Breaker Failure Protection: PSRC - K2 WG
Breaker Failure Protection: PSRC - K2 WG
PSRC K2 WG
An IEEE PSRC Report , Summary Update of Practices on Breaker Failure Protection, IEEE Transaction Power Apparatus and Systems, Vol. PAS-101, No. 3, pp 555-563 , March 1982
Why a Guide ?
Things have changed in 20 years. New Engineers need guidance. Breaker Failure Function being incorporated in multifunction relays.
PSRC K2
K2 Members
Roger Hedding, Chair S.Anderson Alex Apostlov John Appleyard Roy Ball George Bartok Ron Beazer Ken Behrendt Robert Beresh Martin Best Gustav Brunello Art Buanno Zeeky Bukhala
Arvind Chaudhary, Vice Chair Simon Chano Terry Crawley Randy Crellin Randy Cunico Albert N. Darlington Paul Drum Walt Elmore David Emigh Jon Ferraro Kelly Gardner Tony Giuliante George Gresko
K2 Members
Irwin Hassenwinkle Stan Horowitz Randy Horton Mohamed Ibrahim Bob Jackson Gerald Johnson Peter Kemp Tim Kern Shoukat Khan Mike Kloiber Gary Kobet Tom Lanigan Larry Lawhead Bill Lowe Vahid Madani Walter McCannon Mike McDonald Dean Miller
Pratap Mysore Mukesh Nagpal George Nail Russell Patterson Frank Plumptre Elmo Price Dan Reckerd Don Sevcik Charles Sufana Joe Uchiyama Sahib Usman Don Ware James Whatley Roger Whittaker Skip Williams Ray Young Rich Young
Assignment
This working group will investigate issues pertaining to breaker failure protection which will include : breaker failure mechanisms, fault detectors, breaker failure circuits, effect of bus configurations, effect of multifunction microprocessor relays, and the effect of modern breaker control schemes. Prepare a guide covering the application of breaker failure protection to power circuit breakers.
Timing Chart
PROTECTIVE RELAY TIME BREAKER INTERRUPT TIME 50BF CURRENT DETECTOR RESET TIME
FAULT CLEARED
MARGIN TIME TIME AUX TRIP RELAY TIME
LOCAL BACKUP BREAKER INTERRUPT TIME TRANSFER TRIP TIME REMOTE BACKUP BREAKER INTERRUPT TIME
Two Components
Current Detector
Detects current flow Pick up for minimum fault If phase current set above load current If ground current set above unbalance Drop out not delayed by dc offset Use 52a only if no current
Timer
Longer than it takes the breaker to clear a fault Shorter than the Critical Clearing Time plus some margin. Could be longer for Line to Ground Faults than for Three Phase Faults
Dictated by Transient Stability limit Somewhere between 7 and 30 cycles Results from Stability Study
Failure to Trip
Contacts do not open after trip circuit energized. Short or open in Trip coil Mechanical problem with breaker
Failure to Clear
Contacts open but fault not extinguished. Current continues to flow Mechanical or Dielectric problem Why auxiliary switches not reliable
62-2 Timer (Time Delay May be Zero Time) Re-Trip the Breaker
Use where current magnitude may not be enough to pick up current detector Transformers Generators Harmonic Filters
62-1 50BF 52a BFI OR AND Timer Breaker Failure Scheme Output
Ring Bus
Ring Bus
Separate Ct inputs into relay Careful of current distribution after one breaker opens in setting current detectors. Another Working group (K5) to look into this issue.
Relay
Relay
Relay
Trip
Fault Point
Design Considerations
Total Breaker Failure clearing time should be less than system stability limit. Independent of type of failure detected Should operate during loss of dc to breaker
Conclusions
BFP should operate only when desired Timer setting should allow adequate margin between backup breaker clearing and system critical clearing time. Multiple timers can be used for different types of faults Use auxiliary contacts as last resort for BFI.
Conclusions
Phase current detectors should be set above load to protect from scheme operating during testing. Seal in circuits should be used to insure breaker failure scheme does not drop out prematurely Care should be taken when applying breaker failure to ring bus and breaker and one half .
Questions ?