Basics of Low Voltage System & Circuit Breakers: A&D / BD-CD June 04
Basics of Low Voltage System & Circuit Breakers: A&D / BD-CD June 04
G
X’ MER X’ MER
ACB
ACB B C ACB ACB
Folienthema/Folie 1/Jahreszahl
TO TO TO TO TO TO
CCP MCC1 MCC2 ETP EM. UTILITY
LIGHT MCC
Folienthema/Folie 2/Jahreszahl
Voltage 440 Volts
%ge Impedance 16 %
Folienthema/Folie 3/Jahreszahl
Similarly the fault level at the generator terminal works out to be 8.7 kA
Folienthema/Folie 4/Jahreszahl
A&D / BD-CD June ‘ 04
Basics of Low Voltage System & Circuit Breakers
Folienthema/Folie 5/Jahreszahl
A&D / BD-CD June ‘ 04
Basics of Low Voltage System & Circuit Breakers
Folienthema/Folie 6/Jahreszahl
4. Any other points ….
Folienthema/Folie 7/Jahreszahl
Test sequence –
ICU = O – t – CO (t = 3 min)
ICS = O – t – CO – t - CO (t = 3 min)
Types of breakers …
Folienthema/Folie 8/Jahreszahl
A&D / BD-CD June ‘ 04
Basics of Low Voltage System & Circuit Breakers
Current limitation
in to Sentron VL
Folienthema/Folie 9/Jahreszahl
4 ms 10 ms t
Folienthema/Folie 10/Jahreszahl
5. Proper “Discrimination” possible
4 ms 10 ms t
What is “Cascading” ?
Folienthema/Folie 11/Jahreszahl
A&D / BD-CD June ‘ 04
Basics of Low Voltage System & Circuit Breakers
What is “Cascading” ?
VL160X, 100A, 40 kA
Folienthema/Folie 12/Jahreszahl
VF100, 100A, 18 kA
Isc = 35 kA
Cascading U p s tre a m
M C C B fra m e
B r.C a p .
(Ic u ) D o w n s tr e a m M C C B f r a m e
Chart V F100
18 kA
V L160x
40 kA
V L160x
40 kA
V L160
40 kA
V L250
40 kA
V L250
40 kA
V L400
45 kA
R e le a s e TM TM TM TM / E TU TM / E TU TM / E TU TM / E TU
R a t in g s 100A 100A 160A 160A 200A 250A 315A
V F100 TM 18 kA 100A
40 kA 100A
V L160x TM
70 kA 100A
40 kA 160A
V L160x TM
70 kA 160A
40 kA 160A
V L160 TM / E TU
70 kA 160A
40 kA 200A 40 kA
V L250 TM / E TU
70 kA 200A 50 kA
40 kA 250A 40 kA 40 kA
V L250 TM / E TU
70 kA 250A 50 kA 70 kA
Folienthema/Folie 13/Jahreszahl
45 kA 315A 45 kA 45 kA
V L400 TM / E TU
70 kA 315A 50 kA 70 kA
45 kA 400A 45 kA 45 kA 45 kA 45 kA
V L400 TM / E TU
70 kA 400A 50 kA 70 kA 70 kA 70 kA
45 kA 630A 45 kA 45 kA 45 kA 45 kA 50 kA 50 kA
V L630 TM / E TU
70 kA 630A 50 kA 70 kA 70 kA 70 kA 70 kA 70 kA
50 kA 800A 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA
V L800 E TU
70 kA 800A 50 kA 70 kA 70 kA 70 kA 70 kA 70 kA 70 kA
What is “Discrimination” ?
Folienthema/Folie 14/Jahreszahl
A&D / BD-CD June ‘ 04
Basics of Low Voltage System & Circuit Breakers
What is “Discrimination” ?
VL160X, 100A, 40 kA
Folienthema/Folie 15/Jahreszahl
VF100, 100A, 18 kA
Isc = 35 kA
Types of Discrimination
Folienthema/Folie 16/Jahreszahl
A&D / BD-CD June ‘ 04
Basics of Low Voltage System & Circuit Breakers
U p s t re a m B r. C a p .
Discrimination M CCB
fra m e
( Ic u )
D o w n s tr e a m M C B / M C C B f r a m e
Chart 5 S X4
10 kA
5 S X4
10 kA
5 S X4
10 kA
V F100
18 kA
V L160x
40 kA
V L160x
40 kA
V L250
40 kA
V L250
40 kA
R e le a s e TM TM TM TM TM TM TM / E TU TM / E TU
R a t in g s u p to 2 0 A 25 / 32A 40 - 63A 100A 100A 160A 200A 250A
V F100 TM 18 kA 100A 3 .8 k A 3 .0 k A 2 .1 k A
40 kA 100A 10 kA 9 .1 k A 4 .8 k A
V L160x TM
70 kA 100A 10 kA 9 .1 k A 4 .8 k A
40 kA 160A 10 kA 9 .1 k A 4 .8 k A 12 kA
V L160x TM
70 kA 160A 10 kA 9 .1 k A 4 .8 k A 12 kA
40 kA 200A 10 kA 10 kA 6 .5 k A 18 kA 25 kA
V L250 TM / E TU
70 kA 200A 10 kA 10 kA 6 .5 k A 18 kA 25 kA
40 kA 250A 10 kA 10 kA 6 .5 k A 18 kA 25 kA 25 kA
V L250 TM / E TU
70 kA 250A 10 kA 10 kA 6 .5 k A 18 kA 25 kA 25 kA
45 kA 315A 10 kA 10 kA 10 kA 18 kA 40 kA 40 kA 32 kA 26 kA
V L400 TM / E TU
70 kA 315A 10 kA 10 kA 10 kA 18 kA 40 kA 40 kA 32 kA 26 kA
Folienthema/Folie 17/Jahreszahl
45 kA 400A 10 kA 10 kA 10 kA 18 kA 40 kA 40 kA 32 kA 26 kA
V L400 TM / E TU
70 kA 400A 10 kA 10 kA 10 kA 18 kA 40 kA 40 kA 32 kA 26 kA
45 kA 630A 10 kA 10 kA 10 kA 18 kA 40 kA 40 kA 40 kA 40 kA
V L630 TM / E TU
70 kA 630A 10 kA 10 kA 10 kA 18 kA 40 kA 40 kA 40 kA 40 kA
50 kA 800A 10 kA 10 kA 10 kA 18 kA 40 kA 40 kA 40 kA 40 kA
V L800 E TU
70 kA 800A 10 kA 10 kA 10 kA 18 kA 40 kA 40 kA 40 kA 40 kA