1 Electrical Systems
1 Electrical Systems
SYSTEMS
1. GENERAL
GENERATORS
STORAGE BATTERIES
GENERATORS
DIRECT
CURRENT
a
current which flows at a
constant time rate and in the
same direction.
ELECTRIC
UNIT
RESISTANCE
OF
AUTOMATIC
INSTANTANEOUS
DEMAND CONTROL also called rate
control, it is an automated version of
the demand metering alarm system,
where it automatically disconnects or
reconnects loads as required.
IDEALCURVE
CONTROL
This
controller operates by comparing the
actual rate of energy usage to the ideal
rate, and controls KW demand by
controlling the total energy used within
a metering interval.
FORECASTING SYSTEMS are
computerized
systems
which
continuously forecast the amount of
energy remaining in the demand
interval, then examine the status and
priority of each of the connected loads
and decide on the proper course of
action.
POWER
SOURCE
WATTMETER
LOAD
WM
VOLTAGE
LEADS
KWH METERS To
measure energy,
the factor of time is
introduced, such
that; energy =
power x time. A-C
electric meters are
basically small
motors, whose
speed is
proportional to the
power being used.
The number of
rotations is counted
on the dials which
are calibrated
directly in kilowatthours.
R1
10 amp
R2
10 amp
R3
ELEC
SOURCE
10 amp
10 amp
R4
R5
CIRCUIT IN SERIES
R = R1 + R2 + R3 + R4 +
R5
3 amp
1 amp
+
ELECTRICA
L SOURCE
R1
1 amp
R2
R3
CIRCUIT IN PARALLEL
1
R=
1/R1 + 1/R2 + 1/R3
1 amp
GENERALLY
15, 20A
SIZE REQUIRED
FOR ITEM FED
LTG
SINGLE ITEM
Appliance
Branch
Circuit
supplies outlets intended for feeding
appliances. Fixed lighting is not
supplied.
Branch Circuit
The portion of an electrical
system extending from the final
overcurrent device protecting a
circuit to the outlets served by
the circuit
Distribution Panel
A panel for distributing
power to other panels or to
motors and other heavy
power-consuming loads.
Controls, distributes and
protects a number of similar
branch circuits in an
electrical system
Low-Voltage
Of or pertaining to a circuit in which alternating
current below 50 volts is supplied by a step-down
transformer form the normal line voltage used in
residential systems to control doorbells,
intercoms, heating and cooling systems and
remote lighting fixtures. Low-voltage circuits do
not require a protective raceway
C3
C3
20 amp
2.
Range
Ref
C1
C2
20 amp
KIT
DINE
C4
3. Convenience receptacles in an
area shall be wired to at least
two different circuits so that in
case of failure in any one of the
circuits, the entire area will not
be deprived of power.
4. General purpose branch circuits
shall be rated at 20 amperes
wired
with
No.
12
AWG
minimum. Switch legs may be
No. 14 AWG if the lighting load
permits.
5. Limit the circuit load for lighting
and small appliances on 15 amp
and 20 amp circuit loads and on
15 and 20 amp overcurrent
devices respectively.
SWITCH
110 V
220 V
110 V
A B C
A
B
C
A-B 220V
A-C 220V
B-C 220V
MOTOR
Four-Wire Three-Phase AC
A N B C
220V
220V
110V
220V
110V
110V
Service
The supplying of utilities required
or demanded by the public
Substation
An auxiliary power station
where electrical current is
converted or where voltage is
stepped up or down
Line Drop
The decrease in voltage between
two points on a power line,
usually caused by resistance or
leakage along the line
Service Entrance Conductor
The portion of a service conductor extending
from a service drop or service lateral to the
service equipment of a building
Service Drop
The overhead portion of service
conductors extending from the
nearest utility pole to a building
Service Lateral
The underground portion of service
conductors extending from a main
power line or transformer to a
building
Feeder
Watt-Hour Meter
A meter for measuring and recording the
quantity of electric power consumed with
respect to time
Transformer Vault
A fire-rated room housing
a transformer and
auxiliary equipment for a
large building
Standby Generator
For providing emergency power
during a power outage.
Uninterruptible Power Supply
An emergency system designed
to provide pwer automatically and
instantaneously
Switchgear Room
Contains the service
equipment for a large
building
Service Equipment
Equipment necessary for
controlling, metering and
protecting the electric
power supply to a builidng
Switchboard
One or a group of panels on
which are mounted switches,
overcurrent devices,
metering instruments and
buses
Unit Substation
A freestanding enclosure
housing a disconnect
switch, a step-down
transformer and
switchgear
Lightning Rod
Any of several conducting rods installed at the
top of a structure and grounded to divert
lightning away from the structure. Also called
air terminal
Lightning Arrester
A device for protecting electric equipment from
damage by lightning or other high-voltage
currents, using spark gaps to carry the current
to the ground without passing through the
device
Spark Gap
A space between two terminals or electrodes
across which a discharge of electricity may pass
at a prescribed voltage
Servcie Drop
The overhead portion of service conductors extending
from the nearest utility pole to a building
Servcie Lateral
The underground portion of service conductors extending
from a main power line or transformer to a building
Servcie Entrance Conductor
The portion of a service conductor extending from a service
drop or service lateral to the service equipment of a building
Watt-Hour Meter
Measures and records the quantity of electric power
consumed with respect to time. Supplied by the public utility,
it is always placed ahead of the main disconnect switch so
that it cannot be disconnected
For multiple-occupancy buildings, banks of meters are
installed so that each unit can be metered
independently
Grounding Rod or Electrode
Is firmly embedded in the earth to establish a ground
connection
To panelboards
UTILIZATION
EQUIPMENT
Service Switch
The main disconnect for the entire
electrical system of a building
except for any emergency power
systems
Panel
A board on which are
mounted the switches, fuses
and circuit breakers for
controlling and protecting a
number of similar branch
circuits installed in a cabinet
and accessible from the front
only. Also called a
panelboard.
Bus
A heavy conductor, usually in the form of a
solid copper bar, used for collecting, carrying
and distributing large electric currents. Also
called a busbar
Grounded Conductor
Any conductor of an electrical system
intentionally connected to a ground
connection
Grounding Electrode
A conductor, as a metal ground rod,
ground plate or cold-water pipe, firmly
embedded in the earth to establish a
gorund connection
Fuse
A device containing a strip or
wire of fusible metal that melts
under the heat produced by
excess current thereby
interrupting the circuit
Circuit Breaker
A switch that automatically interrupts an electric
circuit to prevent excess current from damaging
apparatus in the circuit or from causing a fire. A
circuit breaker may be reclosed and reused
without replacement of any components. Also
called a breaker.
Ground Wire
A conductor connecting
electric equipment or a
circuit to a ground
connection. Also called a
grounding conductor
BLOCK DIAGRAM
A horizontal single line
diagram of the
buildings electrical
system from the
incoming service to the
utilization items at the
end of the system
where the major
electrical components
are shown as blocks or
rectangles.
HIGH-VOLTAGE
PRIMARY FEEDERS
2,400, 4,160, 7,200
OR 13,200 VOLTS
SECONDARY SERVICE MAIN
FEEDERS
CONDUCTORS
MAIN
TRANSFORMER
SWITCH
VAULT
120/208 OR BOARD
120/240 OR
SWITCHES
227/480 VOLTS
TRANSFORMER
FUSES
DISTRIBUTION
PANELS
RECEPTACLES
LIGHTING
MOTOR
PANELS
LARGE
MOTOR
LIGHTING/
APPLIANCE
PANELS
BRANCH
CIRCUIT
SMALL
MOTORS &
CONTROL
SINGLE LINE
DIAGRAM
When electrical
symbols are
used in lieu of
the blocks, it is
called a one
line or a
single line
diagram.
ELEVATORS
PP
MR
MACHINE
ROOM
ROOF
LP
LEFT
RISER
5A
5B
5C
4A
4B
4C
3A
3B
3C
2B
2C
RIGHT RISER
1A
LP
1B
1C
LOBBY
SPARE
M.C.C.
MACHINE ROOM
FIRE ALARM
PANEL
STAIR
AND EXIT
LPSE
PANEL
M METERING
FA
RISER
DIAGRAM
Is a vertical line
diagram of the
major electrical
components of
the buildings
electrical
system
presented
showing the
spatial relations
between
components.
Engine-Generator
Sets
are
machines
intended
to
produce
electricity and composed of three
components: the machine and its
housing (if any), fuel storage tank
and the exhaust facilities.
EMERGENCY WIRING
USING THE BATTERY
Small
emergency
connected direct to
battery
SYSTEMS
appliance
a storage
CONDUCTOR
SIZES
AWG/MCM STANDARD
All conductor sizes from No. 16 to
No. 0000 (also designated 4/0) are
expressed in AWG.
Beyond AWG No. 4/0, a different
designation, MCM (or thousand
circular mil) is used. In this
designation, the smallest MCM size is
250 MCM or and the biggest is
500 MCM.
A circular MIL is an artificial area
measurement, representing the
square of the cable diameter (diam2)
when the diameter is expressed in
mils (thousands of an inch). Thus a
solid conductor inch in diameter is
500 mils in diameter, or 250,000
circular mils in area, (500)2 or 250
MCM; thus;
CM/1000 = diam2 = (500)2/1000
= 250,000/1000 = 250 MCM
In the metric system, conductor sizes
are given simply as the diameter in
CONDUCTOR AMPACITY
TYPES OF CABLES
Armored Cable (Type AC) a
fabricated assembly of insulated
conductors enclosed in flexible
metal sheath.
Metal Clad Cable (Type MC) a
factory assembled cable of one or
more conductors each individually
insulated and enclosed in a metallic
sheath of interlocking tape of a
smooth or corrugated tube.
Mineral Insulated Cable (Type MI)
a factory assembled conductor/s
insulated with a highly compressed
refractory
mineral
insulation
enclosed in a liquid and gas tight
continuous copper sheath.
Non-Metallic
Sheathed
Cable
(Type NM or NMC) also known by
the trade name ROMEX, is a factory
assembly of two or more insulated
conductors having a moisture
resistant, flame retardant, and nonmetallic material outer sheath.
Underground
Feeder
andtape.
Branch
Circuit Cable (Type UF) a moisture
resistant cable used for underground
connections including direct burial in
the ground as feeder or branch
circuit.
Service Entrance Cable (Type SE or
USE) a single or multi-conductor
assembly provided with or without
an overall covering primarily used
for service wire.
Power and Control Tray Cable (Type
TC) a factory assembled two or more
insulated conductors with or without
associated bare or covered grounding
under a metallic sheath and is used for
installation in cable trays, raceways, or
where supported by wire.
3.2 INSULATORS
INSULATORS are materials which
prevent the flow of electrons
through them.
TYPES OF INSULATORS
General Wiring
Trade name
Moisture-&
resistant
rubber
Type
Letter
heat-
Thermoplastic
Moisture-resistant
thermoplastic
Heat-resistant
thermoplastic
Maximum
Operating
Temperatur
e
Application
Provisions
RHW
75O C
167O F
60O C
140O F
Dry locations
TW
60O C
140O F
THHN
90O C
194O F
Dry locations
Moisture-&
resistant
thermoplastic
heat-
THW
75O C
167O F
Moisture-&
resistant
thermoplastic
heat-
THWN
75O C
167O F
XHHW
90O C
194O F
75O C
167O C
Dry locations
Wet
locations
SA
90O C
194O F
Dry locations
Silicone-asbestos
3.3 CONDUITS
CONDUITS are circular raceways
used to enclose wires and cables
and are of metal or plastic (PVC).
To
protect
the
enclosed
conductors from mechanical injury
and chemical damage.
To protect people from shock
hazards by providing a grounded
enclosure.
To provide a system ground path.
To
protect
the
surroundings
against fire hazard as a result of
overheating or short circuiting of
the enclosed conductors.
To support the conductors.
Convenience
Outlet
or
Attachment Cap - the complete
set-up
which
establishes
connection
between
the
conductor of the flexible cord and
the
conductors
connected
permanently to the receptacle.
b) Disconnecting or isolating
switches are intended for
disconnecting or isolating
circuits; used for circuits rated
at more than 600 volts.
d) Electrolier or multi-circuit
switches are used for the
control of lights in multi-lamp
fixtures so that one lamp or set
of lamps may be turned on
alone or in combination with
other lamps.
e) Momentary contact switches
are used where it is desired to
connect or cut-off a circuit for
only a short duration. The
switch is provided with a spring
so that it will return to its
original position as soon as the
handle or button is released.
f) Dimmer switches a rheostat
[1] or similar device for
regulating the intensity of an
electric light without
appreciably affecting spatial
distribution. Also called a
dimmer.
SPECIAL SWITCHES
1. Time Controlled Switches This
device comprises a precision low
speed miniature drive motor
(timer) to which some type of
electric contact-making device is
connected.
2. Remote Control (RC) Switches A
contactor[1], or more
specifically, a relay[2], that
latches after being operated
wireless from a distance.
3.Air Switch a switch in which the
interruption of a circuit occurs in
air.
4. Knife Switch a form of air
switch in which a hinged copper
blade
is placed between two
contact clips.
3.8
OVER-CURRENT
CIRCUIT
PROTECTIVE DEVICES are
devices whose sole purpose is to
protect insulation, wiring, switches
and
other
apparatus
from
overheating or burning, due to
overloads, to faults or to short
circuits, by automatically cutting off
the circuit.
GROUND
FAULT
CIRCUIT
INTERRUPTERS (GFCI or GFI) is
an over current protective device
that will provide ground fault
protection as well as function as an
ordinary circuit breaker.
4. WIRING SYSTEMS
4.1 WIRING METHODS
KNOB AND TUBE WIRING an
obsolete wiring system consisting
of single insulated conductors
secured to and supported on
porcelain knobs and tubes. When
wires run through walls, they are
inserted into a nonmetallic fire
resistant
tubing called
a loom.
RIGID METAL
CONDUIT
WIRING
is the best and most expensive
among the usual type of wiring. Its
advantages are:
1. it is fireproof;
2. moisture proof;
3. it is mechanically strong so that
nails cannot be driven through it
and it is not readily deformed by
blows;
4. it resists the normal action of
cement when embedded in concrete
or masonry.
FLEXIBLE
METAL
CONDUIT
WIRING Its installation is much
easier and quicker than that of rigid
metal conduits. Unlike the rigid
conduits which come in short
lengths of 10 ft. (3 M), flexible
metal conduit wiring comes in
length of 25 ft 250 ft (8 M 83 M)
depending on the size of the
conduit.
ARMORED CABLE WIRING (BX
WIRING) consists of rubber or
thermoplastic
covered
wire
protected from injury to a certain
extent from dampness by one or
two layers of flexible steel armor.
SURFACE
METAL
RACEWAY
WIRING the wires are supported
on a thin sheet steel casing. The
raceway is installed exposed, being
mounted on the walls or ceiling.
Metal raceways must be continuous
from outlet to outlet or junction box,
designed especially for use with
metal raceways.
PRE-WIRED
CEILING
DISTRIBUTION SYSTEMS are
ceiling raceways that are pre-wired in
the factory and plugged in where
required.
ELECTRICAL SYMBOLS
FEEDER
BRANCH CIRCUIT-CEILING/WALL
BRANCH CIRCUIT-FLOOR
3&4 WIRES CIRCUIT NO.
MARK INDICATES 2 WIRES
CROSSING WIRES
LAMP HOLDER
PUSH BUTTON
PS
C
BELL
CLOCK OUTLET
DROP CORD OUTLET
BUZZER
CH
CHIME
FAN OUTLET
ANNUNCIATOR
CONNECTING WIRES
RADIO OUTLET
LIGHTING PANEL
FLOOR OUTLET
POWER PANEL
RECESSED CEILING OUTLET
DASH INDICATES SHAPE OF
FIXTURE
FUSE
FLUORESCENT LAMP
RANGE OUTLET
SPECIAL PURPOSE OUTLET
ref
REFRIGERATOR OUTLET
WATT-HOUR METER
TRANSFORMER
JUNCTION BOX
GROUND
ELECTRICAL REGULATIONS
BY PD 1096
Property line
2.3
10 m
7.5 m
2.4
Secondary, neutral and service lines shall have a minimum
vertical
clearance of 7.5 m from the crown of the road pavement
when
crossing the highway and from the top of the shoulder or
sidewalk
Towers and
others and their guys and braces measured from the
nearest
parts of the objects concerned:
A. From Fire Hydrants, not less than 5 m.
B. From the Street Corners, where hydrants are
located at street corners, poles and towers
shall
not be set so far from the corners as to make
necessary the use of flying taps which are
inaccessible from the poles.
C. From Curbs, not less than 150 mm
measured from
the curb away from the roadway.
5 m
150 mm
Pole
4.1 Conductors of more than 300 volts to ground shall not be carried
along or
near the surface of the buildings unless they are guarded or
made
inaccessible.
4.2 To promote safety to the general public and to employees not
authorized
to approach conductors and other current-carrying parts of
electric supply
lines, such parts shall be arranged so as to provide adequate
clearance
from the ground or other space generally accessible, or shall be
provided
with guards so as to isolate them effectively from accidental
contact by
such persons.
4.3 Undergrounded metal-sheathed service cables, service conduits,
metal
fixtures and similar noncurrent-carrying parts, if located in urban
districts
and where liable to become charged to more than 300 volts to
ground,
Horizontal
Clearance in
Meters
Vertical Clearance
in Meters
1.0
2.5
8,700 to 15,000
volts
2.5
2.5
15,000 to 50,000
volts
3.0
3.0
Clearance of line
conductors from -
Communication LInes
Supply LInes
In general
On jointly used
poles
In general (0 to
8700 volts)
On jointly used
poles (0 to 8700
volts)
Exceeding 8700
volts, add for each
1000 volts of excess
75 mm
75 mm
75 mm
75 mm
6.25 mm
75 mm
75 mm
150 mm
150 mm
10 mm
75 mm
150 mm
150 mm
150 mm
10 mm
75 mm
150 mm
300 mm
300 mm
10 mm
Lightning protection
wires parallel to line:
surfaces of cross
arms
75 mm
75 mm
75 mm
75 mm
5 mm
Lightning protection
wires parallel to line:
surfaces of poles
75 mm
125 mm
75 mm
125 mm
5 mm
1 m
500mm
Service Drop Conductor
1.2 m 300 volts
Highest point
platform
5.50 m
3m
protecto
r
3m
existing service
drop conductors or any other over-head wiring; nor shall such wiring
be
installed above the following:
a. Swimming and wading pools and the area extending
3m
outward horizontally from the inside of the walls of
the pool.
3
b. Diving Structures
mplatforms
c. Observation stands, towers or
Service
drop
conductor
Swimming
pool
and
window openings shall be safeguarded from fires originating in
oilinsulated transformers installed on, attached to, or adjacent to a
building
or combustible material. Space separations, fire-resistant
barriers and
enclosures which confine the oil of a ruptured transformer tank
are
recognized safeguards. One or more of these safeguards shall be
applied
according to the degree of hazard involved in cases where the
transformer
installation presents a fire hazard. Oil enclosures may consist of
fireresistant dikes, curbed areas or basins, or trenches filled with
coarse,
Exterior Oil-insulated
crushed stone. Oil enclosures shall be provided with trapped
Transformer
drains in
cases where the exposure and the quantity of oil involved Trench
are
all
such that
around
removal of oil is important.
300mm
Combustible ceiling
Dry-type transformer
112-1/2 Kva or less 3.70 m
Transformer more
than 35,000 volts
1.85 m
as follows:
1. NOT OVER 112-1/2KVA TOTAL CAPACITY. The provisions for
transformer
vaults specified in Section 9.3 of this Rule apply except that the
vault may
be constructed of reinforced concrete not less than 100mm thick.
2. NOT OVER 600 VOLTS. A vault is not required provided suitable
arrangements are made where necessary to prevent a transformer
oil fire
igniting other materials, and the total transformer capacity in one
location
does not exceed 10 KVA in a section of the building classified as
> 100mm thick
reinforced is
combustible, or 75 KVA where the surrounding
structures
concrete vault
classified as
fire-resistant construction.
oil insulated transformer
< 112-1/2 KVa
Floor:
100mm thick
2-1/2 hours fire rating
have
roughly half of the total area of openings required or ventilation in
one or more
openings near the floor and the remainder in one or more openings in
the roof or in the sidewalls near the roof; or all of the area required for
ventilation may be provided in one or more openings in or near the
roof.
3. SIZE. In the case of vaults ventilated to an outdoor area without
using ducts or flues the combined net area of all ventilating openings
after deducting the area occupied by screens, grating, or louvers,
shall be not less than 0.006 sqmm per KVA of transformer capacity in
service, except that the net area shall be not less than 0.1 sqm for
any capacity under 50 KVA.
4. COVERING. Ventilation openings shall be covered with durable
gratings, screens, or louvers, according to the treatment requirement
required in order to avoid unsafe conditions.
5. DAMPERS. Where automatic dampers are used in the ventilation
openings of vaults containing oil-insulated transformers, the actuating
device should be made to function at a temperature resulting from
fire and not a temperature which might prevail as a result of an
overheated transformer or bank of transformers. Automatic dampers
should be designed and constructed to minimize the possibility of
12.Emergency Systems
1. The provisions of this Section shall apply to the installation,
operation and maintenance of circuits, systems and equipment
intended to supply illumination and power in the event of failure of
the normal supply or in the event of accident to elements of a
system supplying power and illumination essential for safety to life
and proper where such systems or circuits are required by the Fire
Code, or by any government agency having jurisdiction.
Emergency systems are generally installed in places of assembly
where artificial illumination is required, such as buildings subject to
occupancy by large numbers of persons, hotels, theaters, sports
arenas, hospitals and similar institutions. Emergency systems
provide power for such functions as refrigeration, operation of
mechanical breathing apparatus, ventilation essential to maintain
life, illumination and power for hospital room, fire alarm systems, fire
pumps, industrial processes where current interruption would
produce serious hazards, public address systems and other similar
functions.
2. All requirements of this Section shall apply to emergency systems.
6. Current supply shall be such that in the event of failure of the normal
supply to or within the building or group of buildings concerned,
emergency lighting or emergency power, will be immediately
available. The supply system for emergency purposes may be
composed one or more of the types of systems covered in Section
12.7 to Section 12.10 of this Rule. Unit equipment in accordance with
Section 12.21 shall satisfy the applicable requirements of this Section.
Consideration must be given to the type of service to be rendered;
whether for short duration, as for exit lights of a theater, or for long
duration, as for supplying emergency power and lighting during long
periods of current failure from trouble either inside or outside the
buildings, as in the case of a hospital.
Assignment of degree of reliability of the recognized emergency
supply system depends upon the careful evaluation of the variables of
each particular installation.
7. A storage battery of suitable rating and capacity shall supply, by
means of a service installed according to Section 200 of the PEC and
maintained at not more than 90 per cent of system voltage, the total
load of the circuits supplying emergency lighting and emergency
power for a period of at least hour.
light
actuated device approved for the purpose.
21. In hospital corridors, switching arrangements to transfer corridor
lighting in
patient areas of hospitals from overhead fixtures to fixtures designed
to provide
night lighting maybe permitted, provided that the switching system
is so
designed that switches can only select between two sets of fixtures
but cannot
extinguish both sets at the same time.
22.The branch circuits over current devices in emergency circuits shall
be
accessible to authorized persons only.
23. Where permitted by the authority having jurisdiction, in lieu of other
methods specified elsewhere in this Section, individual unit
equipment for emergency illumination shall consist of:
a. Battery
b. Battery charging means, when a storage battery is used
c. One or more lamps, and
d. A relaying device arranged to energize the lamps
maintain, at not less than 90 per cent of rated lamp voltage, the total lamp
load associated with the unit for a period of at least hour. Storage
batteries, whether of the acid or alkali type, shall be designed and
constructed to meet the requirements of emergency service. Lead-acid
type storage batteries shall have transparent jars.
Unit equipment shall be permanently fixed in place and shall have all wiring
to each unit installed in accordance with the requirements of any of the
wiring methods discussed in Chapter II of the PEC. They shall not be
connected by flexible cord. The supply circuit between the unit equipment
and the service, the feeders or the branch circuit wiring shall be installed
as required by Section 12.17. Emergency illumination fixtures which obtain
power from a unit equipment which are not part of the unit equipment shall
be wired to the unit equipment as required by Rule 5257 of the PEC and in
accordance with the one of the wiring methods described in Chapter II of
the PEC.
13.Effectivity
1. All primary and secondary supply lines already existing shall comply with
the provisions of this Rule within two (2) years from the effectivity of this
Rule.
2. Transformers to be installed on, attached to, or in buildings shall comply
with the requirements of this Rule. Transformer installations already
existing shall comply with the requirements within two (2) years from the
effectivity of this Rule.
THANK YOU