Power Rating Table For TP90 (1) .TP90 Multi Core
Power Rating Table For TP90 (1) .TP90 Multi Core
POWER RATING
Table 1-1
Current Carrying Capacities of Multi-Cores 0.6/1kV Sheathed cable with TP-90 insulation at Ambient Air Temperature
40C (referenced to AS/NZS 3008.1.1:1998 Tables 10 + 13) FIXED INSTALLATION
Unenclosed
Spaced
Conductor
Size
mm
1.0
1.5
2.5
4.0
6
10
16
25
35
50
70
Note :
A
18
24
34
45
57
78
105
140
175
210
270
A
16
20
28
38
48
66
88
120
145
180
230
A
17
22
31
42
53
73
97
130
160
195
250
A
14
19
26
35
45
62
83
110
135
170
215
Enclosed
Non-metallic wiring enclosure in air
Touching
Page 1 of 5
A
13
17
24
33
42
59
79
110
130
160
200
A
12
16
22
29
38
53
70
98
115
140
175
Table 1-2A
Table 1-2B
Current Carrying Capacities of Multi-Core 0.6/1kV Sheathed cable with TP-90 insulation at Ambient Air Temperature 25C
(reference to AS/NZS 3008.1.1:1998 Tables 16) FLEXING
Conductor Size
Current-carrying capacity
mm
1.0
1.5
2.5
4.0
A
10
15
20
25
Current Carrying Capacities of Multi-Core 0.6/1kV Sheathed cable with TP-90 insulation at Ambient Air Temperature 40C
(reference to AS/NZS 3008.1.1:1998 Tables 15) FLEXING
Two-core
Conductor
Size
Exposed to Sun
mm
6
10
16
25
35
50
70
A
54
74
99
135
165
195
250
A
43
58
77
105
125
145
185
A
46
63
85
115
140
165
215
Notes
1) Where layers of flexible cable are accommodated on a drum, multiply the values by a appropriate factor in Table 1-5.
Page 2 of 5
A
37
50
66
88
105
125
155
Table 1-3
Derating Factors for variations in ambient temperature for cables in air (reference to AS/NZS 3008.1.1:1998 Table 27(1))
Ambient Temperature in C
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
75
1.35
1.28
1.21
1.14
1.07
1.00
0.91
0.82
0.72
0.60
0.49
0.37
-------
Conductor Temperature in C
80
1.31
1.25
1.19
1.12
1.06
1.00
0.92
0.84
0.76
0.66
0.56
0.45
0.27
-----
Page 3 of 5
90
1.26
1.20
1.15
1.10
1.05
1.00
0.94
0.88
0.81
0.73
0.65
0.57
0.47
0.34
0.19
Table 1-4
Derating Factors - for bunched circuits of single core cables in air or in wiring enclosures (reference to AS/NZS
3008.1.1:1998 Table 22)
Correction Factors
Number of Circuits
Arrangement of cables
1
Bunched in air
Bunched on a surface or
enclosed
Single layer on wall Touching
or floor
Spaced
Single layer on wall Touching
under ceiling
Spaced
10
12
14
16
18
---
---
---
---
---
---
---
---
1.00 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.48 0.45 0.43 0.41 0.39
0.38
1.00
1.00
0.95
0.95
0.70
0.90
0.61
0.85
0.85
0.94
0.81
0.85
0.79
0.90
0.72
0.85
0.75
0.90
0.68
0.85
0.73
0.90
0.66
0.85
0.72
0.90
0.64
0.85
0.72
0.90
0.63
0.85
0.71
0.90
0.62
0.85
0.70
0.90
0.61
0.85
0.70
0.90
0.61
0.85
0.70
0.90
0.61
0.85
0.70
0.90
0.61
0.85
0.70
0.90
0.61
0.85
0.70
0.90
0.61
0.85
Table 1-5
Derating Factors of spooled/winded cables (in accordance to AS/NZS 2008.1.1:1998 Table 15 & 16)
For conductor sizes 1.0mm to 4.0mm
Number of layers
1
2
3
Derating Factor
0.76
0.58
0.47
4
0.40
4
0.35
20 or
more
---
2
0.65
Page 4 of 5
3
0.45
Table 1-6
Correction Factors - for circuits of multi-core cables installed in trays, racks, cleats, or other supports in air (reference to
AS/NZS 3008.1.1:1998 Table 24)
Installation
Unperforated trays
Perforated trays
Unperforated trays
Unperforated trays
Perforated trays
Ladder supports
Notes :
1
0.97
0.97
0.97
0.97
0.97
0.97
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
Correction Factors
Number of circuits per tier or row
2
3
4
5
0.85
0.78
0.75
0.71
0.84
0.76
0.73
0.68
0.83
0.75
0.72
0.66
0.96
0.94
0.93
0.90
0.95
0.92
0.90
0.86
0.94
0.91
0.89
0.84
0.88
0.82
0.78
0.76
0.87
0.80
0.76
0.73
0.86
0.79
0.75
0.71
1.00
0.98
0.95
0.91
0.99
0.96
0.92
0.87
0.98
0.95
0.91
0.85
0.87
0.82
0.80
0.79
0.86
0.80
0.78
0.76
0.85
0.79
0.76
0.73
1.00
1.00
1.00
1.00
0.99
0.98
0.97
0.96
0.98
0.97
0.96
0.93
0.88
0.82
0.77
0.73
6
0.68
0.63
0.61
------0.73
0.68
0.66
------0.78
0.73
0.70
------0.72
2
1
1.00
1.00
0.88
0.91
0.81
0.89
0.76
0.88
0.72
0.87
0.70
---
1.00
0.91
0.88
0.87
0.86
---
Number of tiers or
rows of cable
supports
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
1) The vertical spacing of horizontal trays and ladder supports shall be not less than 300mm
2) The horizontal spacing of vertical trays mounted back to back shall be not less than 230mm
Page 5 of 5