0% found this document useful (0 votes)
68 views33 pages

Announcements: - Next Class Is The Course Evaluation - Final Project Related Additional Office Hours

The document discusses several topics related to HVAC automatic control: 1. It announces upcoming class evaluations, office hours, and a discussion of final projects and exam problems. 2. It provides guidelines for final project presentations including timing, number of slides, and submitting powerpoints in advance. 3. It covers HVAC control terminology like sensors, controllers, set points, and error; and describes proportional, PI, and PID control algorithms.

Uploaded by

Faiz Mansur
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
68 views33 pages

Announcements: - Next Class Is The Course Evaluation - Final Project Related Additional Office Hours

The document discusses several topics related to HVAC automatic control: 1. It announces upcoming class evaluations, office hours, and a discussion of final projects and exam problems. 2. It provides guidelines for final project presentations including timing, number of slides, and submitting powerpoints in advance. 3. It covers HVAC control terminology like sensors, controllers, set points, and error; and describes proportional, PI, and PID control algorithms.

Uploaded by

Faiz Mansur
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 33

Announcements

Next class is the course evaluation


Final project related additional office hours
Tomorrow afternoon from 1 till 4 pm
Thursday afternoon
Friday by appointment
Objectives
Discuss the exam problems
Talk about final project report and presentation
Learn about automatic control
PID and Control terminology
Sequence of operation
Control optimization
Project presentation
Timing: 10 minutes for presentation
Approximately 1 PowerPoint Slides per minute
For example
Specify the project Provide some basic floor layout and input variable assumptions
Results (form calculation and manufacturer catalogs)
Disuses you system challenges and modifications related to your design solutions

3 minutes for Questions and Answers

I will need you power point before the class


You can email it to me.
HVAC automatic control
Maintain environmental quality
Thermal comfort
Indoor air quality
Material protection
Conserve energy
Protect equipment
Terminology
Sensor
Measures quantity of
interest
Controller
Interprets sensor data
Controlled device
Changes based on
controller output
Figure 2-13
outdoor

Direct Indirect
Closed Loop or Feedback Open Loop or Feedforward
Set Point
Desired sensor value
Control Point
Current sensor value
Error or Offset
Difference between control point and set point
Two-Position Control Systems
Used in small, relatively simple systems
Controlled device is on or off
It is a switch, not a valve
Good for devices that change slowly
Modulating Control Systems
Example: Heat exchanger control
Modulating (Analog) control

Cooling coil

air
x

water

(set point temperature)


Modulating Control Systems
Used in larger systems
Output can be anywhere in operating range
Three main types
Proportional
PI
Electric (pneumatic) motor
PID
Position (x)

fluid

Volume flow rate


Vfluid = f(x) - linear or exponential function
The PIDconstants
control algorithm
time

e(t) difference between


set point and
measured value
Position (x) Proportional Integral Differential

For our example of heating coil:

K d (Tset point Tmeasured )


x K (Tset point Tmeasured ) (Tset point Tmeasured )d K Td
Ti d

Proportional Integral Differential


(how much) (for how long) (how fast)

Position of the valve


Proportional Controllers
x A K (Tset point Tmeasured )
x is controller output
A is controller output with no error
(often A=0)
Kis proportional gain constant
e = Tset point Tmeasured is error (offset)
Unstable system Stable system
Issues with P Controllers
Always have an offset
But, require less tuning than other
controllers
Very appropriate for things that change
slowly
i.e. building internal temperature
Proportional + Integral (PI)
K
x A K (Tset point Tmeasured ) (Tset point Tmeasured )d
Ti

K/Ti is integral gain

If controller is tuned
properly, offset is
reduced to zero

Figure 2-18a
Issues with PI Controllers
Scheduling issues
Require more tuning than for P
But, no offset
Proportional + Integral +
Derivative (PID)

Improvement over PI because of faster response


and less deviation from offset
Increases rate of error correction as errors get larger
But
HVAC controlled devices are too slow responding
Requires setting three different gains
Ref: Kreider and Rabl.Figure 12.5
The control in HVAC system only PI
K
x K (Tset point Tmeasured )
Ti (Tset point Tmeasured )d

Proportional Integral
value

Set point
Proportional
affect the slope

Set point Integral


affect the shape after
the first bump
The Real World

50% of US buildings have control problems


90% tuning and optimization
10% faults
25% energy savings from correcting control
problems
Commissioning is critically important
Practical Details
Measure what you want to control
Verify that sensors are working
Integrate control system components
Tune systems
Measure performance
Commission control systems
HVAC Control
Example 1:
Economizer (fresh air volume flow rate control)
Controlled device is damper
fresh
damper air - Damper for the air
- Valve for the liquids

mixing
recirc.
air

T & RH sensors
Economizer
% fresh air
Fresh air volume flow rate control
enthalpy 100%

Fresh
(outdoor)
TOA (hOA)
Minimum for
damper air ventilation

mixing
Recirc.
air

T & RH sensors
Economizer cooling regime
How to control the fresh air volume flow rate?
If TOA < Tset-point Supply more fresh air than the minimum required

The question is how much? % fresh air

Open the damper for the fresh air


100%
and compare the Troom with the Tset-point .
Open till you get the Troom = Tset-point
Minimum for
If you have 100% fresh air and your ventilation
still need cooling use cooling coil.

What are the priorities:


- Control the dampers and then the cooling coils or
- Control the valves of cooling coil and then the dampers ?

Defend by SEQUENCE OF OERATION


the set of operation which HVAC designer provides to the automatic control engineer
Economizer cooling regime

Example of SEQUENCE OF OERATIONS:

If TOA < Tset-point open the fresh air damper the maximum position

Then, if Tindoor air < Tset-point start closing the cooling coil valve

If cooling coil valve is closed and T indoor air < Tset-point start closing the damper
till you get T indoor air = T set-point

Other variations are possible


HVAC Control
Example 2:
Dew point control (Relative Humidity control)
fresh filter cooling heating
damper filter
air
fan coil coil

mixing

T & RH sensors

Heat gains
Humidity generation

We should supply air with lower humidity ratio (w) and lower temperature

We either measure Dew Point directly or T & RH sensors substitute dew point sensor
Relative humidity control by cooling coil

Cooling Coil

Mixture

Room
Supply

TDP Heating coil


Relative humidity control by cooling coil (CC)
Cooling coil is controlled by TDP set-point
if TDP measured > TDP set-point send the signal to open more the CC valve
if TDP measured < TDP set-point send the signal to close more the CC valve

Heating coil is controlled by Tair set-point


if Tair < Tair set-point send the signal to open more the heating coil valve
if Tair > Tair set-point send the signal to close more the heating coil valve

Control valves
Fresh air

mixing

cooling heating
coil coil

Tair & TDP sensors


Sequence of operation
(ECJ research facility)
Mixture 3

DPTSP
Set Point
(SP)
Mixture 1 Mixture 2
Control logic:
DBTSP
Mixture in zone 1: IF (( TM<TSP) & (DPTM<DPTSP) ) heating and humidifying
Heater control: IF (TSP>TSA) increase heating or IF (TSP<TSA) decrease heating
Humidifier: IF (DPTSP>DPTSA) increase humidifying or IF (DPTSP<DPTSA)
decrease humid.

Mixture in zone 2: IF ((TM>TSP) & (DPTM<DPTSP) ) cooling and humidifying


Cool. coil cont.: IF (TSP<TSA) increase cooling or IF (TSP>TSA) decrease
cooling
Humidifier: IF (DPTSP>DPTSA) increase humidifying or IF (DPTSP<DPTSA)
decrease hum.

Mixture in zone 3: IF ((DPTM>DPTSP) ) cooling/dehumidifying and reheatin


Cool. coil cont.: IF (DPTSP>DPTSA) increase cooling or IF (DPTSP<DPTSA)
decrease cooling
Heater control: IF (TSP>TSA) increase heating or IF (TSP<TSA) decrease heating
Other examples for HVAC:

Heat recovery

Dual duct system


Other examples
Thermal storage UTs CHP
Thermal storage for
adjustment production to
consumption

You might also like