Generator Troubleshooting
Generator Troubleshooting
Unity Power Factor (pf 1)
Purely resistive load, i.e. heating, tungsten filament lighting, has a power
factor of one, (pf1), and contains very little Wattless (inductive) load, which
is power factor zero, (pf 0).
An AC Generator will deliver continuously the rated full load current at any
power factor between pf1 (unity) and 0.8. However, the prime mover,
(engine), is greatly affected by the power factor. At pf1, the kVA and kW are
equal; therefore the engine is supplying 20% more kW load at pf1, than at
pf 0.8. It is important, therefore, that this is taken into consideration, when
approaching 75% to 100% load current of the Generator, with a power
factor
higher than 0.8.
Lagging Power Factors
A Generator is designed to deliver the full load current at any power factor
between unity and 0.8 lagging. Certain loads have a power factor lower
than 0,8 lag, e.g. welding transformers; autotransformer, motor starting,
gas discharge lighting. A reduction in the full load (kVA), rating is required
for a continuous lagging pf lower than 0.8.
Leading Power Factors
Capacitive load e.g. some fluorescent lighting, and power factor correction
capacitor banks, produce leading power factor current. The latter is
required by the Electricity authorities to improve the customers lagging
power factor. The capacitor bank size is measured in kVAr (reactive).
A purely Capacitive load can cause the Generator control system, (AVR),
to loose control, creating voltage instability, and possible high voltage from
the Generator. This is due to the fact that, unlike most loads, which are pf1,
(unity) or lagging pf, a leading pf load current will cause the Generator
excitation voltage to decrease, as the load current increases.
Leading Power Factors
Eventually the control system will be unable to control the Generator
excitation level, and voltage instability will occur. The degree of instability is
determined by the kVAr size of the capacitors, relative to the kVA size of
the alternator.
Capacitive load can present a problem for mains failure (standby)
Generators. When the mains electricity supply fails, all motor, (inductive),
load is disconnected by the individual contactors.
Subsequently, when the Generator is connected to the system, the load
will mainly consist of lighting, and possibly power factor correction
capacitors. In this situation the AC Generator will see a very low, (leading),
power factor, and may become unstable, and/or generate high voltage.
Leading Power Factors
In order to prevent this situation, it is advisable to ensure that the
power factor correction capacitors are switched OFF when the
generator takes the initial load.
Further advice in this respect may be obtained from Cummins
Generator Technologies if required.
Resistances - measuring component values
When fault finding it is necessary to measure the resistance values of
components and windings, and compare them with known normal values,
in order to identify a faulty winding. The normal resistances of the windings
are given in the winding resistance charts, in the generator installation and
maintenance handbooks, service and maintenance section. Resistance
values above 10 ohms can be measured accurately with a multimeter.
Between 0.5 and 5 ohms a multimeter has a limited accuracy, and other
test methods may be adopted.
Resistances between 0.5 And 5 Ohms
The resistance value of a winding such as a brushless main rotor will be
between 0.5 and 3 ohms. A multimeter may not give an accurate enough
reading at these levels. If a Wheatstone Bridge Resistance Meter is not
available, an accurate measurement can be obtained by means of a
battery supply, using a Multimeter in series on the 10 Amps D.C. range.
Most Multimeters have this current range, or alternatively, a battery
charging Ammeter could be used instead).
Resistances between 0.5 And 5 Ohms
Using 6 volt battery cells the resistance of the winding can be
calculated i.e.