SOP for Preventive Maintenance of Diesel Generator
SOP for Preventive Maintenance of Diesel Generator
OBJECTIVE:
To lay down the Procedure for Preventive Maintenance of
Diesel Generator Set.
SCOPE:
This SOP is applicable to Preventive Maintenance of Diesel Generator Set
installed at Utility Block .
RESPONSIBILITY:
Technician/ Officer engineering shall be responsible for proper execution of
Preventive Maintenance of Diesel Generator as per SOP.
Engineering – Head shall be responsible for reviewing the SOP and for
ensuring proper execution of preventive maintenance of Preventive
Maintenance of Diesel Generator.
ACCOUNTABILITY:
Engineering – Head shall be accountable for proper implementation of the
SOP.
DEFINITIONS:
Nil
PROCEDURE:
Preventive Maintenance of Diesel Generator shall be executed as per the SOP
No.: SOP/EN/XXXYYY – Execution of Preventive Maintenance.
Ensure that the spare parts shall be available at the time of preventive
maintenance
“A” Daily Operational Checks
Fill the daily operational checks of DG report for following points as per Format
no. SOP/EN/XXXYYY
Daily warm up start for 5 Minutes.
Check the engine oil level.
Check fuel supply.
Drain sediment from fuel tanks.
Check and clean the water separator.
Check air Filter.
Check coolant level.
Check voltage of batteries.
Check for any leakage in DG set.
Check engine belts and in line engine water pump belts for belt tension.
“B” 300 Hrs Preventive Maintenance Checks in Preventive Maintenance
of Diesel Generator
Lubricating oil systems; if the lubricating oil is drained from the oil pan to
make an engine repair, top up with new fresh oil, never used oil after has been
drained from oil pan.
Analyze the oil for the contamination, if required add the fresh oil.
Change engine oil and lubricating oil if required change filter elements.
Record oil pressure.
Clean and change crankcase breather
Check coolant inhibitor, add coolant concentrate if required.
Check the working of governor in DG set.
Change fuel filter element.
Clean fuel tank breather.
Check air piping linkage.
Check safety control and alarms.
Equipment ID Frequency
Analyze the oil for the contamination, if required add the fresh oil.
Change engine oil and lubricating oil if required change filter elements.
Record oil pressure.
Check the sound level test accordingly ISO 8528 Part 10 for each year.
Repeat the Daily, Weekly, Half yearly and Yearly Preventive maintenance checks.
Replace the coolant after 6000 Hrs or after two years which comes earlier.
Done By
Signature
Checked By: