CMC
CMC
Manual Mode
Boiler Follow Mode
Turbine Follow Mode
Co-Ordinated Master Control Mode
MANUAL MODE
In this Mode both Boiler Master and Turbine
Controller switched over to manual and unit
controlled manually.
BOILER FOLLOW MODE
In this mode turbine takes lead and boiler follows.
In this mode boiler has to supply the steam for
whatever load has been set from Turbine desk.
In this mode turbine maintain MW Demand and
Boiler maintain MS Pressure.
BOILER FOLLOW MODE
TURBINE FOLLOW MODE
In this mode Boiler takes lead and Turbine follows.
Boiler manually controlled.
In this mode Turbine master On Auto- controls
Turbine throttle steam pressure and MW depends on
the steam output of the Boiler.
TURBINE FOLLOW MODE
CO ORDINATED MASTER
CONTROL
In this mode the target load is set through CMC unit
demand.
Unit load demand is fed to BOILER MASTER to generate
Boiler Demand i.e. air & fuel requirement and to
TURBINE CONTROL to set Turbine Demand i.e. MW.
In this mode both BOILER MASTER and TURBINE
CONTROL are put in AUTO and Unit Load Demand is
fed to both Boiler and Turbine to compute their individual
Load Demands.
CO ORDINATED MASTER
CONTROL
SALIENT FEATURES OF CMC
RUN DOWN
Run down is switched ON automatically when the Process
error (negative) i.e. Feed water, Air flow etc. becomes
excessive AND(&) the controller output of the
particular loop(feed water, air flow, furnace pressure and
fuel) goes to maximum position making process
uncontrollable. Under the situation, Unit load demand is
reduced to a value as Permitted by the Process to get over
the blockage.
SALIENT FEATURES OF CMC
INCREASED BLOCK :
In this if any of the condition comes i.e. if process
error (negative) OR the controller output goes to
maximum then Incr. blocked will come and it will
hold the unit load demand till process recovers
within limits.
SALIENT FEATURES OF CMC