Rmb
Rmb
II
Precautions
Changing DIP switch and jumper settings, and all wiring should
be done by an experienced technician. The controller and wiring
should be installed in accordance with national and local
electrical codes. To avoid serious personal injury and damage to
equipment, follow all warnings and cautions provided in the
manual supplied with the mainframe.
III
If a controller shows signs of having been damaged during
Caution shipping, do not power up or install the controller. Save all
packing materials and report any damage to the carrier
immediately.
IV
Table of Contents
Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Features and Benefits of RMB Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 What Happens When You Power Up the Controller . . . . . . . . . . . . . . . . . . . . . . 6
2.3 Operation Basics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4 Manual Tuning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3. Setting Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.1 Factory Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4. Setup and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.1 Prepare the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.2 Install the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.3 Apply Power to the Mainframe and Controller . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.4 Adjust the Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.5 Wait for the Controller to Tune Itself . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5. Error Messages and Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2 Summary of Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.3 Ground Fault in Controller Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.4 Loop Break in Sensor Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.5 Open Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.6 Reversed Thermocouple Leads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.7 Heater Current Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.8 Autotune Errors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6. Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.2 Cleaning the Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.3 Replacing the Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.4 Unit Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
i
Series RMB Hot Runner Controller Instruction Manual
ii
Series RMB Hot Runner Controller Instruction Manual
1. Introduction
1.1 About This Manual
This manual contains all the information An orange LED on the front panel
needed to set up and operate the Series indicates heater on, and a red LED
RMB Hot Runner controllers. indicates high or low process alarm.
Instructions for wiring, installing, and Green LEDs signal current mode and
troubleshooting the controllers are in the boost action.
manual supplied with the mainframe. Front panel keys make it easy to change
mode, change setpoint (normal mode),
1.2 Features and Benefits output % (manual mode), and to activate
of RMB Controllers the boost. You can also use the front
panel to change tuning parameter values.
1.2.1 Introduction
RMB controllers with the optional 30 amp
The Series RMB Hot Runner controllers output TRIAC are wider than the 15 amp
offer many advanced features designed units (to accommodate the heat sink), but
to increase productivity and ensure fast, the user interface is the same.
accurate, and repeatable mode
temperature control. Each unit is Detailed instructions for using the front
designed to control one temperature panel are in Section 2.
zone based on input from a J or K
thermocouple. The controllers are set at
the factory for J thermocouple input. To
use a K thermocouple, change a switch-
setting; see 3.4.
1.2.2 Convenient User Interface
RMB controllers are equipped with a bright
two-line LED display that is easy to read
over wide viewing angles.
The process value is displayed on the top
line (three digits).
The lower line (four digits) displays your
choice of setpoint (normal mode), output
percentage (normal and manual), and
output current to the closest tenth of an
amp (normal and manual).
1
Series RMB Hot Runner Controller Instruction Manual
2
Series RMB Hot Runner Controller Instruction Manual
3
Series RMB Hot Runner Controller Instruction Manual
1.3 Specifications
1.3.1 Operating Limits
Ambient Temperature 32°F to 131°F (0°C to 55°C)
Relative Humidity Tolerance 10 to 95% Non-Condensing
Shipping Temperature –40°F to 158°F (–40°C to 70°C)
Power Requirements 115 to 240 Vac 50 or 60 Hz nominal, CE compliant
1.3.2 Performance
Accuracy ± 0.3% of span
Setpoint Resolution 1 degree Fahrenheit
Repeatability ± 0.1% of span
Temperature Stability ± 0.5% of full scale over the ambient range of 32°F to
131°F (0°C to 55°C)
Thermocouple Cold-End Tracking automatic, better than 0.02°F per °F
(0.01°C per °C)
Noise Rejection Common Mode > 100 dB, Series Mode > 70 dB
Process Sampling Rate 10 Hz (100 ms)
1.3.4 Inputs
Thermocouple J or K
Supported Sensor Range 32 to 999°F (0 to 537°C)
1.3.5 Output
TRIAC, 15 amps at 120/240 Vac (30 amp optional), driven by optically isolated
interface circuit. Protected with a pair of 15 amp (or one 30 amp) field-
replaceable fuses. Instructions for replacing the fuses are in 6.3. Replacement
fuses must be Type F fast-acting 250 Vac fuses rated at 15 amps (or 30 amps).
A 15 amp (120/240 Vac) relay (30 amp optional) interrupts power to the heater if
the controller detects shorting of the TRIAC output or other system failures.
A ground fault detection circuit is also standard.
4
Series RMB Hot Runner Controller Instruction Manual
2. Operation
2.1 Front Panel
RMB controllers with the optional 30 amp output TRIAC are wider than the 15 amp units
(to accommodate the heat sink), but the user interface is the same.
5
Series RMB Hot Runner Controller Instruction Manual
1
It is a good idea to make a note of the
firmware version number. If you phone for
technical support, you will be asked for this
version information, as well as for the
complete model number of the controller in
question.
6
Series RMB Hot Runner Controller Instruction Manual
7
Series RMB Hot Runner Controller Instruction Manual
8
Series RMB Hot Runner Controller Instruction Manual
9
Series RMB Hot Runner Controller Instruction Manual
2. Inspect the controller for damage. When the controller is powered up, all
segments of the display and all LEDs light
3. Make sure the power switch on the briefly, and then the firmware version
front of the controller is set to off (O). number is displayed.
If a controller shows signs of having been
damaged during shipping, do not install or 4.4 Adjust the Setpoint
power up the controller. Save all packing When the controller is powered up, it will
materials and report any damage to the automatically do a CompuStep soft start
carrier immediately. for heater bake out if the process value is
4.2 Install the Controller below 200°F. (PV is on the top line of the
display. SP is on the lower line.) During
This guide assumes that the mainframe the soft start the NORMAL LED flashes.
has already been wired as described in
During the soft start (which lasts five
the installation manual supplied with the
minutes or until the PV is 200°F),
mainframe.
adjust the setpoint to a value that is
1. Make sure the plunger in center of representative of the setpoint you expect
the locking pin is pulled out (or to use when the controller is in service. 2
loosen the locking screw). ▼
To adjust the setpoint press the or
2. With the controller and mainframe ▼ key.
power switches set to off (O), align
the RMB controller’s printed circuit 4.5 Wait for the Controller
board with the guide channels in a to Tune Itself
slot in the Hot Runner mainframe.
New RMB controllers are set to do a soft
3. Slide the controller into the main start every time they are powered up (if
frame until the RMB connectors are the PV is less than 200°F), and then to do
firmly seated in the backplane of an Autotune operation each time the
the mainframe. controller is powered up until a successful
4. Lock the controller into the frame by Autotune is completed.
pressing in the plunger on the locking If you are setting up a new process,
pin (or tighten the locking screw). Autotune all the RMB controllers in the
process simultaneously, so that interac-
4.3 Apply Power to the
tions between zones during tuning
Mainframe and Controller
When the controller is powered up, the 2
If the PV is greater than 200°F, then the
output may be activated. controller will skip the soft start, and will
Autotune as soon as you power up the con-
1. Before powering up the controller, troller the first time. However, the tuning will
consider the effects on your process not be valid, because you have not yet
entered the appropriate setpoint for your
if the output is activated. Take site- process. Press MODE once to interrupt the
specific precautions. Autotune. With the controller in normal
mode (NORMAL LED lit), adjust the set-
2. Turn on the power to the mainframe. point, and then cycle power to start
Autotune again with a valid setpoint.
10
Series RMB Hot Runner Controller Instruction Manual
parallel the interactions expected while the The display reverts to the normal mode
controllers are in use. operating display: PV on top line, SP on
lower line. The proportional band and rate
If you need to stop the Autotune, press the
values calculated by the controller during
MODE key until the controller is in
the Autotune have been saved. (The
standby. (When you are ready to
integral (reset) action for PID control is
Autotune, cycle the power to the
always set to five times the rate value in
controller.)
an RMB controller.) Autotune is disabled.
If you are installing a single replacement (If the Autotune is not successful, output
controller, let the Autotune proceed without goes to 0%, and you will see an error
interruption. During Autotune, the process code; see 5.8.)
value alternates with tun.
RMB controllers do not require calibration.
At the conclusion of a successful
The controller is ready to use.
Autotune, the flashing tun disappears.
11
Series RMB Hot Runner Controller Instruction Manual
12
Series RMB Hot Runner Controller Instruction Manual
5.4 Loop Break in Sensor • the controller output goes to 0%, and
13
Series RMB Hot Runner Controller Instruction Manual
Autotune Errors
Error Code Description
Er3 Setpoint is higher than the process value. Look at the setpoint.
If it is realistic for your process, then check the thermocouple
leads; maybe they are reversed.
Er5 There is not enough difference between initial PV and the
setpoint. For Autotune to work, the difference must be at least
9°F (5°C).
Er8 The startup curve (change in PV) was not acceptable to the
Autotune algorithm. This could be caused by a process upset
that occurred during tuning. Try Autotuning again when the
process is stable. If the error recurs, your process is not
suitable for Autotuning. Use manual tuning; see 2.4.
Er9 The Autotuning timed out, because the process was
unresponsive (or extremely slow). Your process is not suitable
for Autotuning. Use manual tuning; see 2.4.
14
Series RMB Hot Runner Controller Instruction Manual
6. Maintenance
6.1 Introduction
This section contains instructions for cleaning the front panel of the controller
and instructions for replacing the fuses.
Except for fuses, the controller contains no user-serviceable parts.
15
Series RMB Hot Runner Controller Instruction Manual
3. Use a cotton cloth to gently and 4. Use the handle on the front of the
sparingly apply isopropyl alcohol to controller to pull it out of the
the front panel of the controller. Do mainframe.
not use cleaning solutions or other
5. Replace the fuses.
solvents. Use of anything other than
isopropyl alcohol can result in 6. Re-install the controller and return it
damage to the controller. to service.
Do not allow alcohol to enter the 6.4 Unit Repairs
power switch on the controller’s front
panel. It is recommended that units requiring
service be returned to an authorized
4. Allow the controller to air-dry service center. Before a controller is
thoroughly. Do not use a heater or returned for service, please consult the
compressed air to dry the unit. service center nearest you. In many
5. Inspect all surfaces to make sure that cases, the problem can be cleared up over
they are completely dry. the telephone. When the unit needs to be
returned, the service center will ask for a
6. When the controller is completely dry,
detailed explanation of problems
re-install it and return it to service.
encountered and a Purchase Order to
6.3 Replacing the Fuses cover any charge. This information should
also be put in the box with the unit. This
Each RMB controller with 15 amp output should expedite return of the unit to you.
contains two fuses, located on the main
printed circuit board. An RMB with 30
amp output has one fuse on the main cir-
cuit board.
To replace the fuses in an RMB
controller:
1. Make sure that you have the correct
replacement fuse.
• For RMB controller with 15 amp
output – Type F fast-acting 250
Vac fuses rated at 15 amps.
Suitable fuses are p/n
210B001U01 and Littlefuse Inc.
p/n 314015.
• For RMB controller with 30 amp
output – Type F fast-acting 250
Vac fuse rated at 30 amps.
Suitable fuses are p/n
210A009U01 and Cooper
Bussmann FWX-30A14FB.
2. Put the power switch of the controller
in the “OFF” position.
3. Pull out the plunger in the locking pin
(or loosen the locking screw).
16
Series RMB Hot Runner Controller Instruction Manual
7.2 FAQs
7.2.1 How do I change from a J to a K thermocouple?
Every Series RMB controller is shipped ready to accept input from a J thermo
couple. If you plan to use a K thermocouple for input, you must set
SW2-switch 2 to ON as described in Section 3. Read the safety warnings at
the front of this manual before changing switch settings.
7.2.4 I turned on the power; why doesn’t the controller light up?
If SafeChange is enabled, but the mainframe does not support SafeChange, the
controller will not work. Instructions for checking to see if a mainframe supports
SafeChange are in 3.2.
17
Series RMB Hot Runner Controller Instruction Manual
Index
A G
alarms, 2, 5, 6 gFI error message, 13
At.OP parameter, 6, 7, 11 ground fault detection, 3, 13
automatic mode. See normal mode
Autotune, 2, 6, 7, 10 H
Autotune errors, 12, 14 HEAT LED, 5, 6
Autotune Operation parameter, 6, 7, 11 heater conversion error, 12
heater current display, 7
B heater current monitoring, 3
bad Htr error message, 14 HT.rd Err message, 12
boost, 5, 7
bumpless transfer, 6
I
input failure, 13
C input switch setting, 3, 17
integral action, 2, 7, 11
calibration, 11, 17 interrupt (unexpected or invalid), 12
calibration value corrupted error, 12
CE EMC compliance, II
changing setpoint or output, 7
J
checksum error, 11 J thermocouple, switch setting for, 3, 10,
cleaning controllers, 15 17
CompuStep, 2, 3 jumper setting, 9
current displayed, 3, 7
current monitoring, 3, 14 K
K thermocouple, switch setting for, 3, 10,
D 17
18
Series RMB Hot Runner Controller Instruction Manual
N S
NORMAL LED, 5 SafeChange feature, 9, 17
normal mode, 2 safety information, I, 15
sensor error, 3
O sensor type, switch setting for, 3, 17
setpoint, 5, 7
open sensor, 13 soft start, 2, 3
Out Shrt error message, 14 span calibration, 17
output bad, 3, 14 STANDBY LED, 5
output displayed, 7 switch settings, 3, 9, 10, 17
output for control, 2, 6
output in manual mode, 7
output state on power up, 6
T
output TRIAC short error, 3, 14 tC oPn error message, 13
tC rEv error message, 13
P technical support, 17
TRIAC short error message, 3, 14
part number for fuses, 16
troubleshooting, 11, 17
part number for SafeChange clip, 10
tuning, 7, 10
Pid menu, 2, 6, 7, 11, 12
powering up controller, 6
process value display, 5, 6
U
proportional band, 2, 7, 11 unit of measure switch setting, 9, 10
user interface, 5
R user-serviceable parts, 15
RAM error, 11
rate, 2, 7, 11
Z
replacing fuses, 16 zero calibration, 17
reset, 7, 11
reversed sensor, 13
19
Series RMB Hot Runner Controller Instruction Manual
20
Series RMB Hot Runner Controller Instruction Manual
Notes
21
Plastic Process Equipment, Inc.
8303 Corporate Park Drive
Macedonia, OH 44056
1.800.321.0562 • 216.367.7000
FAX: 216.367.7022 • www.ppe.com