Heathcote Marketplace, VA (48100R008350) - BID Set - Structural Special Inspections
Heathcote Marketplace, VA (48100R008350) - BID Set - Structural Special Inspections
Building Owner’s Name: JP MORGAN CHASE BANK, N.A. Contact: DON REED
This Statement of Special Inspections is submitted as a condition for permit issuance in accordance with the Virginia Uniform Statewide Building
Code. The Special Inspections Schedule is an integral part of the Statement of Special Inspections.
The Special Inspections Engineer of Record shall keep records of specified special inspections and testing and shall furnish copies of inspection and
testing reports to the Prince William County Special Inspections Section (PWCSIS) and to the appropriate Registered Design Professional(s) of
Record (RDPR), (e.g. the SER for building structural elements, MER for smoke control system, AR for EIFS and SFRM). Discrepancies from the
approved plans and specifications and code violations observed during the conduct of special inspections services shall be brought to the immediate
attention of the Contractor for correction, to the attention of PWCSIS, and to the RDPR. A Final Report of Special Inspections, documenting
completion of specified special inspections, correction of any discrepancies and observed code violations shall be submitted to and approved by
PWCSIS prior to the building concealment inspection by the Building Construction Inspections Branch.
Prepared by:
Signature & Date By checking this box, I agree to electronically signing this form.
Reviewed and Approved by:
Structural Engineer of Record: Jennifer Zabik 11/04/24
Signature & Date By checking this box, I agree to electronically signing this form.
Mechanical Engineer of Record (Smoke Control Systems Only) Bruce C. Branscum 10/24/24
Signature & Date ✔ By checking this box, I agree to electronically signing this form.
D. MASONRY CONSTRUCTION -
LEVEL 2 1705.4 SIER
1. Verify compliance with the approved
— X — — Art. 1.5
submittals.
2. Verification of f'm and f'AAC prior to
construction and for every 5,000 square — X — — Art. 1.4B
feet during construction.
3. Verification of proportions of materials in
premixed or pre-blended mortar and grout — X — — Art. 1.5B
as delivered to the site.
4. Verification of slump flow and VSI as
delivered to the site for self-consolidating X — — — Art. 1.5B.1.b.3
grout.
2.
3.
4.
5.
At the time of these inspection, all items inspected were in accordance with the County approved building plans and the Virginia Uniform Statewide
Building Code; a copy of the required building permit was posted on the construction site. Additionally, the erosion control devices were properly installed
and maintained; or the department of Public Works was notified within one business day of the erosion control deficiency in accordance with Policy 1.16
Third Party Inspection Certification Program.