% volts, 50 cycles, 3 phase AC supply & fan-motor efficiency exceeding
ASHRAE 90.1-2013 Criteria and static pressure shall be as per indicated. All the Emergency
fans shall be activated in case of fire signal from fire alarm system.
1. The bidder shall submit fan performance curves for all fans.
2. The item should be all complete in line with relevant standards, technical
specifications of the standards and direction of engineer incharge.
3. All the normal operation Fans shall be Vane Axial Type
4. The sound level not exceed 75 dB(A) at 3 m distance for Normal operation fans.
Basement-3:
20.1 2450 CFM @ 25mmWg Nos.
20.2 1150 CFM @ 25mmWg Nos.
20.3 1900 CFM @ 25mmWg Nos.
20.4 1500 CFM @ 25mmWg Nos.
20.5 21350 CFM @ 25mmWg Nos.
20.6 9800 CFM @ 25mmWg Nos.
Basement-2:
20.7 2400 CFM @ 25mmWg Nos.
20.9 24000 CFM @ 25mmWg Nos.
20.10 13100 CFM @ 25mmWg Nos.
Basement-1:
20.11 3950 CFM @ 25mmWg Nos.
20.12 2150 CFM @ 25mmWg Nos.
20.13 3900 CFM @ 25mmWg Nos.
20.14 8850 CFM @ 25mmWg Nos.
20.15 2850 CFM @ 25mmWg Nos.
20.16 6650 CFM @ 25mmWg Nos.
20.17 4000 CFM @ 25mmWg Nos.
20.18 1200 CFM @ 25mmWg Nos.
20.19 11650 CFM @ 30mmWg Nos.
20.20 12400 CFM @ 25mmWg Nos.
Ground Floor:
20.20 3050 CFM @ 25mmWg Nos.
20.21 1550 CFM @ 25mmWg Nos.
1st Floor:
20.22 6200 CFM @ 25mmWg Nos.
20.23 800 CFM @ 25mmWg Nos.
20.24 1900 CFM @ 25mmWg Nos.
2nd Floor:
20.25 700 CFM @ 25mmWg Nos.
20.26 1100 CFM @ 25mmWg Nos.
20.27 5000 CFM @ 25mmWg Nos.
3rd Floor:
20.28 2500 CFM @ 25mmWg Nos.
20.29 3500 CFM @ 25mmWg Nos.
20.30 700 CFM @ 25mmWg Nos.
4th Floor:
20.31 3250 CFM @ 25mmWg Nos.
20.32 800 CFM @ 25mmWg Nos.
5th Floor:
20.33 3250 CFM @ 25mmWg Nos.
20.34 800 CFM @ 25mmWg Nos.
Terrace:
20.35 1200 CFM @ 25mmWg Nos.
20.36 1100 CFM @ 25mmWg Nos.
20.37 1850 CFM @ 25mmWg Nos.
Class-F motors shall be suitable for 415±10% volts, 50 cycles , 3 phase AC supply &
fan-motor efficiency exceeding ASHRAE 90.1-2013 Criteria and static pressure shall be as
indicated. All the Emergency fans shall be activated in case
of fire signal from fire alarm system.
Basement-3:
21.1 2450 CFM @ 25mmWg Nos.
21.2 1150 CFM @ 25mmWg Nos.
21.3 3100 CFM @ 25mmWg Nos.
21.4 21350 CFM @ 25mmWg Nos.
21.5 9800 CFM @ 25mmWg Nos.
Basement-2:
21.6 2400 CFM @ 25mmWg Nos.
21.7 12400 CFM @ 25mmWg Nos.
21.8 24000 CFM @ 25mmWg Nos.
21.9 13100 CFM @ 25mmWg Nos.
Basement-1:
21.10 3950 CFM @ 25mmWg Nos.
21.11 2150 CFM @ 25mmWg Nos.
21.12 3900 CFM @ 25mmWg Nos.
21.13 11700 CFM @ 25mmWg Nos.
21.15 6650 CFM @ 25mmWg Nos.
21.16 3600 CFM @ 25mmWg Nos.
21.17 800 CFM @ 25mmWg Nos.
21.18 1200 CFM @ 30mmWg Nos.
21.19 10500 CFM @ 25mmWg Nos.
21.20 1600 CFM @ 25mmWg Nos.
Ground Floor:
21.20 3050 CFM @ 25mmWg Nos.
21.21 6950 CFM @ 25mmWg Nos.
1st Floor:
21.22 800 CFM @ 25mmWg Nos.
21.23 1900 CFM @ 25mmWg Nos.
2nd Floor:
21.24 700 CFM @ 25mmWg Nos.
21.25 1100 CFM @ 25mmWg Nos.
21.26 5000 CFM @ 25mmWg Nos.
3rd Floor:
21.27 6000 CFM @ 25mmWg Nos.
21.28 700 CFM @ 25mmWg Nos.
4th Floor:
21.29 4450 CFM @ 25mmWg Nos.
21.30 800 CFM @ 25mmWg Nos.
5th Floor:
21.31 3250 CFM @ 25mmWg Nos.
21.32 800 CFM @ 25mmWg Nos.
Terrace:
21.33 1200 CFM @ 25mmWg Nos.
21.34 1100 CFM @ 25mmWg Nos.
21.35 1850 CFM @ 25mmWg Nos.
Pressurization Fans:
a) Lift Well:
i) 10150 CFM @ 30mmWG Nos.
ii) 9650 CFM @ 30mmWG Nos.
b) Lift Lobby:
i) 34750 CFM @ 30mmWG Nos.
ii) 21250 CFM @ 30mmWG Nos.
c) Staircase:
i) 18200 CFM @ 30mmWG Nos.
ii) 17850 CFM @ 30mmWG Nos.
22 Propeller Fans
Supplying & Installing of Propeller fans complete with motor, supporting frame, gravity
louvres,etc. as per drawings and specifications.
20.1 150 CFM Nos
20.2 250 CFM Nos
20.3 500 CFM Nos
20.4 750 CFM Nos
20.5 1000 CFM Nos
23 FAN SECTION
Supply, installation, testing, commissioning of double skin fan section with 50mm thick PUF
insulation fan section consist of Centrifugal Fan, forward curve, with radial tip double
wheel, double inlet, consisting of motor, drive arrangement, aluminium common frame for
fan and motor, cushy foot mounting, aluminium base frame for the unit, VCD on the outlet
of fan, and accessories as per specification and drawing.
25.1 Nominal Capacity 1.0 TR including Bracket for indoor unit Nos.
25.2 Nominal Capacity 1.5 TR including Bracket for indoor unit Nos.
25.3 Nominal Capacity 2.0 TR including Bracket for indoor unit Nos.
25.4 Nominal Capacity 2.5 TR including Bracket for indoor unit Nos.
27 Air Curtain
Supply, Installation, Testing and Commissioning of Air curtain as per mentioned
specifications:
Air Curtain-
27.1 L~2000 mm; H~235 mm; W~208 mm; Max. Velocity ~ 23 / 18 m/s; Dual Speed; Al Chassis
with CRC Plates
Accessories/LS MAG Double Flap/Limit Switch Limit Switch; Magnetic Type; for a Double
Flap Push Pull Door
Nos.
Note:- The pipes size 150 mm & below shall be M.S. `C' class as per IS:1239 and
pipes size above 150 mm shall be black steel pipe heavy class as per IS:3589, from
minimum 6.0 mm thick M.S. sheet for pipes from 200mm dia upto 400 mm dia.
2 Valves
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the
chilled water piping duly insulated to the same specification as the connected piping and
for condenser water fitting non insulated adequetly
supported as per specifications.
2.3.1 20 MM Nos
2.3.2 25 MM Nos
2.3.3 32 MM Nos
2.3.4 40 MM Nos
2.4.1 20 MM Nos
2.4.2 25 MM Nos
2.4.3 32 MM Nos
2.4.4 40 MM Nos
2.8 Y - Strainers
Supply, installation, testing and commi-ssioning of Y - strainer along with flanges
connection complete as per specifications and drawings. (PN-16)
2.8.1 80 MM Nos
2.8.2 65 MM Nos
2.8.3 50 MM Nos
2.8.4 40 MM Nos
2.8.5 32 MM Nos
2.8.6 25 MM Nos
3 Pressure Gauges
Pressure Gauge 6" Dial ( 0 To 6 Kg/CM2 ) with approved ball valve. Industrial type pressure
gauges with SS syphon, gun metal / brass valves complete as
required
Nos
5 Flow Switches
Providing and fixing water flow switch on chilled water outlet complete as per
specifications and drawings.
Nos
2) Pressurized Expansion Tank 2000 liter made from top quality steel and finished
with a gleaming red epoxy-powder coating c/w high quality butyl rubber removable
bladder, Nitrogen filling for longer maintenance of pre pressurization
9 Float Valves
Providing and fixing of the following Float valves.
9.1 50 MM Nos
10 Pot Strainer
Supply, Installation and Testing of MS Pot strainer PN -16, Including Flanges, nutbolts,
gaskits and Lifting shifting to terrace complete as required.
10.1 250 MM Nos
11 Drain Piping
G. I. drain piping of 'B' Class complete with fittings, supports, valves and closed cell
elastomeric insulation/nitrite rubber having a ‘K’ valve of 0.027 W/mK at a mean
temperature of 10 degree C and a minimum density of 55 Kg./cubm of 6 mm thickness
as per specifications and drawings.
Providng and fixing pipes with all necessary fittings, supports and insulation.
11.1 25 MM Rmt
11.2 32 MM Rmt
11.3 40 MM Rmt
12 Refrigerant Piping for Split Air Conditioning Units (Hi Wall and Ductable type)
RM
13 Drain Piping
Supply & Installation of heavy duty PVC drain pipe with min. wall thickness of 4 mm with
insulation as per specification for split air conditioning units including cutting and chasing
in wall for crossing and making good the same if required.Insulation shall be of
9 mm thick sleeve of nitrile rubber having K valve 0.037 W/mk at a mean temp. of 10°C
and min. density of 55 Kg/m3.The insulation joints shall be properly sealed with rubber
based adhesive to ensure proper bonding.
13.1 25 MM RM
13.2 32 MM RM
3 Flexible Duct
Providing and fixing Fire retardant double wall, insulated dia as given below spiral
flexible duct with G.I. adjustable tie bands for either end of duct complete as pet
specifications and drawings.
4 Acoustic Lining
Supplying, installing & testing of acoustic lining within supply and return air ducts as
per the specifications. Acoustic lining of open cell Nitrile Rubber foam within 160-
180 Kg/m3 density with complete in all respects as per specifications.
Supply, installation, testing & balancing of GI Volume Control Damper (20G) within ducts
6.2 to be provided with suitable links, levers and quadrants as per specifications &
approved shop drawings.
Sqm
6.6 Supplying, installing, testing and balancing of powder coated extruded aluminium
construction Supply Air Diffusers with AL powder coated damper as per specification &
approved shop drawings.
Sqm
Supplying, installing , testing & balancing of powder coated extruded aluminium
6.7 construction Fresh Air Louvers with filters with bird screen complete as per
specification & approved shop drawings.
Sqm
Supply, installation, testing and balancing of GI sheet constructed back draft damper /
6.9 gravity Louvers as per specification & approved shop drawings.
Sqm.
Sqmt
Incoming(2 Nos):
630 Amp 4-Pole MCCB, 25kA with thermal magnetic based O/L, S/C and E/F releases.
Multifunction meter and 630/5A, CL-1, 10VA CTs and 2A control MCB.
Bus Bars
800A, TPN Aluminium, colour coded bus bars suitable for 415V, 50Hz. (After deration)
Bus Coupler
800 Amp 4-Pole ACB, 25kA with thermal magnetic based O/L, S/C and E/F releases.
Outgoings
DOL/Star Delta Starter of following rating with Auto/ Manual selector switch, MPCB/MCCB,
over load relay, single phasing preventor, ON/OFF/ Trip indication lamps, Ammeters with
CTs, ON/OFF push Buttons, contractor and suitable No. of Potential free contacts for
remote / local operations, indication, interlocking with Fire Alarm panel and Building
Management system. (Starter shall have MPCB/MCCB in the incomer as per type -2
coordination for fuseless type feeders.)
Incoming:
One (1),400A FP MCCB with microprocessor based releases, ON/OFF/Trip indicating
lamps with 2A control MCB.
Multifunction meter and 400/5A, CL-1, 10VA CTs and 2A control MCB.
Bus Bar:
500A, TPN aluminium, colour coded bus bars with PVC heat shrink sleeves suitable for
415V, 50Hz
Outgoing:
Multifunction meter and 32/5A, CL-1, 10VA CTs and 2A control MCB.
Sets of phase indicating lamps with 2A control MCBs.
Bus Bars
40A, TPN Aluminium, colour coded bus bars suitable for 415V, 50Hz. (After deration)
Outgoings
DOL/Star Delta Starter of following rating with Auto/ Manual selector switch, MPCB/MCCB,
over load relay, single phasing preventor, ON/OFF/ Trip indication lamps, Ammeters with
CTs, ON/OFF push Buttons, contractor and suitable No. of Potential free contacts for
remote / local operations, indication, interlocking with Fire Alarm panel and Building
Management system. (Starter shall have MPCB/MCCB in the incomer as per type -2
coordination for fuseless type feeders.)
Incoming:
16 Amp 4-Pole MCB, 25kA with thermal magnetic based O/L, S/C and E/F releases.
Multifunction meter and 16/5A, CL-1, 10VA CTs and 2A control MCB.
Sets of phase indicating lamps with 2A control MCBs.
Bus Bars
32A, TPN Aluminium, colour coded bus bars suitable for 415V, 50Hz. (After deration)
Outgoings
DOL/Star Delta Starter of following rating with Auto/ Manual selector switch, MPCB/MCCB,
over load relay, single phasing preventor, ON/OFF/ Trip indication lamps, Ammeters with
CTs, ON/OFF push Buttons, contractor and suitable No. of Potential free contacts for
remote / local operations, indication, interlocking with Fire Alarm panel and Building
Management system. (Starter shall have MPCB/MCCB in the incomer as per type -2
coordination for fuseless type feeders.)
Incoming:
63 Amp 4-Pole MCCB, 25kA with thermal magnetic based O/L, S/C and E/F releases.
Multifunction meter and 63/5A, CL-1, 10VA CTs and 2A control MCB.
Sets of phase indicating lamps with 2A control MCBs.
Bus Bars
100A, TPN Aluminium, colour coded bus bars suitable for 415V, 50Hz. (After deration)
. Outgoings
DOL/Star Delta Starter of following rating with Auto/ Manual selector switch, MPCB/MCCB,
over load relay, single phasing preventor, ON/OFF/ Trip indication lamps, Ammeters with
CTs, ON/OFF push Buttons, contractor and suitable No. of Potential free contacts for
remote / local operations, indication, interlocking with Fire Alarm panel and Building
Management system. (Starter shall have MPCB/MCCB in the incomer as per type -2
coordination for fuseless type feeders.)
Incoming:
63 Amp 4-Pole MCCB, 25kA with thermal magnetic based O/L, S/C and E/F releases.
Multifunction meter and 63/5A, CL-1, 10VA CTs and 2A control MCB.
Sets of phase indicating lamps with 2A control MCBs.
Bus Bars
100A, TPN Aluminium, colour coded bus bars suitable for 415V, 50Hz. (After deration)
Outgoings
DOL/Star Delta Starter of following rating with Auto/ Manual selector switch, MPCB/MCCB,
over load relay, single phasing preventor, ON/OFF/ Trip indication lamps, Ammeters with
CTs, ON/OFF push Buttons, contractor and suitable No. of Potential free contacts for
remote / local operations, indication, interlocking with Fire Alarm panel and Building
Management system. (Starter shall have MPCB/MCCB in the incomer as per type -2
coordination for fuseless type feeders.)
Incoming:
63 Amp 4-Pole MCCB, 25kA with thermal magnetic based O/L, S/C and E/F releases.
Multifunction meter and 63/5A, CL-1, 10VA CTs and 2A control MCB.
Sets of phase indicating lamps with 2A control MCBs.
Bus Bars
100A, TPN Aluminium, colour coded bus bars suitable for 415V, 50Hz. (After deration)
Outgoings
DOL/Star Delta Starter of following rating with Auto/ Manual selector switch, MPCB/MCCB,
over load relay, single phasing preventor, ON/OFF/ Trip indication lamps, Ammeters with
CTs, ON/OFF push Buttons, contractor and suitable No. of Potential free contacts for
remote / local operations, indication, interlocking with Fire Alarm panel and Building
Management system. (Starter shall have MPCB/MCCB in the incomer as per type -2
coordination for fuseless type feeders.)
Incoming:
63 Amp 4-Pole MCCB, 25kA with thermal magnetic based O/L, S/C and E/F releases.
Multifunction meter and 63/5A, CL-1, 10VA CTs and 2A control MCB.
Sets of phase indicating lamps with 2A control MCBs.
Bus Bars
100A, TPN Aluminium, colour coded bus bars suitable for 415V, 50Hz. (After deration)
Outgoings
DOL/Star Delta Starter of following rating with Auto/ Manual selector switch, MPCB/MCCB,
over load relay, single phasing preventor, ON/OFF/ Trip indication lamps, Ammeters with
CTs, ON/OFF push Buttons, contractor and suitable No. of Potential free contacts for
remote / local operations, indication, interlocking with Fire Alarm panel and Building
Management system. (Starter shall have MPCB/MCCB in the incomer as per type -2
coordination for fuseless type feeders.)
Incoming:
40 Amp 4-Pole MCB, 25kA with thermal magnetic based O/L, S/C and E/F releases.
Multifunction meter and 40/5A, CL-1, 10VA CTs and 2A control MCB.
Sets of phase indicating lamps with 2A control MCBs.
Bus Bars
63A, TPN Aluminium, colour coded bus bars suitable for 415V, 50Hz. (After deration)
Outgoings
DOL/Star Delta Starter of following rating with Auto/ Manual selector switch, MPCB/MCCB,
over load relay, single phasing preventor, ON/OFF/ Trip indication lamps, Ammeters with
CTs, ON/OFF push Buttons, contractor and suitable No. of Potential free contacts for
remote / local operations, indication, interlocking with Fire Alarm panel and Building
Management system. (Starter shall have MPCB/MCCB in the incomer as per type -2
coordination for fuseless type feeders.)
Incoming:
32 Amp 4-Pole MCB, 25kA with thermal magnetic based O/L, S/C and E/F
releases.
Multifunction meter and 32/5A, CL-1, 10VA CTs and 2A control MCB.
Sets of phase indicating lamps with 2A control MCBs.
Bus Bars
40A, TPN Aluminium, colour coded bus bars suitable for 415V, 50Hz. (After
deration)
Outgoings
Incoming:
16 Amp 4-Pole MCB, 25kA with thermal magnetic based O/L, S/C and E/F
releases.
Multifunction meter and 16/5A, CL-1, 10VA CTs and 2A control MCB.
Sets of phase indicating lamps with 2A control MCBs.
Bus Bars
40A, TPN Aluminium, colour coded bus bars suitable for 415V, 50Hz. (After
deration)
Outgoings
Incoming:
200 Amp 4-Pole MCCB, 25kA with thermal magnetic based O/L, S/C and E/F releases.
Multifunction meter and 200/5A, CL-1, 10VA CTs and 2A control MCB.
Sets of phase indicating lamps with 2A control MCBs.
Bus Bars
250A, TPN Aluminium, colour coded bus bars suitable for 415V, 50Hz. (After deration)
Outgoings
Incoming:
400 Amp 4-Pole MCCB, 25kA with thermal magnetic based O/L, S/C and E/F
releases.
Multifunction meter and 400/5A, CL-1, 10VA CTs and 2A control MCB.
Sets of phase indicating lamps with 2A control MCBs.
Bus Bars
630A, TPN Aluminium, colour coded bus bars suitable for 415V, 50Hz. (After
deration)
Outgoings
Incoming:
63 Amp 4-Pole MCCB, 25kA with thermal magnetic based O/L, S/C and E/F
releases.
Multifunction meter and 63/5A, CL-1, 10VA CTs and 2A control MCB.
Sets of phase indicating lamps with 2A control MCBs.
Bus Bars
100A, TPN Aluminium, colour coded bus bars suitable for 415V, 50Hz. (After
deration)
Outgoings
DOL/Star Delta Starter of following rating with Auto/ Manual selector switch, MPCB/MCCB,
over load relay, single phasing preventor, ON/OFF/ Trip indication lamps, Ammeters with
CTs, ON/OFF push Buttons, contractor and suitable No. of Potential free contacts for
remote / local operations, indication, interlocking with Fire Alarm panel and Building
Management system. (Starter shall have MPCB/MCCB in the incomer as per type -2
coordination for fuseless type feeders.)
Incoming:
200 Amp 4-Pole MCCB, 25kA with thermal magnetic based O/L, S/C and E/F
releases.
Multifunction meter and 200/5A, CL-1, 10VA CTs and 2A control MCB.
Sets of phase indicating lamps with 2A control MCBs.
Bus Bars
250A, TPN Aluminium, colour coded bus bars suitable for 415V, 50Hz. (After
deration)
Outgoings
DOL/Star Delta Starter of following rating with Auto/ Manual selector switch, MPCB/MCCB,
over load relay, single phasing preventor, ON/OFF/ Trip indication lamps, Ammeters with
CTs, ON/OFF push Buttons, contractor and suitable No. of Potential free contacts for
remote / local operations, indication, interlocking with Fire Alarm panel and Building
Management system. (Starter shall have MPCB/MCCB in the incomer as per type -2
coordination for fuseless type feeders.)
4.0 Providing & fixing control / transmission cable/wiring with suitable size
termination glands ,given below copper cable in M.S conduit/ cable tray or in suitable
boxing between indoor units and outdoor units.
The cost of M.S conduits shall include all accessories (I.e., clamps, nuts/ bolts, bends,
junction boxes, inspection boxes and outlet boxes etc) concealed or exposed called
for including necessary civil work such as chase cutting &
making good:
3
3
3
2
1
3
3
1
1
1
1
1
1
RO
RO
5
1
2
3
3
3
1
16
2
20
9
18
16
15
5
26
32
25
RO
4
2
87
49
5
1
4
2
1
1
1
1
1
2
RO
2
1
2
1
3
2
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
2
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
2
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
RO
1
1
4
1
1
1
1
1
RO
RO
2
RO
RO
1
1
2
10
5
RO
8
1
3
RO
RO
RO
202
63
159
273
604
824
683
527
635
1050
RO
0
0
3
0
1
9
9
16
6
20
26
50
2
5
3
2
2
0
110
19
11
0
110
19
15
0
0
6
9
1
5
7
6
14
23
14
RO
3
6
2
RO
3
0
3
6
2
0
0
5
13
10
14
8
6
12
6
136
128
9
20
0
189
0
28
11
42
25
11
16
105
131
525
399
7373
3486
1313
593
0
420
173
53
37
53
0
0
1260
95
4148
599
252
25
147
263
17
15
43
25
53
28
110
RO
RO
420
1000
-
1
3
1
5
1
1
2
1
2
2
1
2
1
1
1
2
4
2
1
1
3
1
1
2
3
1
1
5
1
1
2
1
1
1
1
1
5
1
2
2
2
4
6
7
2
2
6
4
8
1
5
2
3
3
2
2
1
7
2
3
5
7
2
2
6
3
1
239
273
0
609
840
78
189
473
0
5104
911
37
662
90
84
79
263