Condenser Surface: Hotwell Condensate Sump
Condenser Surface: Hotwell Condensate Sump
It was not found pitingo advanced corrosion on the plates of the body princpal.
It can be seen that there is a thin layer of rust beginning to manifest.
Most of the corrosion found comes from area where the welds made.
It has been found in some severe corrosion more stiffeners near the transition
Zana.
CONDENSER SURFACE
Tube Bundle
CONDENSER SURFACE
WATER BOXES
It has been found that the water boxes are in perfect condition.
No discontinuities found in the epoxy coating.
It is consultation with the manufacturer on the installation of sacrificial anodes and
performance, since coatings are normally submerged generally try spark test
unless they have additional protection.
Tube sheets is in perfect condition.
It has been found dust and dirt at the bottom of the boxes, since the provisional
coverage does not prevent the passage of rainwater and dust.
CONDENSER SURRFACE
Neck
It was found in the lower faces greater than the hot well corrosion due to
temporary accumulation of water sometime an assembly.