Short Circuit Calculations
Short Circuit Calculations
Sector Energy
D SE PTI NC
Steffen Schmidt
IEC 60909:
Short-Circuit Current Calculation in Three-Phase A.C. Systems
3-phase
2-phase
1-phase
Sk" 3 Un Ik"
NOTE: Sk is often used to calculate the internal impedance of a network feeder at the
connection point. In this case the definition given should be used in the following form:
c Un2
Z
Sk"
Page 10 28.06.2008 Steffen Schmidt Copyright Siemens AG 2008. All rights
E D SEreserved.
PTI NC
Short-Circuit Calculations
Definitions according IEC 60909 (II)
NOTE: The magnitude of the peak short-circuit current varies in accordance with the
moment at which the short circuit occurs.
2 2 IB
tB
Assumptions
quasi-static state instead of dynamic calculation
no change in the type of short circuit during fault duration
no change in the network during fault duration
arc resistances are not taken into account
impedance of transformers is referred to tap changer in main position
neglecting of all shunt impedances except for C0
real network
Q A F
equivalent circuit
ZN Q ZT A ZL
~
c.U n
I"K
3
maximum minimum
short circuit currents short circuit currents
c Un c Un2
ZQ
3 Ik
"
Sk"
ZQ
XQ
1 (R / X)2
If R/X of the network feeder is unknown, one of the following values can
be used:
R/X = 0.1
R/X = 0.0 for high voltage systems >35 kV fed by overhead lines
ZTK = ZT KT
general
c max
K T 0,95
1 0,6 x T
ZGK = ZG KG
general
Un c max
KG
UrG 1 xd sin rG
Q
ZS(O) = (tr2 ZG +ZTHV) KS(O)
G
2
1 UrM
ZM
ILR / IrM SrM
ZM
XM
1 (RM / XM )2
(0)
(0) (0)
(0)
(0) (0)
(0) (0)
zero sequence system
L1-L2-L3-system Z(1)l
012-system Z(1)r
L1 ~ ~
L2 ~ c Un (1)
L3 3
~
Z(2)l Z(2)r
-Uf c U r ~ ~
I sc2 (2)
Z 1 Z 2
Z(0)l Z(0)r
~ ~
c U r
I sc2 3
I sc2 (0)
2 Z 1
I sc3 2
network left of network right of
IL1 = 0 U fault location
U (1) U ( 2 ) c n fault location fault location
3
IL2 = IL3 I(0) = 0
L1-L2-L3-system 012-system
Z(1)l Z(1)r
~ ~
L1
~ c Un (1)
L2
3
L3
Z(2)l Z(2)r
~ ~
~ 3 c U r
-Uf
I scE2E (2)
Z 1 2 Z 0
Z(0)l Z(0)r
~ ~
(0)
I L1 0
network left of network right of
fault location
2 Un fault location fault location
U L2 a c
3 Un
U (1) U ( 2) c U (1) U ( 0)
Un 3
U L3 a c
3 I(0) = I(1) = I(2)
Z(0)l Z(0)r
~ ~
(0)
Because of Z1 Z2 the
largest short circuit current can
be observed
for Z1 / Z0 < 1
3-phase short circuit
for Z1 / Z0 > 1
2-phase short circuit with
earth connection
(current in earth connection)
110 kV 110 / 20 kV 20 kV
3 GVA 40 MVA 10 km
R/X = 0.1 uk = 15 % R1 = 0.3 / km
PkrT = 100 kVA X1 = 0.4 / km
c Un2
ZI
Sk"
1.1 20 kV
2
ZI
3 GVA
Un2 Un2
Z T uk R T PkrT 2
Sn Sn
20 kV 2 20 kV 2
Z T 0.15 R T 100 kVA
40 MVA 40 MVA 2
c max
K T 0.95
1 0 .6 x T
1 .1
K T 0.95
1 0.6 0.14998
K T 0.95873
RL R' XL X'
RL 0.3 / km 10 km XL 0.4 / km 10 km
RL 3.0000 XI 4.0000
R RI R TK X XI X TK
R 0.0146 0.0240 X 0.1460 1.4379
R 0.0386 X 1.5839
c Un
Ik"
3 R1 j X1
1.1 20 kV
Ik"
3 0.0386 2 1.5839 2
Ik" 8.0 kA
R RI R TK RL X XI X TK XL
R 0.0146 0.0240 3.0000 X 0.1460 1.4379 4.0000
R 3.0386 X 5.5839
c Un
Ik"
3 R1 j X1
1.1 20 kV
Ik"
3 3.0386 2 5.5839 2
Ik" 2.0 kA
RGf = 0,05 Xd" for generators with UrG > 1 kV and SrG 100 MVA
RGf = 0,07 Xd" for generators with UrG > 1 kV and SrG < 100 MVA
Ik" 8.0 kA
R 0.0386 X 1.5839
R / X 0.0244
1.02 0.98 e 3R / X
1.93
ip 2 Ik"
ip 21.8 kA
Ik" 2.0 kA
R 3.0386 X 5.5839
R / X 0.5442
1.02 0.98 e 3R / X
1.21
ip 2 Ik"
ip 3.4 kA
Ib = Ik
IB = Ik
IB = q Ik
Simplified calculation:
Ib = Ik
" "
" "
UGi jX "diK IkGi UMj jXMj
"
IkMj
For short circuits far from generator and as worst case estimation
Ik = Ik
C Superposition of A and B
1000V 720V
10A 50A
1000V -0V -0V
720V 1000V 720V
900V 780V 700V 900. V 700V
90 14 ~
-307.89V -364V
~ ~ 592.11V 336V ~
365.37A
Steffen Schmidt
Senior Consultant
Siemens AG, Energy Sector
E D SE PTI NC
Freyeslebenstr. 1
91058 Erlangen
E-mail: [email protected]