Generator Protection - F
Generator Protection - F
Abbas
(Section Manager - Electrical)
Fault Data
Three phase faults have the highest fault current.
Selectivity: Trip the minimal amount to clear the fault or abnormal operating condition
Speed: Usually the faster the better in terms of minimizing equipment damage and maintaining system integrity Simplicity: Less components simple wiring
Economics: Dont break the bank
25
Reactors - to limit fault current (series) or compensate for charge current (shunt)
VT and CT - to measure primary current and voltage and supply scaled down values to P&C, metering, SCADA, etc. Regulators - voltage, current, VAR, phase angle, etc.
27
GE Consumer & Industrial Multilin
Types of Protection
Overcurrent Uses current to determine magnitude of fault
Simple May employ definite time or inverse time curves May be slow Selectivity at the cost of speed (coordination stacks) Inexpensive May use various polarizing voltages or ground current for directionality
Relay closest to fault operates first Relays closer to source operate slower Time between operating for same current is called CTI (Clearing Time Interval)
CTI
50 +2 50 +2
Distribution Substation
29
GE Consumer & Industrial Multilin
(TOC) Coordination
t
Relay closest to fault operates first Relays closer to source operate slower Time between operating for same current is called CTI
CTI
Distribution Substation
Operate region lies above selected curve, while no-operate region lies below it
Inverse curves can approximate fuse curve shapes
Types of Protection
Differential
current in = current out Simple Very fast Very defined clearing area Expensive Practical distance limitations
Line differential systems overcome this using digital communications
1 pu
IP
CT-X CT-Y
IP
Differential
Note CT polarity dots This is a throughcurrent representation Perfect waveforms, no saturation
IS
IS
Relay
IR-X IR-Y
+1 1 + (-1) = 0
Current, pu
-1 DIFF CURRENT
2 pu
IP
2 pu
Fault
CT-X CT-Y
IP
Differential
Note CT polarity dots This is an internal fault representatio n Perfect waveforms, no saturation
X
IS IS
Relay
IR-X IR-Y
+2 2 + (+2) = 4
Current, pu
-2 DIFF CURRENT
Types of Protection
Voltage Uses voltage to infer fault or abnormal condition May employ definite time or inverse time curves May also be used for undervoltage load shedding
Simple May be slow Selectivity at the cost of speed (coordination stacks) Inexpensive
Types of Protection
Frequency Uses frequency of voltage to detect power balance condition May employ definite time or inverse time curves Used for load shedding & machinery under/overspeed protection
Simple May be slow Selectivity at the cost of speed can be expensive
Types of Protection
Power Uses voltage and current to determine power flow magnitude and direction Typically definite time
Complex May be slow Accuracy important for many applications Can be expensive
Types of Protection
Distance (Impedance)
Uses voltage and current to determine impedance of fault Set on impedance [R-X] plane Uses definite time Impedance related to distance from relay Complicated Fast Somewhat defined clearing area with reasonable accuracy Expensive Communication aided schemes make more selective
Protection Zones
1. Generator or Generator-Transformer Units 2. Transformers 3. Buses 4. Lines (transmission and distribution)
~
Generator XFMR Bus Line Bus XFMR Bus Motor
Std. 242: Buff Book Latest developments reflected in: C37.102: IEEE Guide for Generator Protection Std. 242: Buff Book C37.101: IEEE Guide for AC Generator Ground Protection C37.102: IEEE Guide for Generator C37.106: IEEE Guide for Abnormal Frequency Protection Protection for Power Generating Plants C37.101: IEEE Guide for AC Generator Ground Protection C37.106: IEEE Guide for Abnormal Frequency Protection for Power Generating These are created/maintained by the IEEE PSRC & IAS Plants They are updated every 5 years
32 Reverse Power
40 Loss of Excitation 51V voltage restraint 51G Ground O/C 87 Differential
46 Negative Sequence
51V voltage restraint 51G Ground O/C 87 Differential
Medium up to 12.5 MW
Large up to 50 MW
32 Reverse Power 40 Loss of Excitation 46 Negative Sequence 49 Thermal Overload 51V voltage restraint 51G Ground overcurrent 64 Ground Relay 87 Differential
Devices 27 / 59
Device 32
Device 40
Device 46
The function of generator backup protection is to disconnect the generator if a system has not been cleared by the primary protective device Time delays
Device 51V/21
Device 51G
Device 60
Monitors the availability of PT voltage. Blocks improper operation of protective relays and control devices in the event of a blown PT fuse
Conventional relaying approach analyzing variations in apparent impedance as viewed at generator terminals. Variation in impedance can be detected by impedance relaying and generator separated before the completion of one slip cycle
Device 78
Differential Protection
For rapid detection of generator to or -G faults. When NGRs are used, 87G should be used. Used for protection of larger generators Zone protection
Device 87
Frequency Protection
Significant load addition Sudden reduction in mechanical input power Loss of generation / Loss of load Underfrequency can cause: Higher generator load currents Overexcitation Turbine blade fatigue
Device 81
Temperature Protection
Resistance temperature detectors are used to sense winding temperatures. A long term monitoring philosophy that is not readily detected by other protective devices
RTDs
Tripping Methods
Factors of selection includes severity of fault, probability of Fault spreading & overspeeding, time required to resynchronize, effect on power system etc.
SIMULTANEOUS TRIP GENERATOR TRIP BREAKER TRIP MANUAL RUNBACK & TRIP AUTOMATIC RUNBACK MANUAL RUNBACK
SEQUENTIAL TRIP
MANUAL TRIP
It can be used on generators driven by steam, gas and hydraulic turbine. Any size of generator can be protected with the DGP.
A high degree of dependability and security is achieved by extensive self diagnostic routines and an optional redundant power supply.
Applications
For Small, Medium and Large Generator Protection Suitable for Variety of Prime-Movers - Gas, Steam, Hydro Turbines Most Commonly Used Protection Functions Packaged in a Standard Modular Case
THE DGP SYSTEM TAKES EIGHT CURRENT AND FOUR VOLTAGE SENSING INPUTS.
THE DGP SYSTEM INPUTS The input currents in terminals BH1, BH3, and BH5 (IAS, IBS, and ICS) are used
to process functions 46, 40, 32, and 51V. These currents can be derived from system side or neutral side CTs as desired. Either the system or neutral side CTs can be used for these functions if the Stator Differential (87G) function is enabled. Current inputs INS and INR are derived from the residual connections of the respective phase CTs.
The current inputs INS and INR are derived from the residual connections of the respective phase CTs and do not require dedicated neutral CTs.
Zero-sequence current at system and/or neutral side of the generator stator windings is calculated and then compared with the measured INS and/or INR values by the DGP as a part of the background self-test. The INR current is used to process the 51GN function DGP .If desired, a dedicated neutral CT can be used for the input INR.
The DGP phase voltage inputs can be wye or delta and are derived from the generator terminal voltage. VN is derived from the generator neutral grounding
DGP Monitoring
Present Values
GEN Simulator DGP PRESENT VALUES Station ID:MALVERN Generator ID:MODEL GENERATOR 10/28/93 14:37:23:446 IAS: 5696.0 A -014 DEGS VAN: 008.5 KV 000 DEGS IBS: 5488.0 A -142 DEGS VBN: 008.1 KV -118 DEGS ICS: 4864.0 A 104 DEGS VCN: 008.2 KV 122 DEGS IAR: 5680.0 A -014 DEGS IBR: 5456.0 A -142 DEGS ICR: 4880.0 A 104 DEGS NEGATIVE SEQ CURRENT: 08.1 % 3RD HARM PH: 00.1 % 3RD HARM N: 03.7% WATTS: +126.33 MWATT VARS: +041.95 MVAR INLET VLV: OPEN DIG IN 4: OPEN EXT VTFF: OPEN SAMPLING FREQ: 720.0 0000
GEN OFF-LIN: OPEN DIG IN 3: OPEN OSC TRIG: OPEN FREQ: 60.00
Currents Voltages Watts Vars Frequency Negative Sequence Current 3rd Harmonic Voltage Status of Digital Inputs
Fault Report
Gen Simulator DGP FAULT REPORT 0000
Prefault
Currents Voltages Watts Vars Frequency
Post Fault
Currents Voltages Trip Targets Operating Time
WATTS: +1888.5 KWATT VARS: +3777.0 KVAR 05:10:37.834 87G PHASE A ON 05:10:37.834 87G PHASE B ON
END