Service Manual
Service Manual
Capacity: 24kBtu/h~60kBtu/h
Operation Range:
1
V081020
Foreword
Thank you for choosing MRCOOL Universal air conditioners. In order to correctly install and use our units,
and for the satisfactory operation effect, please read this manual carefully.
This manual specifies safe operation requirements from perspectives of product introduction, control,
troubleshooting and maintenance, as well as basic principles and implementation methods. Professional
operators must abide by relevant national (local) safety requirements and technical specifications set forth in
this manual during operations; otherwise, the air conditioning system may fail or be damaged, and personnel
Safety Notice
Before using the air conditioner, please first read the instruction manual.
Before installing the air conditioner, please first read the instruction manual.
Before repairing the air conditioner, please first read the technical service manual.
CONTENTS
1 Product Introduction ...................................................................................................... 3
1.1 Lists of Units .......................................................................................................................... 3
1.2 Electrical Parameters ............................................................................................................. 5
2 Control ............................................................................................................................. 6
2.1 Operation Mode ..................................................................................................................... 6
2.2 Control Mode ......................................................................................................................... 8
2.3 Functions ............................................................................................................................. 10
3 Troubleshooting............................................................................................................ 14
3.1 Wiring Diagrams .................................................................................................................. 14
3.2 PCB Layout.......................................................................................................................... 17
3.3 Error Code ........................................................................................................................... 25
3.4 Troubleshooting ................................................................................................................... 26
3.5 Failures Not Caused by Errors ............................................................................................. 53
4 Maintenance .................................................................................................................. 55
4.1 System Diagram .................................................................................................................. 55
4.2 Connection Pipe Vacuum Pumping ...................................................................................... 55
4.3 Refrigerant Charging ............................................................................................................ 57
4.4 Maintenance of Major Components ...................................................................................... 59
4.5 Removal of Major Components ............................................................................................ 69
4.6 Explosive View and Lists of Parts ....................................................................................... 104
Appendices .................................................................................................................... 110
1 Resistance/Temperature Lists of Temperature Sensors ......................................... 110
1.1 Voltage List of 15 KΩ Temperature Sensors ....................................................................... 110
1.2 Voltage List of 20 KΩ Pipeline Temperature Sensors ......................................................... 112
1.3 Voltage List of 50 KΩ Discharge Temperature Sensors ...................................................... 114
PROHIBITED:
(3) The appliance shall be stored in a room without continuously operating ignition sources (For example:
(4) Indoor unit adopts special joints that can’t be detached. The installation method is the same with the
common joints. However, because the joint can’t be detached, if it is badly connected and causes leakage,
(5) Using unsuitable parts or tools may lead to electric shock or fire hazard.
(6) If refrigerant leaks during maintenance, please ventilate the room immediately. Heavy leakage may lead to
(8) The appliance should be maintained and cared by authorized technical personnel with necessary
qualifications.
WARNING:
(1) If the working place is more than 6.5 Feet high, please wear a safety helmet, gloves and a safety belt.
(2) Never mix any other substances except the specified refrigerant into the refrigerant circuit.
(3) When re-locating the appliance, check whether the new location is strong enough to withstand the weight
of the appliance.
(4) If there is refrigerant leak, please fix the leak before charging in the refrigerant. After refrigerant is charged,
check for refrigerant leaks. If you cannot spot the leak, stop the maintenance work. Please evacuate the
system and close the service valve to prevent refrigerant leaking into the room.
(6) If you need to carry out maintenance or check the electric circuit without cutting off the power, please be
NOTICE:
(1) If the appliance is maintained at a humid place, it should be grounded to avoid electric shock.
(2) Never repair the unit with wet hands. Operating the unit with wet hands may lead to electric shock.
(3) If the unit is not correctly grounded, please check and fix it.
(4) Before cleaning the unit, please disconnect power to prevent the inner fan from starting up and running at
1
high speed; Otherwise personal injury may occur.
(5) Measure the insulation resistance after maintenance. The resistance must be 3.3 Feet or higher. Bad
(7) Gas appliances, heaters and other fire sources should be kept away from the installation and maintenance
site.
(9) Maintenance should be done only after the refrigerant is completely reclaimed from the unit.
OBSERVED:
(1) After the maintenance work is done, check the drainage of indoor unit.
(2) Do not tilt the unit, otherwise, water may spill out from the unit and make the floor and furniture wet.
(3) Disassembly of the unit, handling of the refrigerant, oil and accessories should all be done according to
PROHIBITED:
(1) Never try to modify the unit, otherwise, it may cause electric shock, overheat or fire hazard.
(2) If the power cord or conducting wires are scratched, please replace them.
(3) Never use connected or extended power cord or share the power socket with other appliances.
WARNING:
(1) If the power plug is dirty, please clean it before inserting it to the power socket. If the power plug is loose,
(2) Do not damage the power cord. A damaged or refitted power cord may lead to electric shock or fire hazard.
NOTICE:
(1) After changing the batteries of remote control, please discard them to avoid being swallowed by children.
(2) When the unit is working, do not remove the fan cover.
(3) Do not use organic solvents to wipe the controller operating panel.
(4) Before cleaning the unit, cut off the power supply.
2
1 Product Introduction
Power Supply
Model Product Code Appearance
V/Ph/Hz
3
1.1.2 List of Indoor Units
Power Supply
Cooling/Heating Product
Model Appearance
Capacity (Btu/h) Code
V/Ph/Hz
4
1.2 Electrical Parameters
Power supply Circuit breaker capacity
Model
V/Ph/Hz A
MDUO18024036 208/230V-1Ph-60Hz 35
MDUO18036048 208/230V-1Ph-60Hz 45
5
2 Control
6
2.1.2 Heating Mode
7
2.2 Control Mode
When cooling or heating mode is turned on, indoor fan will run for a while before the compressor starts.
Under different modes, the compressor can only be stopped after running for some time (special cases excluded).
This is to protect the compressor from frequent start or stop. Once the compressor is stopped, it must not be
When the unit is first started, the electronic expansion valve will reset control. During the process, the
expansion valve will produce rattling sound. When cooling or heating mode is turned on, the valve will be open at
This series air conditioner has two types of outdoor units: one with a single fan and the other with double
fans. The outdoor fan can run at the highest level 10 and the lowest level 1. By controlling the speed of outdoor
fan, the unit can achieve cooling at low temperature and heating at high temperature. In fan mode, outdoor fan
After heating mode is turned on for a while, 4-way valve will be energized to change the direction of
refrigerant flow so that the system can run in heating and the indoor unit will not blow cold air. Under other modes,
To avoid the 4-way valve from incorrectly changing directions, when the unit stops in heating, due to a
temperature point or other protection reasons, the 4-way valve will continue to function temporarily and lose
There must be adequate differential pressure for the 4-way valve to change directions.
ODU defrosting control in heating: Defrosting will start when the temperature sensed by outdoor tube
temperature sensor reaches a preset value. During defrosting, the 4-way valve will switch to the cooling condition,
8
and outdoor and indoor fan will both stop. When the temperature sensed by outdoor tube temperature sensor
reaches the preset value of defrosting stop, system will quit defrosting. The 4-way valve will switch back to the
If the unit is running at low frequency for a long time, system will enable oil return control. This is to lead oil in
the pipeline back to the compressor so that the compressor will not be lack of oil. Generally, the oil return takes
about 5min. The compressor running frequency will be raised to the preset oil return frequency.
System will enable high pressure protection control if the high pressure switch is detected open for
continuously a little time. Under high pressure protection, system will be shut down and display error code E1.
When high pressure protection occurs for the first time, system will restore operation if the high pressure
switch is detected to be reclosed for continuously a little time. When high pressure protection occurs for the
second time in a certain time period, system will not restore operation. You need to manually turn off the unit and
clear the error before restarting up the unit. (If high pressure protection occurs frequently, please send for
System will enable low pressure protection control if the low pressure switch is detected open for
continuously a little time. Under low pressure protection, system will be shut down and display error code E3.
When low pressure protection occurs, system will restore operation if the low pressure switch is detected to be
reclosed within a few minutes after shutdown. If low pressure protection occurs for several times in a period of
time, system will not restore operation automatically. You need to manually turn off the unit before restarting up
the unit.
Under heating mode, system will enable high temperature prevention control if the temperature sensed by
indoor tube temperature sensor reaches a certain value. When high temperature prevention control is enabled,
System will enable discharge temperature protection control if the discharge high temperature sensor is
9
detected open for continuously a little time. Under discharge high temperature protection, system will be shut
down and display error code E4. When discharge high temperature protection occurs, system will restore
operation if the discharge high temperature sensor is detected to be reclosed within a few minutes after shutdown.
If discharge high temperature protection occurs for several times in a period of time, system will not restore
operation automatically. You need to manually turn off the unit before restarting up the unit.
2.3 Functions
Set the capacity of the outdoor unit through the four dip switches of the outdoor unit main control board.
Specific dip switch definition, the first dip switch distinguishes the capacity.
Dip Switches
The second dip switch is used to change the defrost setting, factory default setting is standard defrost. Under
extremely low environment temperature, if the standard defrost cannot have the condenser defrosted completely,
please set the second dip switch to be strong defrost. Under strong defrost, the defrosting time will be longer,
Standard Defrost
(Default)
Strong Defrost
10
2.3.3 Set Operating Mode
The third dip switch and the fourth dip switch are selecting the operating mode. Standard mode is the
conventional mode.
By setting the strong mode dip switches of the condensing unit, the air conditioner can quickly increase the
capacity output and ensure reliable operation in a short time, so as to meet the user's demand for the indoor
Energy saving mode is achieved by setting the condensing unit operating mode to operate the air
Strong mode
Set the indoor fan speed through the eight dip switches of the indoor main control board. The higher level,
Capacity 24K indoor unit dip switches 36K indoor unit dip switches
Level 1
(Default)
Level 2
11
Level 3
Capacity 48K indoor unit dip switches 60K indoor unit dip switches
Level 1
(Default)
Level 2
Level 3
Press and hold "SW1" for about 5s to enter the first level menu of the debugging mode, the outdoor unit
mainboard LED displayer flashes. Under the first level menu, short press "SW1" to switch various functions. After
switching to "06", short press "SW2" or "SW3" to enter the forced defrosting mode, "ON" means open, "OF"
means close, and then short press "SW1" to save. During debugging, if no operation is performed within 10s, the
Press and hold "SW1" for about 5s to enter the first level menu of the debugging mode, the outdoor unit
mainboard LED displayer flashes. Under the first level menu, short press "SW1" to switch various functions. After
switching to "08", short press "SW2" or "SW3" to enter the refrigerant recovery control mode, "ON" means open,
"OF" means close. And then short press "SW1" to save. During debugging, if no operation is performed within
Press and hold "SW1" for about 5s to enter the first level menu of the debugging mode, the outdoor unit
mainboard LED displayer flashes. Under the first level menu, short press "SW1" to switch various functions. After
12
switching to "09", short press "SW2" or "SW3" to enter the forced operation control mode, "01" denotes that turn
on the forced operation cooling mode; "02" denotes that turn on the forced operation cooling mode; "OF"
indicates that shut down the forced cooling / heating mode. And then short press "SW1" to save. During
debugging, if no operation is performed within 10s, the debugging mode interface will be exited.
Thermostat model: XE70-00/E1, please refer to the thermostat instruction manual for all functions.
13
3 Troubleshooting
The following electric diagram is for reference only. Please refer to diagram sticked on the unit as the latest
version.
Model: MDUO18024036
14
Model: MDUO18048060
15
Model: MDUI18048, MDUI18060
16
3.2 PCB Layout
3.2.1 Interface
Indoor unit:
17
Pinboard
18
Outdoor unit:
Model: MDUO18024036,MDUO18048060
Mainboard
19
No. Printing Interface No. Printing Interface
Electromagnetic valve
6 VA 16 COM7 Unit communication interface
interface
Drive Board:
Model: MDUO18024036
13 10 9 8
⑩⑩ ⑩ ⑩
7
11
⑩
⑩
12
⑩
17
1 2 3 4 14 15 16 5 6
No. ⑩⑩
Printing ⑩⑩ ⑩ ⑩⑩
Interface No. Printing
⑩ ⑩ Interface
3 L1-1 PFC induction wire (brown) 12 L2-1 PFC induction wire (yellow)
Model: MDUO18048060
1 L2-2 PFC induction wire (blue) 8 L1-2 PFC induction wire (white)
5 JTAG1 Programming interface (for testing) 12 PWR Drive power supply terminal
21
Filtering Board:
Model: MDUO18024036 2
⑩
1
5
⑩ ⑩
6
⑩ 3
7
⑩ ⑩
4
⑩
No. Printing Interface No. Printing Interface
1 AC-L Power input live wire terminal 5 N-OUT Power output neutral wire terminal (reserved)
2 AC-N Power input neutral wire terminal 6 N-OUT Power output neutral wire terminal
3 E1 Filtering board ground wire terminal 7 L-OUT Power output live wire terminal
4 E2 Filtering board grounding hole (reserved) - - -
Model: MDUO18048060
9 7
8 6
3
4
5
1 2
1 AC-L Power input live wire terminal 6 N-OUT1 Power output neutral wire terminal (reserved)
2 N Power input neutral wire terminal 7 N-OUT Power output neutral wire terminal
3 E Filtering board ground wire terminal 8 L-OUT1 Power output live wire terminal
4 E1 Filtering board grounding hole (reserved) 9 L-OUT Power output live wire terminal
5 DC-BUS Power discharge terminal (for testing) - - -
22
3.2.2 IPM, PFC Testing Method
(1) Preparation before test: prepare a universal meter and turn to its diode option, and then remove the wires
Step 1: put the black probe on the place P and the red one on the wiring terminal U, V, W respectively as
shown in the following figure to measure the voltage between UP, VP and WP.
Step 2: put the red probe on the place N and the black one on the wiring terminal U, V, W respectively as
shown in the following figure to measure the voltage between NU, NV and NW.
(3) If the measured voltages between UP, VP, WP, NU, NV, NV are all among 0.3V-0.7V, then it indicates the
IPM module is normal; If any measured valve is 0, it indicates the IPM is damaged.
(1) Preparation before test: prepare a universal meter and turn to its diode option, and then remove the wires
Step 1: Put the black probe on the place P and the red one on the wiring terminal L1-2, L2-1 respectively as
shown in the following figure to measure the voltage between L1-2 and P; L2-1 and P.
Step 2: Put the red probe on the place N and the black one on the wiring terminal L1-2, L2-1 respectively as
shown in the following figure to measure the voltage between N and L1-2; N and L2-1.
(3) If the measured voltages between L1-2 and P; L2-1 and P; N and L1-2; N and L2-1 are all among
0.3V-0.7V, then it indicates the PFC module is normal; If any measured valve is 0, it indicates the PFC is
damaged.
23
MDUO18024036
MDUO18048060
24
3.3 Error Code
If malfunction occurs during operation, LCD temperature display zone will show the failure information. If
several malfunctions occur at the same time, their corresponding error codes will be shown in turn. When
malfunction occurs, please shut off the unit and send for professional personnel to repair. For example, E1 (as
25
3.4 Troubleshooting
It is judged through the action of high pressure switch. If the high pressure switch is cut off, it is judged that
high pressure is too high and the system stops operation for protection.
Possible reason:
26
Troubleshooting:
27
3.4.2 “E3” Compressor Low-pressure Protection, Refrigerant Shortage
It is judged through the action of low pressure switch. If the low pressure switch is cut off, it is judged that low
pressure is too low and the system stops operation for protection.
Possible reason:
28
Troubleshooting:
E3 protection
Enter
Charge
debugging mode
refrigerant
Check if the through wired
according to the
system low No Yes controller and select
requirement and
pressure is lower without refrigerant
then turn on the unit
than 0.05MPa lacking protection; then
to see if E3
turn on the unit to see
protection still
if E3 protection still
occurs
occurs
Yes
Yes
Check if there is
leakage in the
pipeline
Yes
Yes
Replace the outdoor main
control board
Weld the leakage point and
recharge refrigerant after
vacuum pumping and pressure
retaining are passed
sensor. If the tested temperature value is higher than 115℃, the unit will stop for protection
29
Possible reason:
30
Troubleshooting:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the
range of AD value, If the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously, report
31
the error.
Possible reason:
Troubleshooting:
Malfunction of
condenser
temperature
sensor
Yes
Disconnect
the temperature sensor and No Replace the
measure if its resistance is temperature sensor
normal
Yes
Replace the
outdoor
mainboard
NOTE:
Please refer to Appendix 1 for the relation between temperature and resistance of temperature sensor.
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the
range of AD value, If the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously, report
the error.
32
Possible reason:
■Poor contact between ambient temperature sensor and terminal in mainboard interface
Troubleshooting:
NOTE:
Please refer to Appendix 1 for the relation between temperature and resistance of temperature sensor.
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the
range of AD value, If the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously, report
the error.
33
Possible reason:
Troubleshooting:
Malfunction of
discharge
temperature
sensor
Check if the
Correctly insert the
discharge temperature sensor on No
temperature sensor
mainboard is inserted on the on the needle stand
needle stand correctly
Yes
Disconnect
the temperature sensor and No Replace the
measure if its resistance is temperature sensor
normal
Yes
Replace the
outdoor
mainboard
NOTE:
Please refer to Appendix 1 for the relation between temperature and resistance of temperature sensor.
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the
range of AD value, If the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously, report
the error.
34
Possible reason:
Troubleshooting:
Malfunction of
discharge
temperature
sensor
Check if the
Correctly insert the
discharge temperature sensor on No
temperature sensor
mainboard is inserted on the on the needle stand
needle stand correctly
Yes
Disconnect
the temperature sensor and No Replace the
measure if its resistance is temperature sensor
normal
Yes
Replace the
outdoor
mainboard
NOTE:
Please refer to Appendix 1 for the relation between temperature and resistance of temperature sensor.
35
Troubleshooting:
When condensing pressure is higher than the protection value, system will report overload protection.
Possible reason:
36
Troubleshooting:
H4 Overload
YES
Outdoor heat exchanger is blocked Remove the obstacle
NO
YES
Indoor heat exchanger is blocked. Remove the obstacle
NO
NO
NO
YES
Error still exists? Replace the compressor
When power is connected and drive chip received IPM lead F0 that is of low level, than it is IPM module
Possible reason:
37
■Drive board IPM module’s 15V power supply is lower than 13.5V.
■Drive board 6-line PWM signal and the corresponding element are abnormal.
■Drive board compressor current sampling circuit element is damaged or drive chip current sampling AD terminal
is abnormal.
■Compressor is damaged.
Troubleshooting:
Mainboard doesn’t receive the signal of outdoor fan within 30s after the outdoor fan starts up.
38
Possible reason:
■If it is a new unit or a new motor has been replaced in the unit and the wire connection is correct, then probably
Troubleshooting:
Malfunction of
discharge
temperature
sensor
Check if the
Correctly connect the
control wire of outdoor fan motor is No
control wire of fan motor
connected on the outdoor on the mainboard
mainboard correctly
Yes
Replace the
outdoor fan motor and then No Operate the unit with
restart the unit to see if there still
the new motor
is malfunction of outdoor fan
motor
Yes
Replace the
outdoor
mainboard
39
■Drive board compressor current sampling circuit element is damaged or drive chip current sampling AD terminal
is abnormal.
■Compressor is damaged.
Troubleshooting:
40
3.4.13 “HC” PFC Protection
After power is connected, and drive chip received PFC lead F0 that is of low level, than it is PFC module
Possible reason:
■Drive board PFC module’s 15V power supply is lower than 13.5V.
■Drive board PWM signal for PFC and the corresponding element are abnormal.
■Drive board PFC current sampling circuit element is damaged or drive chip current sampling AD terminal is
abnormal.
Troubleshooting:
HC
PFC protection
YES
YES
41
3.4.14 “Lc” Startup Failure
Check the error code on nixie tube of ODU main control board. If PJ is displayed, it indicates
Possible reason:
■Compressor is broken;
Troubleshooting:
42
3.4.15 “P0” Driver Reset Protection
Troubleshooting:
YES
If compressor’s instant current value is higher than the set current protection value, then it can be judged that
compressor over-current occurs and system will shut down for protection.
Possible reason:
43
■Drive board current sampling circuit element is damaged or drive chip current sampling AD terminal is
abnormal.
■Compressor is damaged.
Troubleshooting:
If there is no other malfunction and the communication between master control and driver is cut off for 30s,
then it can be judged that the communication between master control and driver is faulted. System will shut down
for protection.
Possible reason:
■Communication wire between master control and driver is not well connected, or has bad contact, or is broken.
44
■The switch power of drive board is abnormal, therefore, the 3.3V power voltage is abnormal.
■Communication circuit of the drive board or the master control board is abnormal.
Troubleshooting:
If IPM or PFC module temperature is lower than the set protection value, then it can be judged that driver
module sensor error occurs and system will shut down for protection.
Possible reason:
■Drive board current sampling circuit element is damaged or drive chip current sampling AD terminal is
abnormal.
45
Troubleshooting:
■Thermal grease is not applied or not evenly applied to the module, or there is other substance on the back of the
module.
■Drive board temperature sampling circuit element is damaged or drive chip temperature sampling AD terminal is
abnormal.
Troubleshooting:
46
3.4.20 “PA” AC Current Protection
If input current value exceeds the set protection value, then it can be judged that AC current protection
Possible reason:
■Drive board PFC current sampling circuit element is damaged or drive chip PFC current sampling AD terminal is
abnormal.
Troubleshooting:
After power charging, if offset voltage average is detected to exceed 12.5% of 1.65V in 1s, then it can be
judged that current detection (or current sensor) circuit is faulted. System will shut down for protection.
47
Possible reason:
Troubleshooting:
PC Current detection
(or current sensor)
circuit error
When compressor is running and there is no other malfunction, if busbar voltage is lower than the set value
for low voltage protection, then it can be judged that bus low-voltage protection occurs. System will shut down for
protection.
Possible reason:
■Drive board busbar voltage sampling circuit element is damaged or drive board busbar voltage sampling AD
terminal is abnormal.
Troubleshooting:
NO Normal
Grid voltage is normal or not ?
protection
YES
48
3.4.23 “PH” Bus High-Voltage Protection
If there is no other malfunction and the busbar voltage is higher than the set value for high voltage protection,
then it can be judged that bus high-voltage protection occurs. System will shut down for protection.
Possible reason:
■Drive board busbar voltage sampling circuit element is damaged or drive board busbar voltage sampling AD
terminal is abnormal.
Troubleshooting:
When the charge loop starts to get charged and the busbar voltage cannot reach the set value in a certain
period of time, then it can be judged that charge loop error exists. System will shut down for protection.
Possible reason:
■Drive board busbar voltage sampling circuit element is damaged or drive chip busbar voltage sampling AD
terminal is abnormal.
49
Troubleshooting:
PU
Charge loop error
YES
Grid voltage is too low ? Normal protection
NO
If power is connected but the drive board with memory chip cannot detect the memory chip or read the
memory chip data correctly, then it can be judged that drive memory chip error exists.
Possible reason:
■The drive board that needs memory chip is not installed with the memory chip.
Troubleshooting:
YES
50
3.4.26 “e1” High Pressure Sensor Error
Sample the AD value of pressure sensor through pressure sensor detecting circuit and judge the range of
AD value, If the sampling AD value exceeds upper limit and lower limit in 30 seconds continuously, report the
error.
Troubleshooting:
If jumper cap model doesn‘t match with mainboard, report the error
51
Possible reason:
Troubleshooting:
52
3.5 Failures Not Caused by Errors
(1) If your air conditioner fails to function normally, please first check the following items before maintenance:
53
(2) The following situations are not operation failures.
NOTICE:
Check the above items and adopt the corresponding corrective measures. If the air conditioner continues to
function poorly, please stop the air conditioner immediately and contact MrCool's technical support center.
54
4 Maintenance
① Make sure the outlet of vacuum pump is away from fire source and is well-ventilated.
② Before vacuum pumping, make sure the unit cut-off valves are closed.
③ When vacuum pumping, both the liquid pipe and the gas pipe must be pumped.
(1) Remove the caps of the liquid valve, gas valve and also the service port.
(2) meanwhile the gas and liquid valves should be kept closed in case of refrigerant leak.
(3) Connect the hose used for evacuation to the vacuum pump.
(4) Open the switch at the lower pressure side of the manifold valve assembly and start the vacuum pump.
Meanwhile, the switch at the high pressure side of the manifold valve assembly should be kept closed,
And verify if the pressure gauge at the low pressure side of the manifold valve assembly reads -0.1Mpa
(-750mmHg), if not, it indicates there is leak somewhere. Then, close the switch fully and then stop the vacuum
pump.
55
(6) Wait for 10min to see if the system pressure can remain unchanged. If the pressure increase, there may be
leakage.
(7) Slightly open the liquid valve and let some refrigerant go to the connection pipe to balance the pressure
inside and outside of the connection pipe, so that air will not come into the connection pipe when removing
the hose. Notice that the gas and liquid valve can be opened fully only after the manifold valve assembly is
removed.
(8) Place back the caps of the liquid valve, gas valve and also the service port.
NOTICE:
For large-size units, there are maintenance ports for liquid valve and gas valve. During evacuation, you may
connect the two hoses of the branch valve assembly to the maintenance ports to speed up the evacuation.
Refrigerant should be reclaimed into the appropriate storage tank. System should use oxygen-free nitrogen
purging to ensure safety. This process may need to repeat several times. Do not use compressed air or oxygen in
this process.
56
4.3 Refrigerant Charging
Pre-charging
Step 1: Connect the high pressure gauge line to the valve of liquid pipe and connect the low pressure gauge
line to the valve of gas pipe. Connect the middle gauge line to the vacuum pump. Power on the vacuum pump
Step 2: After vacuum drying, close the high and low pressure gauge valves. Then remove the middle gauge
line from the connector of vacuum pump. Then connect to the refrigerant tank.
Step 3: Loosen the middle gauge line from the connector of pressure gauge to a proper extent and slightly
open the valve of refrigerant tank. Evacuate the middle gauge line. Then tighten up the connector again and
Step 4: Keep the refrigerant tank erect and put it on an electronic scale. Record the current weight as m1.
Step 5: Open the high pressure gauge valve (Keep the low pressure gauge valve closed). Then charge
refrigerant into the system. Meanwhile, record the weight of refrigerant tank as m2.
Step 6: m1-m2=m. If m equals to the required charging quantity M, close the valve of refrigerant tank at once.
Step 7: If you can’t continue to charge refrigerant into the system and the quantity of charged refrigerant is
less than the required charging quantity, then record the current quantity of charged refrigerant:
m=m1-m2
m`=M-m
57
Refrigerant charging when unit is turned on:
Step 1: Close the valve of refrigerant tank. First remove the pressure gauge lines and connect the outdoor
unit to the indoor unit. Then reconnect the pressure gauge lines. Connect the low pressure gauge line to the other
joint of gas valve and connect the high pressure gauge line to the liquid valve. Connect the middle gauge line to
the vacuum pump. Power on the vacuum pump and perform vacuum drying.
Step 2: After vacuum drying, close the high and low pressure gauge valves. Then remove the middle gauge
line from the connector of vacuum pump. Then connect to the refrigerant tank.
Step 3: Loosen the middle gauge line from the connector of pressure gauge to a proper extent and slightly
open the valve of refrigerant tank. Evacuate the middle gauge line. Then tighten up the connector again and
Step 4: Turn on the air conditioner and let it run for a while.
Step 5: Open the low pressure gauge valve (Keep the high pressure gauge valve closed). Then charge in the
Step 6: After all required refrigerant is charged in, close the valve of refrigerant tank.
Step 7: Remove the pressure gauge to finish the refrigerant charging work.
Following is the supplementary requirement for refrigerant charging on the basis of normal procedure:
1) Make sure that when charging refrigerant into the system, no other types of refrigerant will be mixed.
The pipeline for refrigerant charging should be as short as possible to reduce the amount of refrigerant
left in it.
3) Make sure the refrigerating system is already grounded before refrigerant charging.
4) When charging is completed (or not yet completed), stick a label on the system.
5) Before re-charging refrigerant into the system, use oxygen-free nitrogen to perform pressure test. When
charging is completed, perform leak test before trial running. Before leaving the workplace, perform a
58
4.4 Maintenance of Major Components
Step 1:
If the unit can be started up, then start it up to check the current of the faulted compressor. Use a pressure
gauge to measure the pressure of the big and small valves. Connect with a computer to monitor the data. Refer
to the following table based on the recommended working current. The electric current of an inverter compressor
will be different under different rotation speed or different working conditions. If the compressor is working at
60Hz, the working current corresponding to different condensing temperature and evaporating temperature is
shown below:
59
Step 2:
Judge whether the operating noise of the compressor is normal, and whether there is a sharp noise or
obvious scraping. If there is a normal compressor working nearby, compare their operating noise.
Step 3:
Examine whether the electronic expansion valve of the outdoor unit is active and whether the 4-way valve
The electronic expansion valve will be reset every time when the unit is powered on or off. Touch the valve
and you can feel the movement of the valve spool. In the last stage of the reset process, you will hear the click of
Electronic expansion
a. Touch the top of the electronic expansion valve and you can feel its move as it is reset upon startup.
During normal operation, the 4 copper tubes that connect to the valve will have different temperature. When
the 4-way valve is working, it will generate some noise and vibration.
60
This is the position of the 4-way
valve. Do not touch it directly
with your hands. There is hot
refrigerant at the exhaust pipe,
so be careful not to be scalded.
S-connect to the inhalation side of the liquid separator; C-connect to the condenser;
When the system is in cooling mode, C-the pipeline is with high pressure and high temperature; E, S-the
When the system is in heating mode, E-the pipeline is with high pressure and high temperature; C, S-the
Because D is connected to the exhaust side, it is with high pressure and high temperature regardless of the
operating mode. When the unit is powered on, in defrosting or oil return mode, the 4-way valve will produce some
noise. Do not touch the pipes directly with your hands and be cautious of the hot temperature.
Step 4:
Step 1:
Cut off the power supply and detach the cover of the wiring box of the compressor. Check the wiring of the
compressor.
Step 2:
Refer to the following table for the resistance between any two terminals:
QXFT-F310zN450
0.79±7%Ω 0.79±7%Ω 0.79±7%Ω
QXAU-F516zX440A
Measure the earth resistance of each wiring terminal. The resistance should be above 10 megohm. If not, we
Step 3:
On condition that the unit cannot be started up, we also need to check the solenoid valve assembly of the
system, including the electronic expansion valve. The checking method is the same as instructed above.
Step 4:
Check whether the IPM module is normal. Please refer to the IPM checking method in the section of
troubleshooting.
Step 1: Preparation
When carrying the old and new compressors, do not place the compressors horizontally or upside down. The
angle of inclination should be within ±30°. Make sure the lubricant inside the compressors will not flow from the oil
62
balance mouth. The suction and exhaust openings of the compressors must be sealed. If a rubber seal is missing,
user adhesive tape to seal the opening. This is to prevent the compressor oil from contacting the air.
NOTICE: Before replacement, make sure the nameplates and models of the compressors are identical.
63
(2) Prepare relevant tools
1) Prepare nitrogen. Please strictly follow the nitrogen welding standards during the welding process.
Make sure there is sufficient nitrogen. The nitrogen pressure should be above 2.0MPa;
2) Prepare welding rods. Prepare some welding rods of common specifications and some special
welding rods that contain more than 5% silver. They are used to weld the compressor. The suction
and exhaust openings of the compressor are all connected to copper-plated steel pipes, so we
3) Prepare applicable welding tools. Please evaluate how much oxygen and acetylene should be used
4) Prepare a complete set of tools, including an internal hexagonal wrench, diagonal pliers, pincer
pliers, nipper pliers, a universal meter, a pressure gauge, cross screwdriver, straight screwdriver,
If the compressor needs to be replaced after judging as above, then switch off the outdoor unit and
disconnect the power cable of the outdoor unit. Use insulating tape to wrap the power cable and put a notice
When you detach the compressor wires, temperature sensors and electric heaters, mark them
Discharge refrigerant from the system. Discharge simultaneously from the high pressure side and low
pressure side. Do not discharge too fast (It should take more than 12h to completely discharge the refrigerant);
otherwise, large quantity of lubricant will escape from the system together with the refrigerant.
Check the condition of the damaged compressor, including its position and model.
(a) If the oil is clear and impurities-free, we consider that the oil of the system is not polluted. Meanwhile, if
we confirm that the valves and pipes are also normal, then we can replace the compressor only. For the removal
that the contaminant at the bottom of the compressor can be poured out.
64
(2) Place the compressor at a position above the ground level and then pour out the oil from the air outlet of
the compressor. Collect the oil in a transparent container. The amount of oil should be over 150ml.
NOTE:
1) The axial direction of the compressor should not slant at an angle larger than 20° to the horizontal
direction.
3) Put a transparent container (over 150ml in volume) under the exhaust pipe to collect the compressor
(3) Put the container of compressor lubricant in a bright location and see if there is impurity and
(b) If the oil is contaminated, replace the compressor and the gas-liquid separator.
NOTE: Confirm whether the compressor needs to be replaced. The pipe mouths of the faulted compressor must be
sealed by adhesive tape as soon as the compressor is detached. Make sure the compressor is well preserved for the
If the oil is contaminated, check the components of the unit, including the gas-liquid separator.
65
1. Remove the screw bolt of
the separator. 2. Remove the screw bolt of
the separator.
When the separator is detached, check whether there are impurities inside. Below is the checking method:
NOTE:
When pouring the liquid from the separator, make sure the discharge pipe is at the lower position.Slant at an
Use a transparent container to collect the content inside the separator. Check its color, seal it well and return
NOTE:
If the compressor is damaged and needs to be replaced, the gas-liquid separator should also be replaced,
whether or not there are impurities in the separator or other abnormal conditions.
Confirm which parts of the system should be replaced. Make sure the pipe mouths of the damaged parts or
components are sealed by adhesive tape as soon as they are detached. Keep them in the original condition for
future analysis.
After confirming which parts of the system should be replaced, check the pipeline of the system. Blow
through the main pipeline with nitrogen. After clearing the pipeline, if the components are not replaced
immediately, seal the pipeline with adhesive tape to prevent the system from being contaminated by water and
For the removal of compressor, please refer to the section: Removal of Major Components.
NOTE:
If a compressor is damaged and needs to be replaced, its gas-liquid separator should also be replaced. This
is to avoid the abnormal condition of the separator from affecting the safe and reliable operation of the system.
For the removal of gas-liquid separator, please refer to the section: Removal of Major Components.
(1) First of all, check each welding point. Check whether the welding points are smooth and whether there is
(2) Next, fill high-pressure nitrogen into the system for leak detection. If it is only the outdoor unit that needs
to be repaired and the indoor unit is confirmed normal, then it’s OK to charge high-pressure nitrogen into
the outdoor unit only. Fill in the nitrogen simultaneously from the high pressure side and low pressure
side. We recommend charging the nitrogen from the big and small valves at the same time. The
pressure of nitrogen should be above 20kgf. Then use soapy water to check for leaks. Check the
(3) Finally, retain the pressure of the system. Fill high-pressure nitrogen into the system and maintain the
pressure above 25kgf. Close the big and small valves and keep the pressure of indoor and outdoor units
for more than 12h. If the pressure remains unchanged, then start vacuum pumping; otherwise, check the
Temperature should be considered when judging the pressure change. If temperature changes by 1℃
For example, if temperature is 30°C(86°F) when nitrogen of 2.5MPa is charged, and temperature changes
to 25°C (77°F) after 12h, we consider that the system is qualified if the pressure is found at 2.43MPa or above.
Please refer to the section of maintenance: vacuum pumping and refrigerant charging.
Connect cables, compressor wires and the electric heating belt according to the signs marked before and
67
4.4.3 How to replace the drive module of compressor
Step 1: First, make sure that power is cut off. Set the universal meter at the AC voltage and measure the
voltage between L1, L2, L3, and N. If each time the voltage is 0V (Errors may occur to the universal meter,
sometimes the voltage may not be 0V), proceed with the next step and put a sign on the power switch that reads
Step 2: Measure the voltage between DC bus P and N on the drive board of the compressor. Set the
universal meter at the DC voltage and measure the voltage between P and N as shown below. If the voltage is
below 36V, proceed with the next step. In case that a universal meter is not available, disconnect power for 20min
Step 3: Remove all the wires on the drive board of the compressor.
Step 4: Remove the screws on the drive board of the compressor. The screws are located in the white circles
Step 5: Replace with a new compressor drive board. Before replacement, apply some silica gel on the IPM
module.
Step 6: Install the new compressor drive board. Fix the screws and connect the wires correctly.
68
4.5 Removal of Major Components
The power drive of the fan. It enables the fan to run so as to provide
Motor smooth currents of air for forced convection and heat exchange of
condenser and evaporator.
It is used to provide smooth currents of air for forced convection and heat
Fan
exchange of condenser and evaporator.
69
Picture Name Function
It is used to transfer partial heat of the hot flow to the cold flow so that the
Condenser flow temperature can reach the specified index. It is an energy exchanging
device.
Electronic It is used to lower the pressure and temperature of liquefied refrigerant and
expansion valve adjust the flow of refrigerant entering the evaporator.
Electromagnetic
Electromagnetic valve controls increased enthalpy switch.
Valve
70
Model: MDUO18024036
Removal of front panel
NOTE: Before removing the front panel, make sure power is cut off.
Step Picture Work instruction
71
Removal of front panel
NOTE: Before removing the front panel, make sure power is cut off.
Step Picture Work instruction
72
Removal of front panel
NOTE: Before removing the front panel, make sure power is cut off.
Step Picture Work instruction
Model: MDUO18024036
Removal of compressor/gas liquid separator
NOTE: Before removing the compressor/gas liquid separator, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
73
Removal of compressor/gas liquid separator
NOTE: Before removing the compressor/gas liquid separator, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
Screws
74
Removal of compressor/gas liquid separator
NOTE: Before removing the compressor/gas liquid separator, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
Screws
75
Model: MDUO18024036
Removal of 4-way valve
NOTE: Before removing the 4-way valve, make sure refrigerant is fully discharged from the unit and power is cut off.
Step Picture Work instruction
76
Removal of 4-way valve
NOTE: Before removing the 4-way valve, make sure refrigerant is fully discharged from the unit and power is cut off.
Step Picture Work instruction
Model: MDUO18024036
Removal of fan and motor
Note: Before removing the fan, make sure power is cut off.
Step Picture Work instruction
Use a screwdriver to
unscrew the two screws
1. Remove the grill.
on the upper left and lower
right corners.
77
Removal of fan and motor
Note: Before removing the fan, make sure power is cut off.
Step Picture Work instruction
Use a screwdriver to
unscrew the bolt of motor.
3. Remove motor. NOTE: Motor wire should
be first removed from the
electric box.
78
Model: MDUO18024036
Removal of condenser
NOTE:Before removing the condenser, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
79
Removal of condenser
NOTE:Before removing the condenser, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
80
Removal of condenser
NOTE:Before removing the condenser, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
81
Model: MDUO18024036
NOTE:Before removing the electronic expansion valve, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
82
Removal of electronic expansion valve
NOTE:Before removing the electronic expansion valve, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
Take off the coil of
electronic expansion
valve.
Loosen the connection
3. Remove the pipe of electronic
electronic expansion valve by
expansion welding. Then remove
valve. the connection pipe.
NOTE: When welding
the pipe, do not let the
flame bunt the other
components.
83
Removal of electronic expansion valve
NOTE:Before removing the electronic expansion valve, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
Model: MDUO18048060
Removal of front panel
NOTE: Before removing the front panel, make sure power is cut off.
Step Picture Work instruction
84
Removal of front panel
NOTE: Before removing the front panel, make sure power is cut off.
Step Picture Work instruction
85
Removal of front panel
NOTE: Before removing the front panel, make sure power is cut off.
Step Picture Work instruction
86
Removal of front panel
NOTE: Before removing the front panel, make sure power is cut off.
Step Picture Work instruction
87
Model: MDUO18048060
Disassembly of compressor
NOTE:Before removing the compressor, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
88
Disassembly of compressor
NOTE:Before removing the compressor, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
89
Disassembly of compressor
NOTE:Before removing the compressor, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
Model: MDUO18048060
Removal of 4-way valve
NOTE:Before removing the 4-way valve, make sure refrigerant is fully discharged from the unit and power is cut off.
Step Picture Work instruction
90
Removal of 4-way valve
NOTE:Before removing the 4-way valve, make sure refrigerant is fully discharged from the unit and power is cut off.
Step Picture Work instruction
91
Model: MDUO18048060
Removal of fan and motor
NOTE: Before removing the fan, make sure power is cut off.
Step Picture Work instruction
Use a screwdriver to
unscrew the two screws on
1. Remove the grill.
the upper left and lower
right corners.
Use a screwdriver to
unscrew the bolt of motor.
3. Remove motor. NOTE: Motor wire should
be first removed from the
electric box.
92
Removal of fan and motor
NOTE: Before removing the fan, make sure power is cut off.
Step Picture Work instruction
93
Model: MDUO18048060
Removal of gas liquid separator
NOTE: Before removing the gas liquid separator, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
94
Removal of gas liquid separator
NOTE: Before removing the gas liquid separator, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
Install the gas liquid separator
by referring to the positions of
entering and leaving pipes.
Weld the 2 welding
interfaces.
Nitrogen welding: the
4. Install the new gas liquid pressure of nitrogen is
separator 0.5±0.1kgf/ cm² (relative
pressure).
NOTE: When welding the
pipes, do not let the flame
burn the other components.
Tighten the screws of gas
liquid separator.
95
Model: MDUO18048060
Removal of electronic expansion valve
NOTE:Before removing the electronic expansion valve, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
96
Removal of electronic expansion valve
NOTE:Before removing the electronic expansion valve, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
97
Removal of electronic expansion valve
NOTE:Before removing the electronic expansion valve, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
98
Disassembly and Assembly of the Electric Box
Step Picture Work instruction
99
Disassembly and Assembly of the Fan Motor
Step Picture Work instruction
100
Disassembly and Assembly of the Evaporator and Drain Pan
Step Picture Work instruction
5. Remove the primary drain ● Remove the primary drain pan from the
pan. unit.
101
Disassembly and Assembly of the Evaporator and Drain Pan
Step Picture Work instruction
6. Remove the secondary drain ● Remove the secondary drain pan from
pan. the unit.
102
Disassembly and Assembly of the Filter
Step Picture Work instruction
unit.
2. Remove the filter screen.
● After replacing the filter screen,
reassemble the unit as before.
103
4.6 Explosive View and Lists of Parts
2
3
4
5
6
7
8
9
10
11
12 57
13 56
14 55
53
15 54
16 52
17
18 51
50
49
19 48
20 47
21
22
23
46
24 45
25 44
43
42
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
104
No. Material name
8 Inductance
9 Terminal Board
10 Terminal Board
11 Radiator
12 Main Board
13 Condenser Assy
14 Filter Sub-Assy
15 Electromagnetic Valve Sub-Assy
16 Magnet Coil (Electromagnetic Valve)
17 Electromagnetic Valve
18 Strainer
19 Brushless DC Motor
20 Axial Flow Fan
21 Cabinet
22 Diversion Circle
23 Front Grill
24 Front Side Plate
25 Compressor And Fittings
26 Handle
27 Chassis Assy
28 Foot
29 Cut Off Valve
30 Fusible Plug
31 Gas-liquid Separator
32 Accumulator
33 4 Way Valve Coil
34 Drainage Hole Cap
35 Temperature Sensor
36 Temperature Sensor
37 Electrical Heater(Compressor)
38 Electrical Heater (Chassis)
39 Electric Expansion Valve Sub-Assy
40 Drainage Joint
41 Cut-Off Valve 3/8(N)
42 Strainer
43 Electric Expand Valve Fitting
44 One Way Valve
45 Electronic Expansion Valve
46 Strainer
47 Electric Expand Valve Fitting
48 Electric Expansion Valve Sub-Assy
49 Rear Side Plate
50 4-Way Valve Assy
51 Silencer
52 Pressure Protect Switch
105
No. Material name
53 Filter
54 Pressure Protect Switch
55 4-Way Valve
56 Pressure Sensor
57 Rear Grill
MDUO18048060 (Product code: 810512032938)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16 50
17 49
18
19 48
20 47
21
22 46
23 45
24 44
25 43
42
26 41
40
27 28 29 30 31 32 33 34 35 36 37 38 39
No. Material name
1 Coping
2 Rear Grill
3 Left Side Plate
4 Electric Box Assy
5 Drive Board
6 Radiator
106
No. Material name
7 Main Board
8 Filter Board
9 Terminal Board
10 Terminal Board
11 Inductance Box Assy
12 Handle
13 Axial Flow Fan
14 Cabinet
15 Brushless DC Motor
16 Gas-liquid Separator Sub-Assy
17 Front Grill
18 Front Side Plate
19 Pressure Protect Switch
20 Brushless DC Motor
21 Electromagnetic Valve
22 Electric Expand Valve Fitting
23 Electric Expansion Valve Sub-Assy
24 Compressor and Fittings
25 Accumulator
26 Foot
27 Chassis Sub-Assy
28 Cut Off Valve Sub-Assy
29 Strainer
30 Magnet Coil (Electromagnetic Valve)
31 Electric Expand Valve Fitting
32 One Way Valve
33 Cut-off Valve
34 Electronic Expansion Valve
35 4-Way Valve Assy
36 Pressure Sensor
37 Strainer
38 Cut Off Valve 3/8
39 Pressure Protect Switch
40 Electrical Heater(Compressor)
41 Electrical Heater(Compressor)
42 4-Way Valve
43 Handle
44 4 Way Valve Coil
45 Drainage Hole Cap
46 Drainage Joint
47 Temperature Sensor
48 Temperature Sensor
49 Rear Side Plate Sub-Assy
50 Condenser Assy
107
4.6.2 IDU Explosive View and Lists of Parts
MDUI18024 | MDUI18036 | MDUI18048 | MDUI18060
Product Code: 810512032945 | 810512032969 | 810512032976 | 810512032952
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
No. Material name
1 Coping
2 Left Side Plate
3 Electric Box Assy
4 Terminal Board
5 Transformer
6 Terminal Board
7 Main Board
8 Terminal Board
9 Pinboard
108
No. Material name
10 Rear Side Plate
11 Centrifugal Fan Assy
12 Motor For Centrifugal Fan
13 Brushless DC Motor
14 Top Cover Board Sub-Assy
15 Bottom Cover Plate Assy
16 Right Side Plate
17 Bottom Cover Plate Assy
18 Water Tray
19 Strainer
20 Cut-Off Valve 3/8(N)
21 Thermal Expansion Valve
22 Cut Off Valve
23 Evaporator Assy
24 Evaporator Assy
25 Evaporator Assy
26 Water Tray Assy
27 Choke Plug
28 Water Tray
29 Filter Sub-Assy
109
Appendices
temperature sensors)
Temperature (℃) Resistance (kΩ) Voltage (V) Temperature (℃) Resistance (kΩ) Voltage (V)
-20 144 0.311 71 2.523 2.825
-19 138.1 0.323 72 2.439 2.838
-18 128.6 0.345 73 2.358 2.852
-17 121.6 0.362 74 2.28 2.865
-16 115 0.381 75 2.205 2.877
-15 108.7 0.4 76 2.133 2.889
-14 102.9 0.42 77 2.064 2.901
-13 97.4 0.44 78 1.997 2.912
-12 92.22 0.462 79 1.933 2.923
-11 87.35 0.484 80 1.871 2.934
-10 82.75 0.506 81 1.811 2.945
-9 78.43 0.53 82 1.754 2.955
-8 74.35 0.554 83 1.699 2.964
-7 70.5 0.579 84 1.645 2.974
-6 66.88 0.605 85 1.594 2.983
-5 63.46 0.631 86 1.544 2.992
-4 60.23 0.658 87 1.497 3.001
-3 57.18 0.686 88 1.451 3.009
-2 54.31 0.714 89 1.408 3.017
-1 51.59 0.743 90 1.363 3.025
0 49.02 0.773 91 1.322 3.033
1 46.8 0.801 92 1.282 3.04
2 44.31 0.835 93 1.244 3.047
3 42.14 0.866 94 1.207 3.054
4 40.09 0.899 95 1.171 3.061
5 38.15 0.931 96 1.136 3.068
6 36.32 0.965 97 1.103 3.074
7 34.58 0.998 98 1.071 3.08
8 32.94 1.033 99 1.039 3.086
9 31.38 1.067 100 1.009 3.092
10 29.9 1.102 101 0.98 3.098
11 28.51 1.138 102 0.952 3.103
12 27.18 1.174 103 0.925 3.108
13 25.92 1.21 104 0.898 3.114
14 24.73 1.246 105 0.873 3.119
110
Temperature (℃) Resistance (kΩ) Voltage (V) Temperature (℃) Resistance (kΩ) Voltage (V)
15 23.6 1.282 106 0.848 3.123
16 22.53 1.319 107 0.825 3.128
17 21.51 1.356 108 0.802 3.133
18 20.54 1.393 109 0.779 3.137
19 19.63 1.429 110 0.758 3.141
20 18.75 1.467 111 0.737 3.145
21 17.93 1.503 112 0.717 3.15
22 17.14 1.54 113 0.697 3.153
23 16.39 1.577 114 0.678 3.157
24 15.68 1.613 115 0.66 3.161
25 15 1.65 116 0.642 3.165
26 14.36 1.686 117 0.625 3.168
27 13.74 1.722 118 0.608 3.171
28 13.16 1.758 119 0.592 3.175
29 12.6 1.793 120 0.577 3.178
30 12.07 1.829 121 0.561 3.181
31 11.57 1.863 122 0.547 3.184
32 11.09 1.897 123 0.532 3.187
33 10.63 1.931 124 0.519 3.19
34 10.2 1.964 125 0.505 3.192
35 9.779 1.998 126 0.492 3.195
36 9.382 2.03 127 0.48 3.198
37 9.003 2.062 128 0.467 3.2
38 8.642 2.094 129 0.456 3.203
39 5.997 2.125 130 0.444 3.205
41 7.653 2.185 131 0.433 3.207
42 7.352 2.215 132 0.422 3.21
43 7.065 2.243 133 0.412 3.212
44 6.791 2.272 134 0.401 3.214
45 6.529 2.299 135 0.391 3.216
46 6.278 2.326 136 0.382 3.218
47 6.038 2.353 137 0.372 3.22
48 5.809 2.379 138 0.363 3.222
49 5.589 2.404 139 0.355 3.224
50 5.379 2.429 140 0.346 3.226
51 5.179 2.453 141 0.338 3.227
52 4.986 2.477 142 0.33 3.229
53 4.802 2.5 143 0.322 3.231
54 4.625 2.522 144 0.314 3.232
55 4.456 2.544 145 0.307 3.234
56 4.294 2.566 146 0.299 3.235
57 4.139 2.586 147 0.292 3.237
58 3.99 2.607 148 0.286 3.238
59 3.848 2.626 149 0.279 3.24
60 3.711 2.646 150 0.273 3.241
111
Temperature (℃) Resistance (kΩ) Voltage (V) Temperature (℃) Resistance (kΩ) Voltage (V)
61 3.579 2.664 151 0.266 3.242
62 3.454 2.682 152 0.261 3.244
63 3.333 2.7 153 0.254 3.245
64 3.217 2.717 154 0.248 3.246
65 3.105 2.734 155 0.243 3.247
66 2.998 2.75 156 0.237 3.249
67 2.898 2.766 157 0.232 3.25
68 2.797 2.781 158 0.227 3.251
69 2.702 2.796 159 0.222 3.252
70 2.611 2.811 160 0.217 3.253
Temperature (℃) Resistance (kΩ) Voltage (V) Temperature (℃) Resistance (kΩ) Voltage (V)
-30 361.8 0.173 66 3.998 2.75
-29 339.8 0.183 67 3.861 2.766
-28 319.2 0.195 68 3.729 2.781
-27 300 0.206 69 3.603 2.796
-26 282.2 0.218 70 3.481 2.811
-25 265.5 0.231 71 3.364 2.825
-24 249.9 0.245 72 3.252 2.838
-23 235.3 0.259 73 3.144 2.852
-22 221.6 0.273 74 3.04 2.865
-21 208.9 0.288 75 2.94 2.877
-20 196.9 0.304 76 2.844 2.889
-19 181.4 0.328 77 2.752 2.901
-18 171.4 0.345 78 2.663 2.912
-17 162.1 0.362 79 2.577 2.923
-16 153.3 0.381 80 2.495 2.934
-15 145 0.4 81 2.415 2.944
-14 137.2 0.42 82 2.339 2.954
-13 129.9 0.44 83 2.265 2.964
-12 123 0.462 84 2.194 2.974
-11 116.5 0.484 85 2.125 2.983
-10 110.3 0.507 86 2.059 2.992
-9 104.6 0.53 87 1.996 3.001
-8 99.13 0.554 88 1.934 3.009
-7 94 0.579 89 1.875 3.017
-6 89.17 0.605 90 1.818 3.025
-5 84.61 0.631 91 1.763 3.033
-4 80.31 0.658 92 1.71 3.04
-3 76.24 0.686 93 1.658 3.047
-2 72.41 0.714 94 1.609 3.054
112
Temperature (℃) Resistance (kΩ) Voltage (V) Temperature (℃) Resistance (kΩ) Voltage (V)
-1 68.79 0.743 95 1.561 3.061
0 65.37 0.773 96 1.515 3.068
1 62.13 0.804 97 1.47 3.074
2 59.08 0.835 98 1.427 3.08
3 56.19 0.866 99 1.386 3.086
4 53.46 0.898 100 1.346 3.092
5 50.87 0.931 101 1.307 3.098
6 48.42 0.965 102 1.269 3.103
7 46.11 0.998 103 1.233 3.108
8 43.92 1.033 104 1.198 3.114
9 41.84 1.067 105 1.164 3.119
10 39.87 1.102 106 1.131 3.123
11 38.01 1.138 107 1.099 3.128
12 36.24 1.174 108 1.069 3.133
13 34.57 1.209 109 1.039 3.137
14 32.98 1.246 110 1.01 3.141
15 31.47 1.282 111 0.9825 3.145
16 30.04 1.319 112 0.9556 3.15
17 28.68 1.356 113 0.9295 3.153
18 27.39 1.393 114 0.9043 3.157
19 26.17 1.429 115 0.8799 3.161
20 25.01 1.466 116 0.8562 3.165
21 23.9 1.503 117 0.8333 3.168
22 22.85 1.54 118 0.8111 3.171
23 21.85 1.577 119 0.7895 3.175
24 20.9 1.614 120 0.7687 3.178
25 20 1.65 121 0.7485 3.181
26 19.14 1.686 122 0.7289 3.184
27 18.32 1.722 123 0.7099 3.187
28 17.55 1.758 124 0.6915 3.19
29 16.8 1.793 125 0.6736 3.192
30 16.1 1.828 126 0.6563 3.195
31 15.43 1.863 127 0.6395 3.198
32 14.79 1.897 128 0.6232 3.2
33 14.18 1.931 129 0.6074 3.203
34 13.59 1.965 130 0.5921 3.205
35 13.04 1.998 131 0.5772 3.207
36 12.51 2.03 132 0.5627 3.21
37 12 2.063 133 0.5487 3.212
38 11.52 2.094 134 0.5351 3.214
39 11.06 2.125 135 0.5219 3.216
40 10.62 2.155 136 0.509 3.218
41 10.2 2.185 137 0.4966 3.22
42 9.803 2.215 138 0.4845 3.222
113
Temperature (℃) Resistance (kΩ) Voltage (V) Temperature (℃) Resistance (kΩ) Voltage (V)
43 9.42 2.243 139 0.4727 3.224
44 9.054 2.272 140 0.4613 3.226
45 8.705 2.299 141 0.4502 3.227
46 8.37 2.326 142 0.4394 3.229
47 8.051 2.353 143 0.4289 3.231
48 7.745 2.379 144 0.4187 3.232
49 7.453 2.404 145 0.4088 3.234
50 7.173 2.429 146 0.3992 3.235
51 6.905 2.453 147 0.3899 3.237
52 6.648 2.477 148 0.3808 3.238
53 6.403 2.5 149 0.3719 3.24
54 6.167 2.522 150 0.3633 3.241
55 5.942 2.544 151 0.3549 3.242
56 5.726 2.565 152 0.3468 3.244
57 5.519 2.586 153 0.3389 3.245
58 5.32 2.607 154 0.3312 3.246
59 5.13 2.626 155 0.3237 3.247
60 4.948 2.646 156 0.3164 3.249
61 4.773 2.664 157 0.3093 3.25
62 4.605 2.682 158 0.3024 3.251
63 4.443 2.7 159 0.2956 3.252
64 4.289 2.717 160 0.2891 3.253
65 4.14 2.734
Temperature (℃) Resistance (kΩ) Voltage (V) Temperature (℃) Resistance (kΩ) Voltage (V)
-30 911.56 0.036 61 11.736 1.518
-29 853.66 0.038 62 11.322 1.548
-28 799.98 0.041 63 10.925 1.577
-27 750.18 0.043 64 10.544 1.606
-26 703.92 0.046 65 10.178 1.635
-25 660.93 0.049 66 9.8269 1.664
-24 620.94 0.052 67 9.4896 1.693
-23 583.72 0.056 68 9.1655 1.722
-22 549.04 0.059 69 8.9542 1.741
-21 516.71 0.063 70 8.5551 1.778
-20 486.55 0.066 71 5.9676 1.806
-19 458.4 0.07 72 7.9913 1.834
-18 432.1 0.075 73 7.7257 1.862
-17 407.51 0.079 74 7.4702 1.889
-16 384.51 0.084 75 7.2245 1.916
114
Temperature (℃) Resistance (kΩ) Voltage (V) Temperature (℃) Resistance (kΩ) Voltage (V)
-15 362.99 0.088 76 6.9882 1.943
-14 342.83 0.094 77 6.7608 1.969
-13 323.94 0.099 78 6.542 1.995
-12 306.23 0.104 79 6.3315 2.021
-11 289.61 0.11 80 6.1288 2.046
-10 274.02 0.116 81 5.9336 2.071
-9 259.37 0.123 82 5.7457 2.096
-8 245.61 0.129 83 5.5647 2.12
-7 232.67 0.136 84 5.3903 2.144
-6 220.5 0.143 85 5.2223 2.168
-5 209.05 0.151 86 5.0605 2.191
-4 195.97 0.158 87 4.9044 2.214
-3 188.12 0.167 88 4.7541 2.237
-2 178.65 0.175 89 4.6091 2.259
-1 169.68 0.184 90 4.4693 2.281
0 161.02 0.193 91 4.3345 2.302
1 153 0.202 92 4.2044 2.323
2 145.42 0.212 93 4.0789 2.344
3 135.96 0.223 94 3.9579 2.364
4 131.5 0.233 95 3.841 2.384
5 126.17 0.242 96 3.7283 2.404
6 119.08 0.256 97 3.6194 2.423
7 113.37 0.267 98 3.5143 2.442
8 107.96 0.28 99 3.4128 2.46
9 102.85 0.292 100 3.3147 2.478
10 98.006 0.306 101 3.22 2.496
11 93.42 0.319 102 3.1285 2.514
12 89.075 0.333 103 3.0401 2.531
13 84.956 0.348 104 2.9547 2.547
14 81.052 0.362 105 2.8721 2.564
15 77.349 0.378 106 2.7922 2.58
16 73.896 0.393 107 2.715 2.595
17 70.503 0.41 108 2.6404 2.611
18 67.338 0.427 109 2.5682 2.626
19 64.333 0.444 110 2.4983 2.64
20 61.478 0.462 111 2.4308 2.655
21 58.766 0.48 112 2.3654 2.669
22 56.189 0.499 113 2.3021 2.682
23 53.738 0.518 114 2.2409 2.696
24 51.408 0.537 115 2.1816 2.709
25 49.191 0.558 116 2.1242 2.722
26 47.082 0.578 117 2.0686 2.734
27 45.074 0.599 118 2.0148 2.747
28 43.163 0.621 119 1.9626 2.759
115
Temperature (℃) Resistance (kΩ) Voltage (V) Temperature (℃) Resistance (kΩ) Voltage (V)
29 41.313 0.643 120 1.9123 2.77
30 39.61 0.665 121 1.8652 2.781
31 37.958 0.688 122 1.8158 2.793
32 36.384 0.711 123 1.7698 2.804
33 34.883 0.735 124 1.7253 2.814
34 33.453 0.759 125 1.6821 2.825
35 32.088 0.784 126 1.6402 2.835
36 30.787 0.809 127 1.5996 2.845
37 29.544 0.835 128 1.5602 2.855
38 28.359 0.86 129 1.522 2.864
39 27.227 0.886 130 1.485 2.873
40 26.147 0.913 131 1.449 2.882
41 25.114 0.94 132 1.4141 2.891
42 24.128 0.967 133 1.3803 2.9
43 23.186 0.994 134 1.3474 2.908
44 22.286 1.022 135 1.3155 2.916
45 21.425 1.05 136 1.2846 2.924
46 20.601 1.078 137 1.2545 2.932
47 19.814 1.107 138 1.2233 2.94
48 19.061 1.136 139 1.1969 2.947
49 18.34 1.164 140 1.1694 2.955
50 17.651 1.193 141 1.1476 2.96
51 16.99 1.223 142 1.1166 2.969
52 16.358 1.252 143 1.0913 2.975
53 15.753 1.281 144 1.0667 2.982
54 15.173 1.311 145 1.0429 2.988
55 14.618 1.34 146 1.0197 2.995
56 14.085 1.37 147 0.9971 3.001
57 13.575 1.4 148 0.9752 3.007
58 13.086 1.429 149 0.9538 3.013
59 12.617 1.459 150 0.9331 3.018
60 12.368 1.475 - - -
116
2 Temperature/Pressure List of Refrigerant
R410A
Temperature Pressure Temperature Pressure Temperature Pressure
℃ kPa ℃ kPa ℃ kPa
-30 275 0 803 30 1880
-29 286 1 823 31 1910
-28 298 2 851 32 1960
-27 311 3 879 33 2030
-26 324 4 903 34 2080
-25 334 5 937 35 2130
-24 348 6 962 36 2180
-23 363 7 994 37 2240
-22 375 8 1020 38 2290
-21 391 9 1050 39 2350
-20 404 10 1090 40 2410
-19 424 11 1110 41 2460
-18 435 12 1150 42 2510
-17 453 13 1180 43 2580
-16 468 14 1220 44 2650
-15 483 15 1250 45 2710
-14 504 16 1280 46 2770
-13 520 17 1320 47 2840
-12 538 18 1350 48 2910
-11 556 19 1400 49 2980
-10 579 20 1440 50 3050
-9 598 21 1470 51 3100
-8 618 22 1520 52 3180
-7 639 23 1560 53 3250
-6 660 24 1600 54 3320
-5 682 25 1640 55 3400
-4 705 26 1680 56 3480
-3 728 27 1730 57 3540
-2 752 28 1780 58 3630
-1 777 29 1820 59 3720
3 Operation Tools
The following tools will be used: 1) Liquid-level gauge; 2) Screwdriver; 3) Electric driven rotary hammer; 4)
Drill; 5) Pipe expander; 6) Torque wrench; 7) Open-end wrench; 8) Pipe cutter; 9) Leak detector; 10) Vacuum
pump; 11) Pressure gauge; 12) Universal meter; 13) Hexagon wrench; 14) Tapeline.
117
I.!
COIVIFORT IVIADE SIIVIPLE