Generator Protection: Vaishakha SP
Generator Protection: Vaishakha SP
Vaishakha SP
Generator Protection
2 2
Connection to the Power System
1. Direct :
2. Via Transformer :
3 3
Typical Generator Installations
Generator Generator
Transformer Transformer
Station
Trans-
Earthing former
Transformer
Unit / Unit
Station Trans-
Transformer former
1(b) 1(c)
4 4
Generator Protection Requirements
5 5
Generator Faults
Faults include :-
Insulation Failure
Stator
Rotor
Excitation system failure
Prime mover / governor failure
Bearing Failure
Excessive vibration
Low steam pressure
etc.
6 6
System Conditions
Short circuits
Overloads
Loss of load
Unbalanced load
Loss of synchronism
7 7
Generator Protections to be Considered
8 8
Stator Earth Fault Protection
9 9
Method of Earthing (1)
Damage resulting from a stator earth fault will depend upon the
earthing arrangement
10 10
Method of Earthing (2)
11 11
Method of Earthing (3)
limits damage
reduces possibility of developing into phase-phase
fault
12 12
Method of Earthing : Limitation of Earth Fault Current (1)
Less than 5A :
20A :
13 13
Method of Earthing : Limitation of
Earth Fault Current (2)
100A :
As for 20A, but higher current allows better discrimination and sensitivity.
14 14
Stator Earth Fault Protection and Protection Against
Earth Faults on Generator Connections
Depending on the Generator arrangement this can be provided by :-
15 15
Overcurrent Protection (1)
51
16 16
Overcurrent Protection (2)
51
17 17
Stator Earth Fault Protection
51N
50N 51N
xV
xV
F
250/1A IS R
For operation
S(PRIMARY) F
R 33 xV
R
x.6600
x.200
33
1
S(SECONDARY) x.200 x 0.8x
250
For protection of 90% of winding; x = 1-0.9 = 0.1
Relay setting = 0.8 x 0.1 = 0.08A = 8% of 1A
19 19
Stator Earth Fault Protection (1)
Generators connected via step-up transformer (resistance earthed) :
51N 50N
System earth faults ARE not seen by generator earth fault protection
instantaneous relay may be used.
Advantage : Fast
20 20
Stator Earth Fault Protection (2)
Advantage : Sensitive
21 21
Stator E/F Protection for Generator with High
Resistance Earthing via Distribution Transformer (1)
RSTAB
High Impedance Principle
64
Instantaneous Protection
5 x CTs required
RSTAB
64
24 24
Restricted Earthfault Protection for Generators on 4 Wire L.V.
Systems (2)
Earthing at Busbars
RSTAB
64
4 x CTs required
25 25
Differential Protection (1)
Stabilising
Resistors
Relay
26 26
Differential Protection (2)
BIAS BIAS
OPERATE
INTERPOSING
C.T.
Two methods :
29 29
100% Stator Earth Fault Protection
For Large Machines Only
Two methods :-
Low frequency injection Third harmonic voltage - various
Earthing
Trans- 59
former
Complete protection during start-up if source is
independent of generator, e.g. derived from
Injection station battery.
Transformer
Independent of system V, f and load current.
High cost due to injection equipment.
51 Alternative
Injection
Points
30 30
Third Harmonic Neutral Voltage Scheme
Relies on >1%
generated 3rd
harmonic volts
59 27
59P
27 - 3rd harmonic under voltage relay.
59P - Terminal Voltage Check
59
Allows trip if circuit breaker is open but
terminal voltage present.
TRIP
59P 27 59 - Conventional neutral over voltage protection.
27 OVERLAP
0 50 100
Earth Fault Position
31 31
Stator Phase-Phase Fault Protection (1)
Insulation failure
Flashover in terminal box
32 32
Stator Phase-Phase Fault Protection (2)
Single Generator
51 51 51
Type types :
34 34
Stator Phase-Phase Fault Protection (4)
Stabilising
Resistors
Relay
35 35
Stator Phase-Phase Fault Protection
Small machines :
Star connection made inside machine
Winding neutral ends are not brought out
36 36
Stator Interturn Fault Protection (1)
37 37
Stator Interturn Fault Protection (2)
VA
VB
VC
VA VB VC VR
FAULT
R
VR = VA + VB + VC
38 38
Stator Interturn Fault Protection (3)
Transverse Differential Protection
(Double Wound Machines) :
Bias
Coils
Operate
Coils
39 39
Prime Mover Failure (1)
Isolated Generators :
Machine slows down and stops. Other protection initiates shut down.
Parallel Sets :
40 40
Prime Mover Failure (2)
Gas Turbines :
Motoring power 100% rated for single shaft machine, 10% to 15% rated for
double shaft.
Hydro Sets :
41 41
Prime Mover Failure (3)
42 42
Reverse Power Protection (1)
Leading P.F.
Operate Restrain
-MW +MW
87.1
Operate Restrain
Lagging P.F.
+MVARLAG
Exporting lagging VARs
43 43
Loss of Excitation (1)
EFFECTS
Single Generator :
Loses output volts and therefore load.
Parallel Generators :
Operate as induction motor (> synch speed)
Flux provided by reactive stator current drawn from
system-leading pf
Slip frequency current induced in rotor - abnormal
heating
Situation does not require immediate tripping,
however,
large machines have short thermal time constants - should be
unloaded in a few seconds.
44 44
Loss of Excitation (2)
Simple Protection Scheme
Field Exciter
Winding
Shunt Ie Requires access to
field connections.
DC relay Not suitable if
(setting < Ie min) generator operates
Aux Supply normally with low
excitation (large
T1
machines).
Alternative scheme
monitors impedance
T2
at generator
0.2 - 1 sec
Overcomes Alarm or terminals.
Slip Frequency Trip
Effects
2 - 10 secs
45 45
Loss of Excitation (3)
Alternative Scheme
XG XT XS
EG ES
46 46
Loss of Excitation (4)
Load Impedance
R
Impedance Offset Prevents
Locus operation
on pole slips
Diameter
Typically : Relay Characteristic
Offset 50-75%Xd
Diameter 50-100% XS Time Delayed
47 47
Unbalanced Loading (1)
Effects
Gives rise to negative phase sequence (NPS) currents -
results in contra-rotating magnetic field.
49 49
Unbalanced Loading (2)
Protection
Machines are assigned NPS current withstand values :
50 50
Rotor Earth Fault Protection (1)
51 51
Rotor Earth Fault Protection (2)
Potentiometer Method
Exciter
52 52
Rotor Earth Fault Protection (3)
AC Injection Method
AC Auxiliary
Supply
R
Brushless Machines
No access to rotor circuit
Require special slip rings for measurement
If slip rings not present, must use telemetering techniques
(expensive)
53 53
Overload Protection (1)
Governor Setting
54 54
Overload Protection (2)
Overcurrent Protection
55 55
Generator Back-Up Protection (1)
Over current Protection
Typical use :
Very or extremely inverse for LV machines
Normal inverse for HV machines
10 x
FL
with AVR
Full
Load
no AVR
Cycles
56 56
Generator Back-Up Protection (2)
Voltage Restrained
Voltage Controlled
F
57 57
Voltage Controlled Overcurrent Protection
Overload
Characteristic
Is
Current Pick - up
t
Fault
Characteristic
Vs
I Voltage
58 58
Voltage Restrained Overcurrent Protection
Equivalent to impedance
Current Pick-up
devices I>
KI>
VS2 VS1
Voltage
59 59
Impedance Relay
jx
RELAY
CHARACTERISTI
C
MZTU
Set to operate at 70% rated load impedance when voltage drops to zero,
current required to operate relay is 10% rated current. Built-in timer for
co-ordination purposes.
60 60
Under & Over Frequency Conditions (1)
Over Frequency
61 61
Under & Over Frequency Conditions (2)
Under Frequency
62 62
Under & Over Voltage Conditions (1)
Protection
63 63
Under & Over Voltage Conditions (2)
Over Voltage
Under Voltage
64 64
Other Protection Considerations
65 65
Pole Slipping Protection
Rotor Stator
E E
G S
ZG9356
66 66
Pole Slipping Detection
E E = 2.8 (max) X
G S
R
E E = 1.2
G S
E E =1
G S
E E = 0.8
G S
E E = 0.19 (min)
G S
MIS9357
67 67
Pole Slipping Protection
68 68
72 72
Overfluxing
Often applied to :-
Generator transformers
Grid transformers
Flux V / f
Caused by either :-
Increase in voltage
Reduction in frequency
Combination of both
Usually only a problem :-
during run-up or shut down
can be caused by loss of load / load shedding
74 74
Transformer Magnetising
Characteristic
Twice
Normal
Flux
Normal
Flux
Normal
No
Load No Load
Current Current at
Twice Normal
Flux
75 75
Magnetising Current with
Transformer Overfluxed
ZG0780C
76 76
Overfluxing
Effects of overfluxing :-
Increase in magnetising current
Increase in winding temperature
Increase in noise and vibration
Overheating of laminations and metal parts
(caused by stray flux)
77 77
Over-Fluxing Relay
Ex
G
VT
AVR RL
78 78
Low Forward Power Interlocking
Urgent Trip
Trip Directly to Circuit Breaker and Initiate shut down
Risk of overspeed
Examples :-
Generator Differential
stator ground fault
negative phase sequence.
79 79
Low Forward Power Interlocking
Non-Urgent Trip
Trip governor
Use low forward power interlocking to determine when main Circuit
Breaker is tripped
Reduced risk of overspeed, and consequential damage to the machine
Examples :-
Over voltage
Over load
Loss of synchronism
Field failure
80 80
Unintentional Energisation at Standstill
Scheme
Typical Approach
50
27 & Trip
& tPU
tDO
VTS
ZG7965D
82 82
Synchronising Relays
Often applied to :-
Synchronising of Generators
Transmission line auto-reclose schemes
Synchronising of Generators
Check voltage magnitudes
Check slip frequency
Check phase angle difference
Synchroscope
Speed of rotation depends on slip frequency
If frequencies matched, phase angle displacement indicated
Does not indicate voltage magnitude
83 83
Voltage Checking & Comparators
Voltage monitors :-
- Under voltage monitor (e.g. Transmission Line)
84 84
Auto-Synchronising Relays
Controls :-
Filed current to adjust voltage magnitude
Governor to adjust slip frequency
Governor to correct constant phase displacement
85 85
Typical Schemes
86 86
Tripping Modes
Class C HV breaker
87 87