100% found this document useful (2 votes)
2K views3 pages

Cable Termination Failure Reasons

The document discusses proper cable preparation and installation techniques to ensure reliable cable joints and terminations. Key points include carefully removing insulation and screens without damage, cleaning surfaces to remove contamination, using the correctly sized accessory for the job, and following installation instructions closely. Attention to preparation, installation procedures, and cleanliness can help even lower quality accessories last a long time and prevent costly system failures.

Uploaded by

Imran Ahmed
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
2K views3 pages

Cable Termination Failure Reasons

The document discusses proper cable preparation and installation techniques to ensure reliable cable joints and terminations. Key points include carefully removing insulation and screens without damage, cleaning surfaces to remove contamination, using the correctly sized accessory for the job, and following installation instructions closely. Attention to preparation, installation procedures, and cleanliness can help even lower quality accessories last a long time and prevent costly system failures.

Uploaded by

Imran Ahmed
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

CABLE JOINTS, CABLE TERMINATIONS, CABLE GLANDS, CABLE CLEATS FEEDER PILLARS, FUSE LINKS, ARC FLASH, CABLE

ROLLERS, CUT-OUTS

11KV 33KV CABLE JOINTS & CABLE TERMINATIONS FURSE EARTHING


www.cablejoints.co.uk Thorne and Derrick UK Tel 0044 191 490 1547 Fax 0044 191 477 5371 Tel 0044 117 977 4647 Fax 0044 117 9775582

FirstStepstoReliability
XLPECablePreparation Controllingtheinitialinstallationcostsofanypowersystemiscriticaltooperatingcompanies andcontractorsalike.Systemmaintenanceandrepairarealsosubstantialfactorsinoverallcost. Itisimportantthatinstallationsarenotonlycompletedefficientlyandquickly,butalsodone correctly. Nomaterhowwellacableaccessoryisdesigned,itwillfailifthecableisnotproperlyprepared beforeinstallation.Herearesomeofthemorecommoncausesoffailureduetopoor workmanship. Damagetotheinsulationduringsemiconductivescreenremoval Thisisprobablythenumberonecauseofalljointandterminationfailures.Caremustbetaken whenremovingthesemiconductivescreen,anydamageornicktotheinsulationatthisstage willresultincreatinganunscreenedairvoid.Sincethedielectricstrengthofairislessthanthat oftheXLPEinsulation,theconcentrationofelectricalstressinthisareawillexceedthedielectric strengthofair.Theairwillionizecausingcoronadischargetooccur.Thesedischargesbombard thesurroundinginsulation100timesasecond,andwillresultincuttingthroughtheinsulation andultimatefailure. Damagetotheconductorduringinsulationremoval Bynottakingcareorusingincorrectmethods,conductorscan,quiteoften,benicked,this, particularlyinthecaseofaluminiumconductors,canresultinindividualstrandsbreakingfree, leadingtoaresistivehotspotaroundtheconnectorarea,causingthermalrunawayand eventualfailure. Contaminationoftheinsulationsurface Itisimportantthatthecableinsulationbefreefromallmoistureandcontamination.Common contaminatesinclude,mudontheoutsidesurfacesandsemiconductiveparticles,leftonthe surfaceoftheinsulation,aftertheconductivescreenhasbeenremoved.Ifthesecontaminants remainontheinsulationsurfacesbeingjointedorterminated,aconductivepathcanexist,and

thedifferenceinpotential,betweentheenergisedconductorandearthscreenwillcausecurrent toflowthroughthecontamination,resultinginerosionandultimatelybreakdown.Toavoidthis happening,allcaremustbetakentoensuretheinstallerkeepshishands,aswellashistools cleananddry.Furthertothis,theinsulationsurfacesshouldbecleanedpriortotheinstallation oftheaccessoryandprotectedfromfurthercontaminationuntiltheinstallationiscomplete. AccessoryInstallation Incorrectchoiceofaccessory Thismaysoundstrange,butdoyouknowthedifferencebetweenanindoorandoutdoor termination?Justbecausetheterminationistobeoutsidedoesntmeanyouneedanoutdoor type.IndoorkitsareforterminatingcablesthatwillnotbeconstantlyexposedwithdirectUV lightordirectlyexposedtotheelements.Asealedtakeoffchamberonthesideofatransformer requiresanindoortermination,despitethetransformerbeingoutside. Unfortunately,itisnotunusualforanoperatingcompanyorcontractor,tobealittleunsureof theactualcablespecificationpriortoarrivalorexposureonsite.Caremustbetakenbeforeand duringinstallationtoensuretheaccessoryprovided,suitsboththeapplicationrangeandcable type. Themajorityofaccessoriesarerangetakingmakingoneofthechoiceseasier,butthereis normallyadifferencerelatingtocableinsulation,numberofcoresandsystemvoltageetc.The useofakitdesignedfor11kV,XLPEinsulatedcable,willnotnormallyworkeffectivelyonan11kV paperinsulatedcable. Incorrectinstallationdimensionsorprocedures Unfortunately,thisoneusuallycomesdowntomaleego,theinstallernotwantingtoappear unfamiliarwith,orunsureofhowtheaccessoryisassembled.Hegoesblindlyonwithoutreading theinstallationinstructions,doingwhathethinksistherightthing.Weveallbeenthere,how manytimesdowestarttoassemblethatnewSwedishcabinet,onlytofindweshouldhavefitted thoseshelvesbeforefixingthetopanddoors. Allreputablemanufactureswillincludeaninstallationsheetwithinthekit,thisisnotbecause theywanttocontributetothedemiseoftherainforests,itistheonlywaytheyhaveoftelling theinstallerthekit,maynotbeexactlythesameasasimilarkitfromarivalmanufactureror eventhesamekitfromafewyearsago. Incorrectdimensionorprocedurescouldleadtomisplacedorevenomittedcomponents, resultinginpotentialbreakdown. Incorrectconnector/lugapplication Eachconnectormanufacturerwillrecommendaconnectorandthecorrectdieset,fora particularsizeandformatofconductor,mixingthetoolingandconnectormanufacturerscanin somecircumstancescauseproblems.Withthevariationsinphysicalsizeofthemodern conductors,itissometimesdifficulttoensurecompressionconnectorsareinstalledcorrectly. Theincreaseuseoftorqueshearconnectorsgoessomewaytoalleviatingthisproblem,butat acost.Mostmechanicalconnectorsarelargerindiameterthanthecompressionequivalent.Care

shouldbetakenwhensizingtheaccessory,toensuretheyfitwithintheaccessorymanufacturers recommendedparameters. SiteCleanliness Withoutexceptionallaccessoriesaretypetestedinnicewarmandcleanlaboratories, unfortunately,acoldandmuddybuildingsiteplaysnopartinthetypeapprovalprocess.Any contaminationwithintheassemblycouldhaveadetrimentaleffectonitsefficiencyand longevity. Dirtorgreaseonthehandsiseasilytransferredtoanytapesorcomponentsapplied,mudisone ofthosethingsthatnoamountofdegreasingsolventwillremove.Acommonmisconception whenusingheatshrinkableaccessoriesisanywaterpresentwilldisappearwhenthetubesare shrunkinplace.Unfortunately,weliveinatimewhentheraincontainsmorethanjustpure water,andonabuildingsite,theraincancarrywithitthingslikecementdustorcarbonparticles fromthatannoyingdumptruckthatkeepsdrivingby.Itistruethemoisturewillevaporateonce heated,butitwillleavebehindallofthepollutants. Keepingthejointareafreefromcluttercanpreventaccidentalandevenunnoticed contaminationoftheassembly,thiscanonlybeagoodthing,butmoreimportantly,youll probablyloosefewertools. Finally Mostaccessoriesfromreputablemanufacturerswillmeetandsurpassnormaloperating requirements.However,goodpreparationwillhelpalowerqualityaccessory,andpoor preparationwillhinderabetterproduct.Takecarewheninstallinganyaccessory,rememberthe costofaterminationorjointisafractionoftheworthofthetotalinstallation.Anysystemisonly asgoodastheweakestlink,ajointorterminationfailurecouldbringdownthewholesystem, withallthecoststhatentails.Afewextraminutesspentinthepreparationandinstallationof anyaccessorycouldsavethousandsinthelongterm. CABLE JOINTS, CABLE TERMINATIONS, CABLE GLANDS, CABLE CLEATS FEEDER PILLARS, FUSE LINKS, ARC FLASH, CABLE ROLLERS, CUT-OUTS