(Practical)RTU Hardware Configuratio
(Practical)RTU Hardware Configuratio
here
Insert
image
Configuration
RTU Hardware &
RTU 560 Hardware Installed at Pantai Remis
23 ET 24 – I/O Rack
23 ET23 – I/O Rack
560 PSU01 – Power supply unit
23BE21 – Binary Input Card
23AE21 – Analog Input Card
23BA20 – Binary Output Card
23BA30 – Interposing Module
560BCU03 – Bus communication unit
560CMU05 – CPU unit
560RTC01 – GPS receiver unit
23BA22 – Binary output monitoring unit
© Copyright year ABB - 2 -
RTU 560 Hardware
CMU05
I/O modules
IED Sub-RTU
I/O modules
© Copyright year ABB - 7 -
I/O modules
RTU560 System software package
The structure
© Copyright year ABB - 9 -
RTU 560 Component : Sub rack 23ET23/24
CMU05
© Copyright year ABB - 10 -
process signal
RTU 560 Component : voltage monitoring
23ET23 rack
K01 Relay
23ET24 rack
© Copyright year ABB - 14 -
RTU 560 Component : voltage monitoring
© Copyright year ABB - 15 -
RTU 560 Component : Addressing 23ET23
23ET24
RJ45 type
.
RTU 560 Component : Serial peripheral bus
23ET23
RJ45 DB9
2 2
3 3
7 7
© Copyright year ABB - 22 -
RTU 560 Component : Serial peripheral bus
Electrical
connection for
serial peripheral
bus (RS 485 std)
Use 3 wire, direct
tx, rx and ground.
(shielded cable)
© Copyright year ABB - 23 -
RTU 560 Component : Serial peripheral bus
Other possibilities !
For a longer distance linked or
grounding situation very bad
electrical serial peripheral bus
could be replaced by optical fibre
connection.
Option 1 :- serial peripheral bus in
star configuration.
© Copyright year ABB - 24 -
RTU 560 Component : Serial peripheral bus
560 BCU03
RTU 560 : 24VDC Wetting
Error indicator.
LED signal
Optocoupler chip.
ON – input 24..60 Vdc
OFF – input 0 Vdc
© Copyright year ABB - 31 -
EAP – input/output
processor reads the input
register and process each
input according to the
loaded process signal type
and parameter.
© Copyright year ABB - 32 -
RTU 560 Component: Binary input board
Error indicator.
© Copyright year ABB - 36 -
Configuration of line
frequency.
It scan cycle for per board
hence all channel will be
scan with similar
frequency.
© Copyright year ABB - 39 -
RTU 560 Component: Analogue input board
EAP – input/output
processor control A/D
converter and read
digitized analog
measured value.
Configuration
parameters are loaded
by CMU to RAM.
© Copyright year ABB - 40 -
RTU 560 Component: Binary input board
Command output
monitoring provided by
23BA22 board (1 out of n
check)
Two type of object
command supported
1 or 2 pole output without (1
out of n check)
1.5 or 2 pole output with (1
out of n check)
© Copyright year ABB - 43 -
No hardware setting
required Driver
EAP – input/output
processor activate any
output forced by CMU
by a command output Monitoring of
command output
request.
EAP provide time Voltage
monitoring
to RAM.
© Copyright year ABB - 45 -
RTU 560 Component: Binary Output board
Error indicator.
© Copyright year ABB - 48 -
EAP – input/output
processor controls 2 digital
to analog converter.
DAC resolution is 11 bit +
sign
Output value remain until
new value receive.
Configuration data and
processing parameter
loaded to RAM via peripheral
bus from CMU.
© Copyright year ABB - 49 -
RTU 560 Component: Analog Output board
© Copyright year ABB - 50 -
RTU 560 Component: Analog output board
Antenna mounting.
BNC front plug for coax cable
(50 ohm, RG 58, max 200 m)
RJ 45 connector provide a RS
232 interface which offering 33
byte of ASCII coded time
message every minute.
It also provide configuration of
the clock or for monitoring the
actualization of the system
software.
© Copyright year ABB - 56 -
Pin arrangement of RJ 45
RTU 560 Component: 560 RTC 01
Connection diagram
RTU 560 Component: 23PK27
2 microprocessor
MPU 32 bit main processing
unit
SLC 8 bit serial line
controller
Removable non-volatile
memory card provide
storage for configuration
files and power fail save
files.
© Copyright year ABB - 61 -
RTU 560 Component: 560ETH02/03
CPA/B interface in RS232 mode.
CMU05 has
2 Ethernet port E1/E2
4 Serial CPA/CPB/CP1/CP2
configurable for RS232/
RS485.
© Copyright year ABB - 62 -
RTU 560 Component: 560ETH02/03
CPA/B interface in RS232 mode.
CPA/B Interface can be
configured as RS 485 or
RS 232.
Baudrate <= 19200 bit/s
Software selectable for
type and baudrate.
CPA/B interface in RS485 mode.
Both interfaces are
working with similar
protocol.
Serial peripheral bus is
directly connected to CPB.
© Copyright year ABB - 63 -
RTU 560 Component: 560ETH02/03
CPA/B interface in RS232 mode.
For peripheral bus
connection CPB must be
configured with segment
address = 2
Software configuration
© Copyright year ABB - 64 -
RTU 560 Component: 560ETH02/03
CPA/B interface in RS232 mode.
By default X1 jumper is
always at position 1-2
If the jumper is at position
2-3 then it will read IP from
the configuration set
The default IP is
192.168.0.1
The IP can be changed
using RTUtil
© Copyright year ABB - 65 -
RTU 560 Component: Power supply unit 560PSU01
560PSU01 generate 2
type of supply voltage 5 V
dc and 24 V dc.
2 type of input supply
24 to 60 V dc (-20% -
+15%)
110 to 220 V dc ( -20% -
+15%)