Chapter 222
Chapter 222
Chapter 2:
ECEg4241
Illumination
Adigrat University
Department of Electrical & Computer Engineering
[email protected]
@ 2009 E.C
Introduction
In ancient times, much of the indoor work done by humans
depended upon daylight being available to light the interior.
Today almost all buildings have electric lighting installed and
we automatically assume that we can work indoors or out of
doors at any time of the day or night, and that light will
always be available.
Good lighting is important in all building interiors:
helps work to be done efficiently and safely.
creates pleasant and comfortable surroundings.
The fundamental goal of artificial lighting design:
to provide sufficient light for the performance of visual
tasks to enable the person to do these tasks efficiently and
accurately
to create a comfortable environment with a minimum of
Contd
Size of object
the larger the object the more easily it can be seen.
Visual acuity is a measure of the smallest detail that can
easily be seen.
It is a function of the visual angle, that is, the angle
subtended at the eye by the object.
By bringing a small object closer to the eye, a person is
increasing the visual angle in order to see it more clearly.
Increasing lighting levels will markedly increase visual
acuity.
Contd
Brightness of the object
depends both on the amount of light striking an
object and the proportion of the light that is
reflected from it in the direction of the eye.
Naturally, a dark-colored object reflects less light
and is harder to see than a light-colored object
with the same lighting levels.
Therefore, a dark object requires more lighting for
it to be seen as clearly as a light object.
Contd
Contrast
equally important in clearly seeing an object is the
contrast between it and its immediate background.
As an example, the print on this page is dark
lettering against a near white background. If the
same printing were on dark gray paper, then the
printing would be harder to see.
Where poor contrast conditions cannot be avoided,
higher lighting levels are required to clearly see an
object.
Contd
Time
it requires time for the eye to properly see an object.
The longer the time available, the greater the detail
the eye can see. Conversely, more light is required
for rapid seeing.
In the case of a moving object, the time factor
particularly important.
Higher lighting levels make moving objects appear to
be moving more slowly.
Lighting Terminologies and Basic
Units
Luminous Flux
Luminous Intensity
Illuminance
Luminance
Color rendering and CRI
Luminous Flux (measured in Lumens)
Is the amount of light emitted by a light source (is
measure of the total power of light emitted)
is the quantity of the energy of the light emitted per
second in all directions.
One lumen is defined as the luminous flux of light
produced by a light source that emits one candela
of luminous intensity over a solid/spatial angle of
one steradian. Steradianis a unit solid angle.
Steradian is the spatial angle that limits the surface
area of the sphere equal to the square of the radius. Steradian
This is actually one steradian.
For a general sphere ofradiusr, any portion of its
surface with areaA=r2subtends one steradian.
The value of the solid angle is numerically equal to
the size of that surface area divided by the square of
the radius of the sphere.
E.g. A sphere has total of 2
steradian, because the surface
area of a sphere is 2R2
Luminous Flux contd
Typical Values
Candle 12lm
60W incandescent
750 lm
lamp
1WLED 130 lm
luminous intensity (I)-measured in lumen
per steradian also called candela (cd)
describes the quantity of light that is
radiated in a particular direction.
Luminous intensity of a source is
luminous flux per unit solid angle in a
given direction.
If the point light source emits
lumens into a in spatial
small candela (cd),
angel
the luminous intensity is
This is important to
remember when designing
a lighting layout using
incandescent lamps.
The normal end of life is reached when the filament wire breaks or
burns through at its thinnest point. Thus, the light output and the life
of a lamp are very interdependent.
For a specific wattage and voltage rating, a lamp can be designed for
a higher light output, but only at the expense of its rated life.
The type of lamps we will discuss are those most often used for
general lighting applications in buildings.
General-Service Lamps
Reflectorized Lamps
Tungsten-halogen Lamps
General-Service Lamps:
This is the most familiar type, as
they are used extensively in our
homes. They have either the type A
or PS shape bulb, with inside frosted,
white silica, or clear finishes, and
screw bases.
Wattage ratings range from 10 to
1500 watts.
Reflectorized Lamps:
These lamps combine in one unit the light
source and a very efficient sealed-in
reflector.
There are two types designated PAR and
R.
The PAR lamp has a molded reflector
to which a separate lens is then
attached.
The R lamp uses a less expensive, one-
piece blown-glass bulb, which can
result in a less accurate beam pattern
than for the molded type.
Both types can have either spot
(narrow) or flood (wide) beams.
Wattages for the type R range from 30
to 1000 watts, and for the type PAR
they range from 75 to 1000 watts.
Tungsten-halogen Lamps:
These lamps are a high-pressure incandescent lamp containing a
halogen gas such as iodine which allows the filament to be operated
at a higher temperature than an incandescent lamp, increasing its
efficacy.
These lamps are sometimes referred to as quartz halogen lamps, as
the envelope is almost always made not from glass, but from quartz,
which can better withstand the high temperatures at which these
lamps operate (although some lower wattage lamps that do not
generate too much heat, use 'hard glass'. This is a cheaper material
which has thermal properties between soda glass and quartz). They
have a long tubular quartz envelope, as shown below.
Contd
Inside the bulb, the high-temperature chemical reaction
involving tungsten and the halogen gas (iodine) recycles
evaporated particles of tungsten back onto the filament
surface through the so called halogen cycle.
This effectively reduces the deposits of the tungsten on the
envelope surface, which in turn increases the maintenance of
light over the life of the lamp and allows for a rated life of
2000 hours.
The double-ended type of lamp also has the advantage that it
can be easily designed for operation at higher voltages. For the
higher voltages, the filament diameter can remain the same,
and instead the filament length can be increased (a longer tube)
to provide the required higher filament resistance.
A major application for these lamps is floodlighting.
Partial Listing of Tungsten-halogen
Lamps
PAR and R tungsten-
halogen lamps are
another recent
development.
These lamps combine the
higher efficacy and longer
life of the low-voltage
tungsten-halogen source
with the beam control
afforded by the PAR and
R reflectors.
They are being widely
used for special accent
lighting for display
purposes in stores and art
galleries.
Electric Discharge Light sources
The electric type of source produces light by the
passage of an electric current through a vapor or gas.
When an electrical potential is applied between the
electrodes at each end of the lamp tube, the gas is
ionized and current (that is, electrons) flows between
the electrodes.
The electrons travel at tremendous speeds, and when
they collide with the atoms of the vapor, they
temporarily alter the atomic structure.
Energy is given off in the visible and/or ultraviolet
region as the disturbed atoms return to their normal
state.
The electrodes at the ends of the tube are generally
Contd
The types and shapes of the bases at each end of the lamp
are shown below.
Recessed light: the protective housing is concealed behind a
ceiling or wall, leaving only the fixture itself exposed. The ceiling-
mounted version is often called a downlight.
2- Surface-mounted light: the finished housing is exposed, not
flush with surface.
Under-cabinet light: mounted below kitchen wall cabinets.
Lighting Design
Lighting design is the planning of our visual environment.
Good lighting design aims to create perceptual conditions which
allow us to work effectively and orient ourselves safely while
promoting a feeling of well-being in a particular environment and
at the same time enhancing that same enviroment in an aesthetic
sense.
Lighting design is not a completely scientific process because it
involves human perception, tastes, and moods.
Satisfactory lighting for children and youth might not be
acceptable for seniors because of differences in their visual
acuity.
In addition, the colors and textures of floors, walls, and ceilings
affect the selection of appropriate luminaires.
Contd
The design of a lighting system for an interior space involves many
variable factors.
the size and shape of the space;
the types of finishes on the ceilings, walls, and floors; the details
of the construction;
the economic considerations of both the initial and the operating
costs;
the compatibility of the lighting system with the architectural
design; and
the type of activities that will be carried out in the space.
Contd
The principal factors to be considered for satisfactory room
lighting are the following.
Room dimensions: ceiling height and floor area
Architectural or structural features that can affect lighting
Reflectance, diffusion, and absorption of light by ceilings, walls,
floor, and furnishings
Proper selection of luminaires by evaluating their light
distribution, efficiency, decorative value, elimination of glare,
and economy
Height and spacing of luminaires within rooms based on room
function
Contd
In general, lighting design procedure can be seen as having
three steps.
Assessing the illumination level for the task;
Making calculations to determine the number of luminaries
required and their distribution in the space.
Selection of luminaries type based on light quality,
architecture of building, economics, etc.
1. When the algebraic sum of the weighting factors is 3 to -2 use the lowest value
2. If the algebraic sum of the weighting factor it is 1 to +1 use the middle value, and
3. If the algebraic sum is 2 to 3 use the highest value.
Contd
The criteria for the final single-value illuminance
selection involves the workers ages, the demand
for speed and/or accuracy, and the task
background reflectance.
To use these tables the first step is to determine
the type of activity involved.
After selecting the letter category from the
tables, next refer to the weighing factor table for
the single-value recommendation.
Example:
Determine the Illumination level for technical school lecture room
requiring medium pencil handwriting based on IESNA.
Category E with a range of 500-750-1000 fits this type of activity.
The total weighing factor: Workers age (consider students under 40)
1, speed and accuracy (not important as errors will not lead to cost
and no safety hazard) 1, and reflectance of task background (paper
at 70%) 0 resulting in total 2. Therefore; the low value of the range
can be (500 lux) chosen.
Lighting calculation
1.Point by point method
2.Lumens method
Point by point method
The
inverse square and the cosine laws are used to calculate the
illuminance at a single point on a plane.
Since each calculation gives the value at only one point, a number of
calculations are required to determine the illuminance at a series of points
over the place. This method is therefore referred to as the point-by-point
method.
An intensity distribution curve of the luminaire is required to obtain the
intensity of the light source at the specific angle involved in each
calculation.
Besides the multiplicity of calculations required, there are two inherent
disadvantages to the point by point method:
1. It doesnt take into account any light reflected from the surfaces of a
room
2. It is only applicable to the point sources of light.
Therefore, the lumen method is the preferred way to handle lighting
calculations for an indoor space.
The point-by-point method , however, is widely used for outdoor lighting
calculations where there is little or no reflected light and the light source is
Contd
Illumination design for exterior lighting and localized lightings are generally done
using point by point method.
In the point by point method selected points illumination is calculated from the total
illuminated area. This is an accurate illumination level for the points of calculation.
Example 1: Lighting posts are used to illuminate a horizontal road in a city. The Fixture
is at the height of 8 meters on the post. Determine the distance between the poles to
have minimum illumination level of 10 lux between the posts. The fixtures have 10,000
candelas in all directions.
Solution:
The illumination from the two adjacent lighting posts is considered, neglecting the effect
of the others. The surface is further assumed horizontal. Therefore; incident angle,
illumination contribution from each post are assumed to be similar. Hence; Contribution
of the illumination from one post will be 5 lux at the center middle of the two posts.
It can be shown that the equation of
illumination level from one of the
luminaries is given by
`
The light loss factor is the ratio of the illuminance when it reaches its lower
level just before corrective action is taken as compared to the initial level.
The light loss factor is the product of all the individual factors that
contribute to the loss of light. These factors are divided into two
categories, unrecoverable and recoverable.
Unrecoverable factors: are those attributed to equipment and site
conditions that can not be changed with normal maintenance. These are
temperature factor, line voltage factor, and ballast factor.
Recoverable factors: those that can be changed with normal
maintenance. They can be changed by regular scheduled maintenance such
as cleaning and relamping luminaires and cleaning and painting room
surfaces.
Contd
Contd
The recoverable factors that must be considered in
calculating the light loss factor are lamp lumen depreciation,
luminaire dirt depreciation, and room surface dirt
depreciation.
LDD: with the passage of time, dirt accumulates on the
lamps and on the surfaces of the luminaires. This dirt
absorbs some of the light. The resulting loss of light is
accounted for by the luminaire dirt depreciation (LDD)
factor.
Depending on the type of luminaire construction, luminaires
are divided into six maintenance categories. These are given
in graphs.
Each luminaire has an assigned maintenance category that
indicates which of the graphs to use. Also, there are five
degrees of operating atmosphere, ranging from very clean to
Example 2
Luminaire 3 is used for a lighting layout. The atmosphere will be
clean and the period between cleanings will be 24 months. Determine
the LDD factor.
Contd
Room Surface Dirt Depreciation: with the passage of time, the
accumulation of dirt on the surfaces of the room further reduces
the amount of light that reaches the workplane.
The exact effect of dirt on light loss varies according to the size
and proportions of the room (that is, the room cavity ratio), the
type of operating atmosphere, and the luminaire distribution type.
The resulting loss of light is accounted for by the room surface
dirt depreciation (RSDD) factor, which is determined by referring
to table below.
First, select the percent of expected dirt depreciation from
the graph accompanying the table, using the appropriate
atmosphere curve and the time interval in months between
cleaning.
Then refer to the table and, depending on the room cavity ratio
and the luminaire distribution type, select the RSDD factor.
Example 3
Example 4
To include the light loss factor, the equation expands
to
Solution:
STEP1: Draw a plan, reasonably to scale, of the outline of the room as shown
below:
Contd
Example 7
A
room 60 by 120 ft room is now to be lighted to a level of 75 fc by
installing luminaire 3 suspended from 5 ft from the ceiling. The luminaire
will be 8 ft long and each will have two rapid-start, 800 mA, T-12, 96 in.,
cool white fluorescent lamps. The atmosphere and cleaning times will be
the same as in example 2. Select a practical lighting layout.
Solution
STEP1: Since the cross section and room surface reflectances are still the same, the
cavity ratios and effective ceiling and floor reflectances calculated in previous example still
apply.
STEP 2: Determine the coefficient of utilization:-
For luminaire 3, , , and RCR = 2.0, a value of 0.63 is read (for 20% floor
reflectance).
The multiplying factor for 10% floor reflectance is the same as in previous
example.
Solutions