DATASHEET - ZB12-12
Overload relay, ZB12, Ir= 9 - 12 A, 1 N/O, 1 N/C, Direct mounting, IP20
Part no. ZB12-12
Catalog No. 278441
Alternate Catalog XTOB012BC1
No.
EL-Nummer 4131836
(Norway)
Similar to illustration
Delivery program
Product range Overload relay ZB up to 150 A
Product range Accessories
Accessories Overload relays
Frame size ZB12
Phase-failure sensitivity IEC/EN 60947, VDE 0660 Part 102
Description Test/off button
Reset pushbutton manual/auto
Trip-free release
Mounting type Direct mounting
Ir A 9 - 12
Contact sequence
Auxiliary contacts
N/O = Normally open 1 N/O
N/C = Normally closed 1 N/C
For use with DILM7, DILM9, DILM12, DILM15,
DIULM7, DIULM9, DIULM12,
SDAINLM12,
SDAINLM16,
SDAINLM22
DS7-34…SX012…
Short-circuit protection
Type “1” coordination gG/gL A 50
Type “2” coordination gG/gL A 25
Notes
Overload release: tripping class 10 A
short-circuit protective device: Observe the maximum permissible fuse of the contactor with direct device mounting.
Suitable for protection of Ex e-motors.
II(2)G [Ex d] [Ex e] [Ex px], II(2)D [Ex p] [Ex t]
PTB 10 ATEX 3010
Observe manual MN03407005Z-DE/EN.
Notes
Fitted directly to the contactor
11/24/2022 Eaton 278441 ED2022 V93.0 EN 1/6
1 Contactor
Technical data
General
Standards IEC/EN 60947, VDE 0660, UL, CSA
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Operating range to IEC/EN 60947
PTB: -5 °C - +55 °C
Open °C -25 - +55
Enclosed °C - 25 - 40
Temperature compensation Continuous
Weight kg 0.145
Mechanical shock resistance g 10
Sinusoidal
Shock duration 10 ms
Degree of Protection IP20
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Altitude m Max. 2000
Main conducting paths
Rated impulse withstand voltage Uimp V AC 6000
Overvoltage category/pollution degree III/3
Rated insulation voltage Ui V 690
Rated operational voltage Ue V AC 690
Safe isolation to EN 61140
Between auxiliary contacts and main contacts V AC 440
Between main circuits V AC 440
Temperatur compensation residual error > 40 ºC ≦ 0.25 %/K
Current heat loss (3 conductors)
Lower value of the setting range W 3.9
Maximum setting W 6.9
Terminal capacities mm
2
Solid mm
2 1 x (1 - 6)
2 x (1 - 6)
Flexible with ferrule mm
2 1 x (1 - 4)
2 x (1 - 4)
Solid or stranded AWG 18 - 8
Terminal screw M4
Tightening torque Nm 1.8
Stripping length mm 10
Tools
Pozidriv screwdriver Size 2
Standard screwdriver mm 1x6
Auxiliary and control circuits
Rated impulse withstand voltage Uimp V 4000
Overvoltage category/pollution degree III/3
Terminal capacities mm
2
Solid mm
2 1 x (0.75 - 4)
11/24/2022 Eaton 278441 ED2022 V93.0 EN 2/6
2 x (0.75 - 4)
Flexible with ferrule mm
2 1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Solid or stranded AWG 2 x (18 - 14)
Terminal screw M3.5
Tightening torque Nm 1.2
Stripping length mm 8
Tools
Pozidriv screwdriver Size 2
Standard screwdriver mm 1x6
Rated insulation voltage Ui V AC 500
Rated operational voltage Ue V AC 500
Safe isolation to EN 61140
between the auxiliary contacts V AC 240
Conventional thermal current Ith A 6
Rated operational current Ie A
AC-15
Make contact
120 V Ie A 1.5
220 V 230 V 240 V Ie A 1.5
380 V 400 V 415 V Ie A 0.5
500 V Ie A 0.5
Break contact
120 V Ie A 1.5
220 V 230 V 240 V Ie A 1.5
380 V 400 V 415 V Ie A 0.9
500 V Ie A 0.8
DC L/R ≦ 15 ms
Switch-on and switch-off conditions based on DC-13, time constant as specified.
24 V Ie A 0.9
60 V Ie A 0.75
110 V Ie A 0.4
220 V Ie A 0.2
Short-circuit rating without welding
max. fuse A gG/gL 6
Notes
Notes Ambient air temperature: Operating range to IEC/EN 60947, PTB: -5°C to +55°C
Main circuits terminal capacity solid and flexible conductors with ferrules: When using 2 conductors use equal cross-sections.
Rating data for approved types
Auxiliary contacts
Pilot Duty
AC operated B300 at opposite polarity
B600 at same polarity
DC operated R300
Short Circuit Current Rating SCCR
600 V High Fault
SCCR (fuse) kA 100
max. Fuse A 15 Class J/CC
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation In A 12
Heat dissipation per pole, current-dependent Pvid W 2.3
Equipment heat dissipation, current-dependent Pvid W 6.9
Static heat dissipation, non-current-dependent Pvs W 0
11/24/2022 Eaton 278441 ED2022 V93.0 EN 3/6
Heat dissipation capacity Pdiss W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 55
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat Meets the product standard's requirements.
and fire due to internal electric effects
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical data ETIM 8.0
Low-voltage industrial components (EG000017) / Thermal overload relay (EC000106)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Overload protection device / Thermal overload relay ([email protected] [AKF075014])
Adjustable current range A 9 - 12
Max. rated operation voltage Ue V 690
Mounting method Direct attachment
Type of electrical connection of main circuit Screw connection
Number of auxiliary contacts as normally closed contact 1
Number of auxiliary contacts as normally open contact 1
Number of auxiliary contacts as change-over contact 0
Release class CLASS 10 A
Reset function input No
Reset function automatic Yes
Reset function push-button Yes
Approvals
Product Standards IEC/EN 60947-4-1; UL 60947-4-1; CSA - C22.2 No. 60947-4-1-14; CE marking
UL File No. E29184
UL Category Control No. NKCR
CSA File No. 12528
CSA Class No. 3211-03
North America Certification UL listed, CSA certified
Specially designed for North America No
Suitable for Branch circuits
11/24/2022 Eaton 278441 ED2022 V93.0 EN 4/6
Max. Voltage Rating 600 V AC
Degree of Protection IEC: IP20, UL/CSA Type: -
Characteristics
These tripping characteristics are mean values of the spreads at 20 °C ambient air temperature in a cold state.
Tripping time depends on response current.
When the devices are at operational temperature the tripping time of the overload relay falls to approx. 25 % of the read off value.
1: Minimum level, 3-phase
2: Maximum level, 3-phase
3: Minimum marker, 2-phase
4: Highest marker, 2-phase
11/24/2022 Eaton 278441 ED2022 V93.0 EN 5/6
Dimensions
① OFF
② Reset/ON
Additional product information (links)
IL03407015Z (AWA2300-2114) Overload relay
IL03407015Z (AWA2300-2114) Overload relay https://es-assets.eaton.com/DOCUMENTATION/AWA_INSTRUCTIONS/IL03407015Z2021_11.pdf
IL03407195Z Sealable shroud
IL03407195Z Sealable shroud https://es-assets.eaton.com/DOCUMENTATION/AWA_INSTRUCTIONS/IL03407195Z2021_10.pdf
MN03407004Z (AWB2300-1527D/GB) ZB12/XTOB...BC1 and ZB32/XTOB...CC1 overload relays, overload monitoring of Ex e motors
MN03407004Z (AWB2300-1527D/GB) ZB12/ https://es-assets.eaton.com/DOCUMENTATION/AWB_MANUALS/MN03407004Z_DE_EN.pdf
XTOB...BC1 and ZB32/XTOB...CC1 overload
relays, overload monitoring of Ex e motors -
Deutsch / English
11/24/2022 Eaton Industries GmbH 6/6
http://www.eaton.eu
© 07/2022 by Eaton Industries GmbH
Eaton 278441 ED2022 V93.0 EN