6000-in100_-en-p
6000-in100_-en-p
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential
Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory
requirements for safe work practices and for Personal Protective Equipment (PPE).
Identifies information that is useful and can help to make a process easier to do or easier to understand.
Rockwell Automation recognizes that some of the terms that are currently used in our industry and in this publication are not in
alignment with the movement toward inclusive language in technology. We are proactively collaborating with industry peers to
find alternatives to such terms and making changes to our products and content. Please excuse the use of such terms in our
content while we implement these changes.
2 Rockwell Automation Publication 6000-IN100D-EN-P - July 2022
Table of Contents
Preface
About This Publication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Download Firmware, AOP, EDS, and Other Files . . . . . . . . . . . . . . . . . . . . 5
Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
What Is Not in this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Required Supplemental Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
General Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Summary of Changes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Commissioning Support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Contractor Scope of Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Environmental Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Chapter 1
Drive Mechanical Installation Mechanical Installation Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Connect Shipping Splits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Affix Cabinets to Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Install Seismic Rated Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Install Main Cooling Fans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Install Power Modules (if applicable) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
External Ducting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Air Conditioning Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Chapter 2
Drive Electrical Installation Safety and Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Electrical Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Grounding System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Power Cable Insulation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Power Cable Design Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Motor Cable Sizing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Control Signal Wiring Design Considerations . . . . . . . . . . . . . . . . . . . . . 43
Electrical Installation Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Connect the System Ground Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Insulation Resistance (IR) Test of Power Cables . . . . . . . . . . . . . . . . . . . . 46
Connect Incoming Line and Outgoing Motor Power Cables . . . . . . . . . 46
Connect Control Power Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Connect External Control Signal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Connect Electrical Safety Interlock Circuit to Input Circuit Breaker . 54
Chapter 3
Drive Electrical Interconnection Electrical Interconnection Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Power Cable Interconnection Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Connect Isolation Transformer Secondary Power Cables . . . . . . . . . . . 59
Connect Motor and Voltage Sensing Board Cables . . . . . . . . . . . . . . . . . 60
Connect LV Control and Fan Wiring Bundles . . . . . . . . . . . . . . . . . . . . . . 62
Connect Ground Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Complete the Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Appendix A
Pre-Commissioning Pre-Commissioning Responsibilities. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Pre-Commissioning Checklist. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Appendix B
Torque Requirements Torque Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Appendix C
General Wire Categories General Wire Categories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Appendix D
Power Cabling and Control Schematic Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Signal Wiring Details Standard Input/Output Connection Points . . . . . . . . . . . . . . . . . . . . . . . . 74
Appendix E
Line and Load Cable Sizes Cable Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
About This Publication This manual provides procedural information for installing PowerFlex® 6000T
medium voltage drives.
Rockwell Automation recognizes that some of the terms that are currently
used in our industry and in this publication are not in alignment with the
movement toward inclusive language in technology. We are proactively
collaborating with industry peers to find alternatives to such terms and
making changes to our products and content. Please excuse the use of such
terms in our content while we implement these changes.
Download Firmware, AOP, Download firmware, associated files (such as AOP, EDS, and DTM), and access
EDS, and Other Files product release notes from the Product Compatibility and Download Center at
rok.auto/pcdc.
Who Should Use This This manual is intended for use by professional riggers, general contractors,
Manual electrical contractors, or plant operations personnel familiar with moving and
siting heavy equipment. Specific experience with solid-state variable speed
drive equipment is NOT required for this part of the installation process, but is
mandatory for subsequent processes.
What Is Not in this Manual This manual provides information specific for installing a PowerFlex 6000T
drive. It excludes project-specific, or drive-specific topics such as:
• Dimensional Drawings (DD) and Electrical Drawings (ED) that are
generated for each customer’s order.
• Spare parts lists compiled for each customer’s order.
• Drive-specific technical specifications.
Required Supplemental This manual includes generic information about the drive cabinet layout
Information orientation and generic electrical connection information.
General Precautions
ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive
parts and assemblies. Static control precautions are required when
installing, testing, servicing, or repairing this assembly. Component damage
may result if ESD control procedures are not followed. If you are not familiar
with static control procedures, reference Allen-Bradley publication 8000-
4.5.2, “Guarding Against Electrostatic Damage” or any other applicable ESD
protection handbook.
Summary of Changes This publication contains the following new or updated information. This list
includes substantive updates only and is not intended to reflect all changes.
Topic Page
Typical floor drawing A-frame (2.4…4.16 kV, UL and IEC)
• Added 70 A Non-Seismic/Seismic 15
• Added 140 A Non-Seismic/Seismic 16
• Updated 215 A Non-Seismic/Seismic 17
Updated drive ratings for A-frame drives (IEC) 23, 30, 31, 48, 52
Updated table Line and Load Cable Sizes for A-frame Drives (IEC) 77
Additional Resources These documents contain additional information concerning related products
from Rockwell Automation.
Resource Description
PowerFlex 6000T Drives Shipping and Handling Manual, Provides instructions for shipping and handling PowerFlex6000T drives and related
publication 6000-PC100 equipment.
Provides instructions for daily recurring drive usage, HMI, and maintenance tasks for the
PowerFlex 6000T Drives Hardware Service Manual, publication 6000-TG100 product’s end user.
Provides detailed information on drive features, programming parameters, and
PowerFlex 6000T Drives Programming Manual, publication 6000-PM100 troubleshooting faults and alarms.
Describes how to configure and use EtherNet/IP devices to communicate on the EtherNet/IP
EtherNet/IP Network Devices User Manual, ENET-UM006 network.
Ethernet Reference Manual, ENET-RM002 Describes basic Ethernet concepts, infrastructure components, and infrastructure features.
Provides guidance on how to conduct security assessments, implement Rockwell
System Security Design Guidelines Reference Manual, SECURE-RM001 Automation products in a secure system, harden the control system, manage user access,
and dispose of equipment.
Industrial Components Preventive Maintenance, Enclosures, and Contact Provides a quick reference tool for Allen-Bradley industrial automation controls and
Ratings Specifications, publication IC-TD002 assemblies.
Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides
Safety Guidelines for the Application, Installation, and Maintenance of general guidelines for the application, installation, and maintenance of solid-state control in
Solid-state Control, publication SGI-1.1 the form of individual devices or packaged assemblies incorporating solid-state
components.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, rok.auto/certifications. Provides declarations of conformity, certificates, and other certification details.
Contractor Scope of Work Typical scope of work by the freight company, third-party contractor and/or
customer (based on ex-works Incoterms)(a):
• Load equipment on truck at a Rockwell Automation manufacturing
facility and transport equipment to site
• Offload equipment from truck on-site
• Perform initial inspection(b)
• Move equipment to the final installation location
• Position the cabinet sections together as shown in Dimensional Drawing
and level the cabinet lineup
• Mechanically join cabinets together
• Affix the cabinets to the floor
• Install assemblies shipped loose (fan assemblies).
(a) All or part of these activities could be provided by Rockwell Automation or its
representatives, based on contract Incoterms and negotiated scope of supply/services
agreement. Contact the local Rockwell Automation office for further information.
(b) Customer should lead the initial inspection process.
Rockwell Automation Publication 6000-IN100D-EN-P - July 2022 7
Preface
• Install external ductwork to exhaust heated air from control room (if
required)
• Install power and control cabling and terminate cable connections to
drive system:
- Connect system ground cable
- Insulation Resistance (IR) testing of incoming line and outgoing
motor power cables
- Connect incoming line and outgoing motor power cables
- Connect control power wiring
- Connect all external customer required control signal wiring
- Connect electrical safety interlock control signal wiring circuit to
input circuit breaker
• Connecting the power cables and control wiring between cabinets that
are shipped separately(a)
• Complete Pre-commissioning Checklist
Environmental Conditions • Elevation above sea level must be less than 1000 m (3250 ft)(b).
• Ambient air temperature must be between 0…40 °C (32…104 °F)(c).
• Relative humidity must be less than 95%, noncondensing.
• Operation Vibration limited to 3M11 per IEC 60721-3-3.
• G2 rating with 60% humidity – Storage, Transport, and Operation – as
per ISA 71.04-2013.
• The drive must be installed indoors; there must be no dripping water or
other fluids in the room.
• Cooling air must be clean without significant concentrations of sand,
corrosive or conductive dust, or explosive gas. The drive must be installed
in a Pollution Degree 2 environment as per IEC 61800-5.
• Free from significant vibration.
• The drive must be anchored on a level floor. See the dimension drawing
for the anchor point sizes and locations.
For the equipment to operate in conditions other than those specified, consult
the local Rockwell Automation Sales Office.
(a) Interconnection of power cables and low voltage control wiring bundles, between separately
shipped cabinets, can be done by the contractor or Rockwell Automation. The
commissioning quote from Rockwell Automation reflects this and will contain two options:
a) the base quote, reflecting the power cable and control wiring interconnection work being done by the contractor
b) the optional quote adder, reflecting the additional time and cost for Rockwell Automation to perform the power cable and
control wiring interconnection work immediately before the commissioning process.
(b) Options are available for operation up to 5000 m.a.s.l. However, these must be stated at the
time of order and cannot be retrofitted in the field.
(c) Options are available for ambient temperatures up to 50 ºC. However, these must be stated
at the time of order and cannot be retrofitted in the field.
8 Rockwell Automation Publication 6000-IN100D-EN-P - July 2022
Chapter 1
Mechanical Installation The cabinets must be arranged as shown in the Dimensional Drawing (DD).
Summary Topic Page
Connect Shipping Splits 9
Affix Cabinets to Floor 13
Install Seismic Rated Enclosures 19
Install Main Cooling Fans 27
Install Power Modules (if applicable) 31
External Ducting 35
Follow all applicable guidelines for siting the components before continuing
with these installation instructions.
There may be some variation in the process depending on the type and number
of drive components in your particular installation.
The standard A-frame for PowerFlex 6000T drives comes fully assembled and
does not require any shipping splits. However, if a DV/DT filter is included
with the drive then there is one shipping split, and the drive and filter must be
connected as follows:
1. Remove the M16x16 countersunk screw that secures the LV covers and
grounding cover at the right side of the main drive, and the left side of
the filer cabinet. Then remove the covers.
2. Arrange the sections as described in the Dimensional Drawings and
move the sections together.
3. Align the cabinet side sheets together at the holes for the hardware.
Figure 1 - Align the Cabinets, A-frame
A B
Front Front
Side View
4. Secure the cabinets together with two L-shaped brackets and four M12
hexagon socket bolts, D12 washers, and D12 lock washers at the front and
rear side.
5. Verify that the front of the SIL channels at A and B (Figure 1) are aligned.
LV cover
M16x16 countersunk
head screw (x4)
Grounding cover
M16x16 countersunk
head screw (x2)
The B-frame for PowerFlex 6000T drives are shipped in two sections, the
Isolation Transformer Cabinet and Power Module/LV Control Cabinet. These
two cabinets must be connected after located in its final position. The cabinets
are connected together in 8 or 10 places (depending on the drive rating), half
along the front edge of the cabinet and half along the rear edge of the cabinet.
Access to the interior of the cabinet is required to make these connections.
Access for the front connections requires only opening the doors. Access for
the rear connections requires removing the back plates of the cabinet.
1. Arrange the sections as directed in the Dimensional Drawings and move
the sections together.
2. Align the cabinet side sheets together at the holes for the hardware
(see Figure 3).
Figure 3 - Align the Cabinets, B-frame (6 kV shown)
❶ Front Wireway
❷
❷ U Phase Motor Cable
❸ V Phase Motor Cable
❹ W Phase Motor Cable ❼
❺ Ground Bus Connection
❻ Voltage Sensing Board Cables
Isolation Transformer Secondary
❼
Cables(1)(2) ❻
❸
Front Front
Side View
Open the doors to access front edge joining holes (four or five places).
Secure with M6
hardware (8 places)
Affix Cabinets to Floor Typical floor drawings show minimum clearance distance, conduit openings,
and mounting holes for anchor bolts, as shown in Figure 5. See customer-
specific dimensional drawing for outgoing motor and incoming line cable
openings.
Input cable
Control signal
Secure the cabinet to the channel steel base using M12 bolt (recommended),
lock washer, two flat washers, and a nut.
Flat washer
Optional: The cabinet can also be welded to the steel base once it is securely
bolted, if desired.
Each weld location should be 100 mm (3.9 in.) for every 1000 mm (39.4 in.). See
Mounting Requirements in the PowerFlex 6000T Drives Shipping and
Handling Manual, publication 6000-PC100 for further information on the
steel base and desired trench and mounting customer-specifications.
70 A, Non-seismic
70 A, Seismic
Figure 8 - Typical Floor Drawing, A-frame, 140 A (2.4…4.16 kV, UL and IEC)
Dimensions are in mm.
140 A, Non-seismic
140 A, Seismic
Figure 9 - Typical Floor Drawing, A-frame, 215 A (2.4…4.16 kV, UL and IEC)
215 A, Non-seismic
215 A, Seismic
Secure the cabinet to the channel steel base using M12 bolt (recommended),
lock washer, two flat washers, and a nut.
70 A, Non-seismic/Seismic
140 A, Non-seismic/Seismic
215 A, Non-seismic/Seismic
Secure the cabinet to the channel steel base using M16 bolt (recommended),
lock washer, two flat washers, and a nut.
Install Seismic Rated This section describes how to install the drive for seismic conditions.
Enclosures Figure 11 - Guidance for Seismic Installation
Condition 1 Condition 2
Anchors braced at front Anchors braced at front
and rear side and wall-mounted angle
6. Remove the right side plate, put the secondary cables close to Tx winding,
and disassemble three horizontal baffles.
7. Remove the seismic cover at the front and back side of the JC, and the
right side of the drive.
8. Drill anchor holes at the left-hand side of the cabinet.
9. Drill anchor holes at the right-hand side of the cabinet, then install the
anchors.
Step 10
Step 4 Step 5
Step 6
Step 4 Step 5
Step 6
For condition 2 seismic installation, if there is no rear access available, the top
of the drive can be mounted to the wall rather than mounted to the floor at the
back of the cabinet. If there is a fan redundancy condition for frame 1 and
frame 2, then wall bracket B is not needed.
Figure 12 - Condition 2 Seismic Installation, A-frame Drives (2.4…4.16 kV, UL and IEC)
Wall bracket B Wall bracket A
Wall bracket B
M12xL35
Based on bracket thickness
of 11 mm (0.43 in.)
Frame 1
Wall bracket A
Frame 2
Frame 3
For condition 1 seismic installation, install the cabinet using the anchoring
locations that are shown in Figure 12.
3. Install a seismic end bracket to the Junction cabinet with M16 hardware.
Barrier bracket
Grounding busbar Anchor cover
Wire duct
Left cabinet Step 1 Step 2 Step 3
Barrier bracket
Grounding
busbar
Anchor cover
Wire duct
For condition 2 seismic installation, if there is no rear access available, the top
of the drive can be mounted to the wall rather than mounted to the floor at the
back of the cabinet.
M12xL35
Based on bracket thickness
of 11 mm (0.43 in.)
Install Main Cooling Fans Main cooling fans are shipped in separate crates. The fans are shipped
assembled in the fan housing, but must be installed after siting the drive.
Socket
Aviation plug
Rear View
Install the Cooling Fan and Noise Reduction Barrier for A-frame
Drives (2.4…4.16 kV, UL and IEC)
To install the cooling fan for A-frame 2.4…4.16 kV drives, follow these
instructions.
1. Place the fan housing on the top plate of the drive. Verify that the socket
is on the same side as the aviation plug.
2. Secure the fan housing using M6 hardware (six places).
3. Connect the aviation plug on the top of the cabinet with the socket on the
fan housing.
Figure 15 - Main Cooling Fan Housing, A-frame (2.4…4.16 kV, UL and IEC)
Socket
Aviation plug
If your application uses noise reduction barriers for the fans, follow these
instructions.
1. Remove the four M6 screws on the left and right sides of the front fan
housing.
2. Place the noise reduction barrier in front of the fan housing.
3. Secure the noise reduction barrier wit h the four M6 screws.
Figure 16 - Install the Noise Reduction Barrier
Install the Mixing Hood for A-frame Drives (2.4…4.16 kV, UL and IEC)
If your application uses a mixing hood with redundant fan, follow these
instructions.
1. Remove the air hood from the skid.
2. Install the four eyebolts at each corner of the air hood.
3. Life the air hood by the four eyebolts and align with the provisions on the
top plate.
4. Secure the air hood with 12 M16x16 hexagon combination screws.
5. Put the fan modules onto the air hood and align with the provisions on
the air hood.
6. Secure the fan modules with 16 M16x16 hexagon combination screws.
M16x16 hexagon
combination screw (16)
Eyebolt (4)
M16x16 hexagon
combination screw (12)
To install the cooling fan for A-frame drives, follow these instructions.
1. Place the fan housing on the top plate of the drive and slide the fan
housing back. Verify that the back flange of the fan housing slides under
the top plate fan bracket assembly.
2. Secure the fan housing using M6 hardware across the front of the fan
assembly.
3. Connect fan wiring to fan terminals located behind the cover on the front
of the fan housing.
Front View
Back View
Install Power Modules Power Modules are available in a wide variety of amperage ratings relating to
(if applicable) the required motor current. Power Modules that are rated up to and including
350 A are mounted in the drive and ship already installed.
Power Modules that are rated above 350 A are shipped separately, therefore site
installation and cable connection is needed. In this case, a lift cart is supplied
and shipped together with the other components.
The lift cart’s hydraulic cylinder can be operated by either a hand or foot crank.
The lifting capacity is 400 kg (882 lb).
Lift tray
Foot Crank
IMPORTANT The Power Module should be handled carefully. After removing the
packaging, inspect the Power Module to confirm that there is no damage
and moisture.
1. You can use the lift cart to move and position the Power Module to the
appropriate location in the cabinet.
2. Push the Power Module slowly along the guide rails until it cannot be
pushed in further.
3. After installing the Power Module in place, use the mounting brackets
and the M6 × 16 large flat pad galvanized nickel screws to fix the four
corners, as shown below.
Mounting brackets
Power Module
Guide rail
Mounting brackets
IMPORTANT The Power Module should be handled carefully. After removing the
packaging, inspect the Power Module to confirm that there is no
damage and moisture.
1. Push the Power Module slowly along the guide rails until it cannot be
pushed in further.
2. After installing the Power Module in place:
a. For 140/215 A rating – use the mounting brackets and M6x16 large flat
pad galvanized nickel screws to secure the two bottom corners.
Power Module
Guide rail
Mounting brackets
b. For 70 A rating – use M16x16 large flat pad galvanized nickel screws to
secure the two bottom corners directly.
Power Module
Guide rail
Secure points
External Ducting The PowerFlex 6000T design can accommodate ducting exhaust air outside of
the control room.
Air Conditioning Sizing If the drive is located in an enclosed space, install air conditioners for each
drive. A general formula to calculate air conditioner power required:
DriveRating kW 1 – DriveEfficiency
--------------------------------------------------------------------------------------------------------= Air Conditioning Size (tons)
3.5
This is for a general estimate. See the actual heat loss data to calculate air
conditioning sizing. Contact the local Rockwell Automation office for actual
data.
Notes:
The installation of all external power cables and control signal wiring is
covered in this chapter. General electrical safety and installation guideline
topics are also included. The basic activities include connecting the system
ground cable, line and motor cables, control power, and all control signal
wiring from the sources to the drive. See Figure 40, Figure 41 and Figure 42 for
an overview of these connections.
Lockout and tagout the input circuit breaker before performing any electrical
connection work. After the input circuit breaker cabinet doors are opened,
immediately test the outgoing connections and any components that are
connected to medium voltage with a live-line tool (hot stick) while wearing
high-voltage gloves. Pay special attention to any capacitors connected to
medium voltage that can retain a charge for a period of time. Only after the
equipment has been verified as isolated and de-energized can subsequent
work be performed. Even though the input to the drive may be open, it is still
possible for hazardous voltage to be present.
See national and local safety guidelines for detailed procedures on how to
safely isolate the equipment from hazards.
ATTENTION: The national and local electrical codes outline provisions for
safely installing electrical equipment. Installation must comply with
specifications regarding wire type, conductor sizes, branch circuit
protection, and disconnect devices. Failure to do so may result in personal
injury and/or equipment damage.
Electrical Drawings Before connecting any power cables or control signal wiring, review and
understand the information that is contained in the project-specific Electrical
Drawings (ED).
The practice that is used within the PowerFlex 6000T electrical drawing is
based on the IEC or NEMA standard depending on the requirements. The
symbols used to identify components on the drawings are international.
Device designations that are used on the drawings and labeling are explained
on each drawing set.
Wiring that connects between the sheets or that ends at one point and starts at
another point on a drawing has an arrow and drawing reference to indicate
the ongoing connection. The drawing reference indicates the sheet and the X/
Y coordinates of the continuation point. The reference system is explained on a
sheet in each drawing set. The unique wire numbering system serves as
confirmation that the correct wire is being traced from sheet-to-sheet or
across a drawing. Wires in multi-conductor cables are typically identified by
color rather than by number. Abbreviations used to identify the colors on the
drawings are fully identified on a sheet in the drawing set.
Grounding System As a general guideline, the ground path must be of sufficiently low impedance
Requirements and capacity that:
• the rise in potential of the drive ground point when subjected to a
current of twice the rating of the supply should be no higher than 4V over
ground potential
• the current flowing into a ground fault is of sufficient magnitude to
cause the protection to operate.
The general grounding point must be reliably connected with the grounding
network.
Attach an external ground cable to the main ground bus, in compliance with
applicable national and local electrical codes.
IMPORTANT The primary grounding cable must have a diameter of at least 50 mm2
and meet all applicable national and local electrical codes.
Run the system ground cable separately from power and signal wiring so that
faults:
See the following diagram for ground connections. This ground bus is the
common ground point for all grounds internal to the drive.
Bond each AC motor frame to the buildings steel that is grounded and within
6 m (20 ft) of this location. Tie it to the ground bus of the drive using ground
wires within the power cables or conduit.
IMPORTANT Do not connect the main ground bus of the drive to the system ground.
The conduit or cable armor must bond to ground at both ends.
Isolation Transformer
U
Inverter
V
Rectifier
W
Ground Bus
Power Cable Insulation Incoming line power cable ratings are shown on the Electrical Drawings and
Requirements reflect what would typically be supplied, based on line voltage rating.
All voltage ratings for outgoing motor cables that are shown are line-to-ground
rated power-frequency voltages and line-to-line power-frequency voltages.
Select cables of appropriate voltage classes when the incoming line grid-side
voltage class differs from the outgoing line motor-side voltage class.
IMPORTANT Follow the recommended field power cabling insulation levels to help
achieve trouble-free startup and operation. The cable insulation level
must be increased over that which would be supplied for an across-the-
line application with the same rated line-to-line voltage.
Power Cable Design Use fire retardant cables for the drive input/output connections.
Considerations
Shielded or unshielded cable can be used based on the criteria that are
considered by the distribution system designer and national and local
electrical codes.
If shielded power cables are used, connect the shield of the main input/output
power cables with the general grounding point of the drive. Ground the drive
output protective grounding connection separately, and only at the drive side.
Comply with the maximum tensile stress and the minimum curvature radius
that is recommended by the cable manufacturer.
The power cable tray must not be less than 300 mm (12 in.).
There must be no gaps where the conduit connects to the cabinet and the
ground bond must be less than 0.1 ohms. Spacing between wire groups is the
recommended minimum for parallel runs of approximately 61 m (200 ft) or
less.
IMPORTANT PowerFlex 6000T drives are able to operate motors if the cable length is
less than 800 m (2624 ft). Contact the factory when cable lengths at the
drive output exceed 800 m (2624 ft).
When the cable length is longer than 800 m (2624 ft), an assessment is
required. It does not necessarily mean that an output filter is required.
Configurations can be provided for longer cable distances, but must be
specified at the time of order.
All input and output power wiring, control wiring, or conduit must be brought
through the conduit entrance holes of the cabinet. Use appropriate connectors
to maintain the environmental rating of the cabinet.
Motor Cable Sizing Voltage drop in motor leads may adversely affect motor starting and running
performance. Installation and application requirements may dictate that
larger wire sizes than indicated in national and local electrical codes are used.
Wire sizes must be selected individually, observing all applicable safety and
national and local electrical codes. The minimum permissible wire size does
not necessarily result in the best operating economy. The minimum
recommended size for the wires between the drive and the motor is the same
as that used if a main voltage source connection to the motor was used. The
distance between the drive and motor can affect the size of the conductors
used.
Consult the Electrical Drawings and appropriate national and local electrical
codes to determine correct power wiring. If assistance is needed, contact your
local Rockwell Automation Sales Office.
Control Signal Wiring Use shielded cables for all analog and digital control cables.
Design Considerations
Steel conduit or a cable tray can be used for all PowerFlex 6000T drive power or
control wiring; however, use only steel conduit for all signal wiring.
ATTENTION: Steel conduit is required for all control and signal circuits
when the drive is installed in European Union countries.
Control cables and power cables must be routed separately; the distance
between the control cable tray and the power cable tray must not be less than
300 mm (11.8 in.).
If the control cable must pass through the power cable tray, the angle between
the cable trays must be as close to 90° as possible.
Guidelines for Drive Signal and Safety Grounds: when using interface cables
carrying signals, where the frequency does not exceed 1 MHz, for
communications with the drive, follow these general guidelines:
• Ground screen mesh around the entire circumference, rather than
forming a pigtail grounded only at one point.
• For coaxial cables with one conductor surrounded by a mesh screen,
ground the screen at both ends.
• When using a multi-layer screened cable (that is, a cable with both a
mesh screen and a metal sheath or some form of foil), there are two
alternative methods:
- Ground the mesh screen at both ends to the metal sheath. The metal
sheath or foil (known as the drain) should, unless otherwise specified,
be grounded at one end only, again, as specified above, at the receiver
end or the end that is physically closest to the main equipment ground
bus
- Leave the metal sheath or foil insulated from ground, and ground the
other conductors and the mesh cable screen at one end only, as stated
above.
Ground Bus
Electrical Installation
Summary Topic Page
Connect the System Ground Cable 45
Insulation Resistance (IR) Test of Power Cables 46
Connect Incoming Line and Outgoing Motor Power Cables 46
Connect Control Power Wiring 51
Connect External Control Signal Wiring 54
Connect Electrical Safety Interlock Circuit to Input Circuit Breaker 54
Connect the System Ground The drive ground bus runs along the bottom of the drive at the front. The
Cable ground bus is accessible at the bottom of the front of each drive cabinet when
the cabinet door is opened. Connect the system ground cable to the drive
ground bus (Figure 21, Figure 22, and Figure 23).
Figure 21 - Ground Cable Connection in the Isolation Transformer Cabinet, A-frame (2.4…4.16 kV, UL
and IEC)
Customer/Contractor supplied
System Ground cable
Ground Bus
Figure 22 - Ground Cable Connection in the Isolation Transformer Cabinet, A-frame (6…6.6 kV, IEC
only)
Transformer Cabinet Junction/LV Cabinet Top View of Surge Arrestor Ground Bus
Ground Bus Ground Lug Ground Bus Ground Lug Ground Bus Ground Lug
Customer/Contractor supplied
System Ground cable
Ground Bus
Lock washer
Flat washer
M8x25 bolt
Insulation Resistance (IR) Before connecting the incoming line and outgoing motor power cables, follow
Test of Power Cables standard industry practice to verify the integrity of the power cable insulation
from the input breaker to the drive and from the drive to the motor.
Connect Incoming Line and The installer must ensure that all power connections are in accordance with
Outgoing Motor Power national and local electrical codes.
Cables Each drive is equipped with provisions for bottom power cable entry as
standard. Provisions for top power cable entry can also be provided. This must
be specified at the time of order.
For the location of incoming line and outgoing motor power cable
connections, refer to the customer-specific Dimension Drawing.
The drive is supplied with the following provisions for power cable lugs.
For A-frame drives, Figure 24 and Figure 25 show typical connection points for
the primary entrance/exit cable.
IMPORTANT If a filter cabinet is supplied, the incoming line cables are from Junction
cabinet and outgoing motor cable connections are in the filter cabinet
(see Figure 26). See the PowerFlex 6000T Drives Hardware Service
Manual, publication 6000-TG100.
1. Connect the three-phase medium voltage inputs L1, L2, and L3 for top or
bottom entry to the user-provided input three-phase AC power.
Top entry
Top entry
Incoming line power
cable connections
Outgoing motor power
cable connections
Bottom entry
Incoming line power
cable connections
Cable clamp
Bottom entry
Top entry
Cable clamp
Bottom entry
U L1
V L2
W L3
Front Front
Junction cabinet Junction cabinet
Section View A-A Section View B-B
Figure 26 - Isolation Transformer Cabinet, A-frame (All ratings) (DV/DT filter cabinet applied)
Input Output
Shielded cable
Non-shielded cable
Input Output
Top entry Bottom entry
Remove Barrier for Bottom Entry Connections (2.4…4.16 kV, UL and IEC)
If you choose to connect the cables through the bottom entry of the A-frame
drive, you have to remove the insulation barrier before you proceed.
1. Remove the three plastic M6x25 bolts that secure the removable
insulation barrier.
Removable barrier
For B-frame drives, Figure 27 show typical connection points for the primary
entrance/exit cable.
IMPORTANT If an optional cabinet is supplied, the incoming line and outgoing motor
cable connections are in the Bypass cabinet. See the PowerFlex 6000T
Drives Hardware Service Manual, publication 6000-TG100.
1. Connect the three-phase medium voltage inputs L1, L2, and L3 to the
user-provided input three-phase AC power.
2. Connect three-phase medium voltage inputs U, V, and W to the user-
provided three-phase asynchronous motor.
3. Cable clamps are provided in the cabinet to aid in routing and
supporting the incoming line and outgoing motor power cables.
Figure 27 - Isolation Transformer Cabinet, B-frame (Junction cabinet applied for cable connection)
)
Junction
cabinet
L3 L2 L1
Incoming line
power cable
connections
Outgoing motor
W V U
power cable
connections
Isolation
Transformer
Connect Control Power Externally supplied control power is required to operate the drive. The
Wiring standard voltage that is supported is 220V AC/50 Hz. The other typical phase
voltages of 230V AC, 240V AC, 110V AC, and 120V AC are also supported (50/60
Hz), but must be specified at the time of order. A minimum of 1.5 kVA is
required to supply the control circuit.
The opening for the control power wiring must be specified during the
quotation stage. See the customer-specific Dimension Drawing for the
location of the opening.
Figure 28 - Control Power Wiring Opening, A-frame (2.4…4.16 kV, UL and IEC)
Bracket for
bundling cable
Cable entrance in
top or bottom front
of LV Control Cabinet
The control power wiring terminates to the VFD1 terminal block strip on the
left side of the LV Control cabinet (Figure 31).
VFD1 Terminal
Block strip
-A-
Connect External Control This section summarizes the control signal wiring from the remote DCS/PLC
Signal Wiring or discrete control to the drive. General connections are detailed in Power
Cabling and Control Signal Wiring Details on page 71. Refer to the Electrical
Drawings for connection information specific See the drive being installed.
Four 4…20 mA analog input signals. One may be used for DCS with rotating
speed setting and three for backup. For detailed information, see Table 14 and
Table 15 on page 74.
Up to four 4…20 mA analog output signals for indication signals such as output
motor current and frequency. See Table 14 and Table 15 on page 74.
Twelve passive dry contact inputs (internal 24V DC power supply) start/stop
and reset controls. For detailed information, see Table 14 and Table 15 on
page 74. These inputs are scalable depending on user requirements.
Four dry contact outputs from the POD option cards are standard with a
capacity of 20 W for indication. Interposing relays are provided to interfacing
to power switching devices and fault status information. The quantity is based
on the options that are ordered with the drive. The rating of these contacts is
220V AC/5 A. For detailed information, see Table 14 and Table 15 on page 74.
These outputs are scalable depending on user requirements.
The control signal wiring enters the drive through the same opening as the
control power wiring in the LV Control Cabinet (Figure 30).
The wiring terminates to the VFD1 terminal block strips on the sides of the LV
Control cabinet (Figure 31).
Connect Electrical Safety The electrical safety interlock circuit is part of the overall control signal wiring
Interlock Circuit to Input activity. However, it is mentioned separately in this document due to its
critical importance related to the safe operation of the drive and personnel
Circuit Breaker safety.
The circuits that are connected between the drive and the input circuit
breaker:
• allow the drive to trip the input circuit breaker if a drive cabinet door is
opened. This applies to the cabinet doors where medium voltage is
present. The LV Control cabinet door can be opened while the drive is
energized.
• allow the drive to prevent the input circuit breaker from closing when
required.
• indicate to the drive when the input circuit breaker is closed.
The electrical safety interlock control signal wiring enters the drive through
the same opening as the control power wiring in the bottom of the LV Control
Cabinet (Figure 30).
Notes:
The drive is shipped in two sections, the Isolation Transformer cabinet and the
Power Module/LV Control cabinet. An optional cabinet may also be supplied.
Drive Mechanical Installation on page 9 describes mechanically joining these
cabinets together. This chapter describes the activities that are required to
electrically connect these drive cabinets’ components together.
Electrical Interconnection
Summary Topic Page
Connect Isolation Transformer Secondary Power Cables 59
Connect Motor and Voltage Sensing Board Cables 60
Connect LV Control and Fan Wiring Bundles 62
Connect Ground Bus 62
Power Cable Figure 33 provides a three-line drawing overview of the power cable
Interconnection Overview interconnections between the power modules (PC XX) in the Power Module/
LV Control cabinet and the secondary windings of the isolation transformer in
the Isolation Transformer cabinet. The number of power modules is
dependent solely on output (motor) voltage:
• 9 power modules for 2.3/2.4/3.0/3.3 kV
• 12 power modules for 4.0/4.16 kV
• 15 power modules for 6.0 kV
• 18 power modules for 6.6/6.9 kV
• 24 power modules for 10 kV
• 27 power modules for 11 kV
It also shows the connection point from the U, V, and W motor output phases
from the power module array to the voltage sensing board cables and the
motor cables.
See the Electrical Drawing (ED) for actual wire number designations.
U U
Motor V
V
W W
Isolation Transformer
Voltage Sensing
Board
1U
1V
1W
PC A0
2U
2V
2W
PC A1
3U
3V
3W
PC A2
4U
L1 4V PC B0
Input power 4W
3-phase AC L2
5U
5V PC B1
5W
any voltage
L3 6U
6V PC B2
6W
7U
7V
7W
PC C0
8U
8V
8W
PC C1
9U
9V
9W
PC C2
Isolation Transformer
9W
9V PC C2
9U
8W
8V
8U
PC C1
7W
7V
7U
PC C0
6W
6V PC B2
Input power
L3 6U
5W
3-phase AC L2 5V
5U
PC B1
any voltage
L1 4W
4V
4U
PC B0
3W
3V PC A2
3U
2W
2V
2U
PC A1
1W
1V
1U
PC A0
Voltage Sensing
Board
W W
V V
Motor
U U
Connect Isolation The isolation transformer’s three-phase primary coils are oriented A, B, and C
Transformer Secondary from left to right, as viewed from the front. The secondary windings are also
divided into three principal sections from top to bottom. The upper third are to
Power Cables feed the power modules in the U output phase. The middle third are to feed the
power modules in the V output phase. The bottom third are to feed the power
modules in the W output phase (Figure 35).
U U
SECONDARY WINDING OUTPUT
W W
As shown in Figure 33, the first winding set (1U, 1V, and 1W) connects to the
three-phase input power connection of the first power module in the U motor
phase array (PCA1), the second winding set connects to the second power
module in the U motor phase array (PCA2), and the third winding set connects
to the third power module in the U motor phase array (PCA3). The next three
winding sets connect to the power modules in the V motor phase array. The
remaining three winding sets connect to the power modules in the W motor
phase array.
phase, the middle third feeds the power modules in the V phase, and the
bottom third feeds the power modules in the W phase.
Each three-phase secondary winding set of the isolation transformer has three
individual single-phase power cables connecting its output to the three-phase
power input of its corresponding power module.
Drives are shipped split with an Isolation Transformer cabinet and a Power
Module cabinet, and connection at the site is needed. The power cables
connect to the secondary winding termination in the Isolation Transformer.
All cables can be connected from the front of the cabinet.
1U
2U
3U
4U
5U
6U
Front View
Connect Motor and Voltage The Voltage Sensing Board cables and the motor cables both connect to the
Sensing Board Cables same output point of each motor phase array (Figure 33). The voltage sensing
cables must be connected on site.
For drive ratings with power modules ≥250 A, the connection points are always
on the right side of the power module cabinet. For drive ratings with power
modules ≤200 A, the connection points are on the left side of the power module
cabinet.
60 Rockwell Automation Publication 6000-IN100D-EN-P - July 2022
Chapter 3 Drive Electrical Interconnection
A typical connection with connection points on the left side of the power
module cabinet are shown in the following diagrams (Figure 37, Figure 38).
U Phase
Motor cable
to Junction
cabinet
W Phase
VSB cable
Front View
Motor cable
Lock washer
V Phase
W Phase
Front View
Connect LV Control and Fan There are control wiring bundles that must be reconnected after the drive
Wiring Bundles cabinets are connected together. These control wiring bundles are connected
for the factory test and then disconnected and bundled at the shipping splits
before shipment.
For exact wire numbers and terminal block designations, see the Electrical
Drawings.
Connect Ground Bus A solid ground bus is located at the bottom front of each cabinet. When a
shipping split is required, ground bus connectors are supplied. One is attached
above the solid ground bus and one below (Figure 39).
Ground bus connection openings are provided in the cabinet sidesheets for
this connection.
M8 Hex Nut
Lock Washer
Grounding Bus
Connector
Flat Washer
Grounding
Bus
M8x30 Hex Bolt
Complete the Installation 1. Inspect the interior of all cabinets carefully for hardware or tools that
may have been misplaced.
2. Check and verify that no hardware or foreign material has fallen in the
secondary windings in the Isolation Transformer cabinet.
3. Check that all mechanical work has been completed properly. All barriers
and guards that may have been removed must be reinstalled.
4. Check that all electrical connections have been made and torqued as
specified.
5. Verify that the safety circuit is working properly (see page 54).
6. Reinstall all cabinet back plates.
Pre-Commissioning
Pre-Commissioning Rockwell Automation manages the startup service for each installed drive at
Responsibilities the customer’s site, but there are a number of tasks the customer or its
representatives must complete before scheduling Rockwell Automation
personnel for drive commissioning.
ATTENTION: The CMOS devices that are used on the control circuit boards
are susceptible to damage or destruction by static charges. Personnel
working near static sensitive devices must be appropriately grounded.
Pre-Commissioning Once all points of the checklist are complete, initial each checkbox and provide
Checklist the date. Photocopy the checklist and fax the copy to the Rockwell Automation
Start-up Manager, along with the planned startup date. Upon receiving this
checklist, the Project Manager contacts the site to finalize arrangements for a
startup engineer to travel to the site at your convenience.
Name: Date:
Company:
Phone: Pages:
Fax:
Table 8 - Safety
Initials Date Check
The grounding of the drive should be in accordance with national and local
electrical codes.
Notes:
Torque Requirements
Torque Requirements Proper tightening torque must be used for installation and wiring.
Table 13 - Torque Requirements
Torque
Thread Size Class 8.8
N•m lb•ft
M4 3.0 2.2
M5 5.9 4.4
M6 10.5 7.7
M8 26.0 19.2
M10 51.0 37.6
M12 89.0 65.7
M14 141.0 104.1
M16 215.0 158.7
M20 420.0 310.0
Notes:
Notes:
Schematic Diagrams
Control Signal
MFN1
Customer Supplied
Figure 40 - Schematic Diagram of the Drive System without a Bypass Cabinet, A-frame(a)
Ground
DANGER:
Appendix
The medium voltage drive is one component in this system, which includes an input device that is supplied by others.
Power Cabling and Control Signal Wiring Details
The supplier of the input device is responsible for confirming that there is safe access to the input/output drive (if used) and safe access to the drive.
D
(a) Wiring locations are for design reference only; actual wiring must comply with the drawings
71
72
Appendix D
Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan
29 28 27 26 25 24 23 22 21 35 34 33 32 71
Power Cabling and Control Signal Wiring Details
31(1) 72(1)
Transformer(a)
$ $ $ $
3(*5'
Fan
Control
/ / / 8 9 : Cabinet
9)' 9)'
T1
/
1
DANGER:
Figure 41 - Schematic Diagram of the Drive System without a Bypass Cabinet, B-frame with one
The medium voltage drive is one component in this system, which includes an input device that is supplied by others.
The supplier of the input device is responsible for confirming that there is safe access to the input/output drive (if used) and safe access to the drive.
(a) Wiring locations are for design reference only; actual wiring must comply with the drawings
13.8 kV, 3 phase, 60 Hz
110/120/220/230/240V AC, 1 phase, 50/60 Hz.
Upstream Circuit Breaker
Control Signal with Branch Circuit Protection
(Customer scope of supply)
(Minimum 3 kVA Capacity is needed)
Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan Fan
40(1) 39 38 37 36 29(1) 28 27 26 25 24 23 22 21 35 34 33 32 31(1) 72(1) 71
Transformers(a)
$ $ $ $ $
3(*5'
Fan Fan
Control Control
Cabinet / / / 8 9 : Cabinet
9)' 9)'
T2 T1
/
Control Cabinet Transformer Cabinet 2 Power Cell Cabinet Transformer Cabinet 1 Filter Cabinet /
Junction Cabinet
DANGER:
The medium voltage drive is one component in this system, which includes an input device that is supplied by others.
Figure 42 - Schematic Diagram of the Drive System without a Bypass Cabinet, B-frame with two
The supplier of the input device is responsible for confirming that there is safe access to the input/output drive (if used) and safe access to the drive.
(a) Wiring locations are for design reference only; actual wiring must comply with the drawings
73
Power Cabling and Control Signal Wiring Details
Appendix D Power Cabling and Control Signal Wiring Details
Standard Input/Output
Connection Points
Table 14 - Standard I/O Connections Points
Signal Name DI DO Wire Numbers Signal Usage Signal Logic
MV Close Permissive (NO) X 2535, 2538 Allows MV device to close when closed PIOB - DO1 (NO) + Estop (NO) + MV Doors Closed (NO)
PIOB - DO1 (NC) parallel with Estop (NC) parallel with MV Doors
MV Close Permissive (NC) X 2544, 2545 Allows MV device to close when open Closed (NC)
PIOB - DO0 (NO) parallel with EStop (NC) parallel with MV
MV Open Command (NO) X 2539, 2540 Commands MV device to open when closed Doors Closed (NC)
MV Open Command (NC) X 2546, 2549 Commands MV device to open when open PIOB - DO0 (NC) + Estop (NO) + MV Doors Closed (NO)
Estop Status (NO) X 2541, 2542 Estop active when closed Estop (NC)
Estop Status (NC) X 2541, 2543 Estop active when open Estop (NO)
MV Device Status X D-1035A, D-1036A MV device is closed when closed Goes to interposing relay whose contacts go to PIOB DI0.
Notes:
Cable Sizes The data in the following tables are informative only; do not base final design
criteria solely on this data. Follow national and local installation codes,
industry best practices, and cable manufacturer recommendations. As cabling
methods can vary widely, maximum cables sizes do not account for the size of
the conduit hub.
Table 16 - Line and Load Cable Sizes for A-frame Drives (IEC)
Description Drive Enclosure Max Size and No.
Motor V Frequency Entry Opening mm (in.) Incoming Cables: IEC(1) (2) (3)
Top 435 x 300 (17.1 x 11.8) 203 mm² 6.6 kV/phase or
3000V 50 Hz
Bottom 220 x 143 (8.7 x 5.6) 240 mm² (500 AWG) 15 kV/phase
Top 435 x 300 (17.1 x 11.8) 203 mm² 6.6 kV/phase or
3300V 50 Hz
Bottom 220 x 143 (8.7 x 5.6) 240 mm² (500 AWG) 15 kV/phase
Maximum Line Top 435 x 300 (17.1 x 11.8) 203 mm² 6.6 kV/phase or
Cable Sizes 4000/4160V 50/60 Hz
Bottom 220 x 143 (8.7 x 5.6) 240 mm² (500 AWG) 15 kV/phase
Table 17 - Line and Load Cable Sizes for A-frame Drives (UL)
Description Drive Enclosure Max Size and No.
Motor V Frequency Entry Opening mm (in.) Incoming Cables: IEC(1) (2) (3)
Top 435 x 300 (17.1 x 11.8)
2300/2400V 60 Hz 203 mm² (400 AWG) 6.6 kV/phase
Maximum Line Bottom 220 x 143 (8.7 x 5.6)
Cable Sizes Top 435 x 300 (17.1 x 11.8)
4000/4160V 50/60 Hz 203 mm² (400 AWG) 6.6 kV/phase
Bottom 220 x 143 (8.7 x 5.6)
Top 435 x 300 (17.1 x 11.8)
2300/2400V 60 Hz 203 mm² (400 AWG) 6.6 kV/phase
Maximum Load Bottom 220 x 143 (8.7 x 5.6)
Cable Sizes Top 435 x 300 (17.1 x 11.8)
4000/4160V 50/60 Hz 203 mm² (400 AWG) 6.6 kV/phase
Bottom 220 x 143 (8.7 x 5.6)
(1) Cable sizes are based on overall dimensions of compact-stranded three-conductor shielded cable (common for industrial
cable tray installations). Maximum sizing stated accounts for minimum rated cable insulation requirements and the next
higher-rated cable (that is, 8 kV is not commercially available in many areas of the world, therefore Rockwell Automation
provides an 8 kV (minimum rating) and a 15 kV rating, when applicable. Enclosure openings accommodate the thicker
insulation on the higher-rated cable. IEC ratings show the equivalent to the NEMA sizes. The exact cable mm2 size that is
shown is not commercially available in many cases; use the next smaller standard size.
(2) Minimum cable bend radius recommendations vary by national codes, cable type, and cable size. Consult local codes for
guidelines and requirements. General relationship of cable diameter to bend radius is typically between 7x...12x (for example,
if the cable diameter is 1 in. [2.54 cm] the minimum bend radius could range between 7...12 in. [18.8...30.48 cm]).
(3) As cabling methods can vary widely, maximum cable sizes that are shown do not account for the size of the conduit hub.
Verify size of conduit hubs against the “Drive enclosure openings” shown.
Line and Load Cable Sizes for B-frame Drives (IEC and UL)
Description Drive Enclosure Max Size and No.
Motor V Frequency Opening mm (in.) Incoming Cables(1) (2) (3)
608 mm² (1200 kcmil) 5 kV or
2400V 50/60 Hz 138 x 138 (5.4 x 5.4) 608 mm² (1200 kcmil) 8 kV/phase
608 mm² (1200 kcmil) 5 kV or
3000V 50/60 Hz 138 x 138 (5.4 x 5.4) 608 mm² (1200 kcmil) 8 kV/phase
608 mm² (1200 kcmil) 5 kV or
3300V 50/60 Hz 138 x 138 (5.4 x 5.4) 608 mm² (1200 kcmil) 8 kV/phase
608 mm² (1200 kcmil) 5 kV or
4160V 50/60 Hz 138 x 138 (5.4 x 5.4)
Maximum Line 608 mm² (1200 kcmil) 8 kV/phase
Cable Sizes 608 mm² (1200 kcmil) 8 kV or
6000V 50/60 Hz 138 x 138 (5.4 x 5.4) 608 mm² (1200 kcmil) 15 kV/phase
608 mm² (1200 kcmil) 8 kV or
6600V 50/60 Hz 138 x 138 (5.4 x 5.4) 608 mm² (1200 kcmil) 15 kV/phase
608 mm² (1200 kcmil) 8 kV or
7200V 50/60 Hz 138 x 138 (5.4 x 5.4) 608 mm² (1200 kcmil) 15 kV/phase
10,000V 50/60 Hz 138 x 138 (5.4 x 5.4) 608 mm² (1200 kcmil) 15 kV/phase
11,000V 50/60 Hz 138 x 138 (5.4 x 5.4) 608 mm² (1200 kcmil) 15 kV/phase
608 mm² (1200 kcmil) 5 kV or
2300/2400V 50/60 Hz 138 x 138 (5.4 x 5.4) 608 mm² (1200 kcmil) 8 kV/phase
608 mm² (1200 kcmil) 5 kV or
3000V 50/60 Hz 138 x 138 (5.4 x 5.4) 608 mm² (1200 kcmil) 8 kV/phase
608 mm² (1200 kcmil) 5 kV or
3300V 50/60 Hz 138 x 138 (5.4 x 5.4) 608 mm² (1200 kcmil) 8 kV/phase
608 mm² (1200 kcmil) 5 kV or
4000/4160V 50/60 Hz 138 x 138 (5.4 x 5.4)
Maximum Load 608 mm² (1200 kcmil) 8 kV/phase
Cable Sizes 608 mm² (1200 kcmil) 8 kV or
6000V 50/60 Hz 138 x 138 (5.4 x 5.4) 608 mm² (1200 kcmil) 15 kV/phase
608 mm² (1200 kcmil) 8 kV or
6300/6600V 50/60 Hz 138 x 138 (5.4 x 5.4) 608 mm² (1200 kcmil) 15 kV/phase
608 mm² (1200 kcmil) 8 kV or
6900V 50/60 Hz 138 x 138 (5.4 x 5.4) 608 mm² (1200 kcmil) 15 kV/phase
10,000V 50/60 Hz 138 x 138 (5.4 x 5.4) 608 mm² (1200 kcmil) 15 kV/phase
11,000V 50/60 Hz 138 x 138 (5.4 x 5.4) 608 mm² (1200 kcmil) 15 kV/phase
(1) Cable sizes are based on overall dimensions of compact-stranded three-conductor shielded cable (common for industrial
cable tray installations). Maximum sizing stated accounts for minimum rated cable insulation requirements and the next
higher-rated cable (that is, 8 kV is not commercially available in many areas of the world, therefore Rockwell Automation
provides an 8 kV (minimum rating) and a 15 kV rating, when applicable. Enclosure openings accommodate the thicker
insulation on the higher-rated cable. IEC ratings show the equivalent to the NEMA sizes. The exact cable mm2 size that is
shown is not commercially available in many cases; use the next smaller standard size.
(2) Minimum cable bend radius recommendations vary by national codes, cable type, and cable size. Consult local codes for
guidelines and requirements. General relationship of cable diameter to bend radius is typically between 7x…12x (for example,
if the cable diameter is 1 in. [2.54 cm] the minimum bend radius could range between 7…12 in. [18.8…30.48 cm]).
(3) As cabling methods can vary widely, maximum cable sizes that are shown do not account for the size of the conduit hub.
Verify size of conduit hubs against the “Drive enclosure openings” shown.
Notes:
I P
IEC721-1 8, 35 Power Cables
Incoming Line Power Cable Connections Desing Considerations 42
Location 47, 48, 51 Insulation Requirements 41
Interconnection Overview 57
Input Connection Points 74
Maximum Distance 42
Input/Output Connections Schematic (No Bypass) 71, 72, 73
Remote Distributed Control System 74 Torque Requirements 67
Standard I/O Connection Points 74 Power Module Lift Cart 31
Insulation Resistance (IR) Test Lifting Capacity 31
Power Cables 46 Operating Procedure 31
Isolation Transformer Precautions 31
Location 51 Power Module/LV Control Cabinet
Isolation Transformer Cabinet Control Power Wiring Location 51
Ground Bus 62 Electrical Safety Interlock Wire Entry 55
Layout 47, 49, 51 Ground Bus 62
Secondary Power Cables 59 Motor cables 61
Secondary Winding Connections 60 Power Module Installation 31
Power Module Interconnections 60
Power Module Lift Cart 31
J Terminal Block Strip location 53
Voltage Sensing Board cables 61
Junction Cabinet
Power Modules
Location 51
Air Flow 37
Cable Routing and Connection 60
L Fan Wiring Bundles 62
Installation 31
Lift Cart 31 Lift Cart 32
Lifting capacity 31 Lift cart 31
Operation 31 Motor Cable connection 61
Lifting Angles Voltage Sensing Board connection 61
Torque Requirements 67 Power Terminals 46
Line Cable Sizes 77 PowerFlex 6000T
Drive Enclosure Opening 77 Electrical Installation 39
Maximum Size 77 External Ducting Specifications 35
Motor Voltage/Frequency 77 Isolation Transformer Cabinet Layout 47,
Line-to-Ground Rated Power Frequency 49, 51
Voltage 41 Line Cable Sizes 77
Load Cable Sizes 77
Line-to-Line Power Frequency Maximum
Mechanical Installation 9
Voltage 41 Power Module Lift Cart 31
Pre-Commissioning 63
Schematic (No Bypass) 71, 72, 73
Notes:
Technical Support Center Find help with how-to videos, FAQs, chat, user forums, and product notification updates. rok.auto/support
Knowledgebase Access Knowledgebase articles. rok.auto/knowledgebase
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center Download firmware, associated files (such as AOP, EDS, and DTM), and access product rok.auto/pcdc
(PCDC) release notes.
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our
content, complete the form at rok.auto/docfeedback.
At the end of life, this equipment should be collected separately from any unsorted municipal waste.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Allen-Bradley, expanding human possibility, FactoryTalk, Guardmaster, PowerFlex, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
EtherNet/IP is a trademark of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur