75% found this document useful (4 votes)
405 views

Over View of GTG Plant and Control of Turbine

The document provides an overview of a gas turbine plant and its control system. It describes the basic Brayton cycle used in gas turbines with compression, combustion, expansion, and exhaust. It then summarizes the key components of an open cycle gas turbine, including the compressor, combustor, turbine, and control system. The control system aims to regulate speed, temperature, load, start-up, and acceleration using fuel flow modulation. The Mark VI control system and its configuration, boards, communication, and tools are also outlined.

Uploaded by

dimas
Copyright
© © All Rights Reserved
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
75% found this document useful (4 votes)
405 views

Over View of GTG Plant and Control of Turbine

The document provides an overview of a gas turbine plant and its control system. It describes the basic Brayton cycle used in gas turbines with compression, combustion, expansion, and exhaust. It then summarizes the key components of an open cycle gas turbine, including the compressor, combustor, turbine, and control system. The control system aims to regulate speed, temperature, load, start-up, and acceleration using fuel flow modulation. The Mark VI control system and its configuration, boards, communication, and tools are also outlined.

Uploaded by

dimas
Copyright
© © All Rights Reserved
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 27

OVER VIEW OF GTG PLANT AND

CONTROL OF TURBINE
MAIN GB COMPRESSOR AUX GB STARTING DE

ALTERNATOR TURBINE & LUBE OIL PUMP


COMBUSTOR
Gas Turbine principle

Heat added
2

Heater
Compressor 3 Turbine

1
cooler 4

Heat rejected
Description

At point 1 cold gas enter a compressor to raise pressure


At point 2 the gas passes to the heater where
temperature of gas is raised
At point 3 the hot gas enters the turbine where it
expands to a lower pressure. The shaft work developed
by turbine flows in two direction.
At point 4 the exhaust gas flows to cooler where heat is
rejected and gas is restored in initial position
Brayton /Joule cycle

2 3

Pressure

1 4

Volume

Two reversible adiabatic or isentropic processes (1-2 and 3-4)


Two constant pressure processes (2-3 and 4-1)
Rankine cycle

2 3

Pressure

1
4

Volume
1-2 (BFP)
2-3 (Boiler)
3-4 (Turbine)
4-1 (Condenser)
Open cycle gas turbine

Fuel
2

Compressor Combustion chamber 3 Turbine

1
4

Air from atmosphere Product of combustion to atmosphere


Salient points

The source of energy is normally the combustion of fuel


in air
In closed cycle, gas turbine also product of combustion
of fuel and air may be passed through the heater
In open cycle cooler is not required
The heater is replaced by combustion chamber and fuel
is burnt directly in air stream
Open cycle gas turbine (With heater)
Fuel
Heat exchanger

2 Combustion chamber

Compressor 3 Turbine

1
4
Product of combustion to atmosphere
Air from atmosphere
CONTROL SYSTEM

A control scheme of a gas turbine attempts to control the


following
SPEED
TEMPERATURE (COMBUSTOR OUTLET)
LOAD
START UP CHARACTERISTICS
ACCELERATION CONTROL
Above characteristics are achieved by modulating fuel
flow. Control signal ultimately acts on the fuel valve
CONTROL SYSTEM

SPEED: The speed control loop controls the speed of


the turbine by controlling the fuel flow . Speed control
have speed sensing as input to the controller.
TEMPERATURE: Materials used in the hot gas path of
gas turbine are stretched much closer to their limits than
any other machine. The control system takes design
temperature of hot flue gas path material as set point.
LOAD: The control loop takes the MW as the set point.
The control loop also interferes when rate of loading
exceeds a certain point as turbine is loaded fast the
damage of the component may occur
CONTROL SYSTEM

START UP CHARCTERISTIC: The control


system brings the gas turbine from zero
speed to operating speed using preset
level of fuel flow through automatic
sequencing of control signals to the
accessories, starting device and fuel
control system
CONTROL SYSTEM

ACCELERATION CONTROL: One critical


component of the turbine start sequence is
the acceleration to synchronous speed. A
design acceleration rate must be
maintained throughout start up to limit
stress on turbine parts.
MARK VI CONTROL SYSTEM

The main function of mark VI control


system are
Speed control during start up
Turbine load control during normal
operation on the grid
Protection against turbine over speed on
loss of load
Automatic generator synchronization
MARK VI CONTROL SYSTEM

It runs on PC based work station using MS


window client server architecture.
HMI provides operator display and control for
mark VI turbine controller
HMI contains a number of product feature
Dynamic graphics
Alarm display
Process variable trending
Point control display (For maintenance)
HMI access security
COMMUNICATION

DCS ETHERNET MODBUS DCS ETHERNET GSM

HMI SERVERNODE PLANT DATA HIGHWAY

I/O BOARD

UCVx CONTROLLER UNIT DATA HIGHWAY


MARK VI TMR CONFIGURATION

To other GE
TO DCS
control sys
Backup Protection
Primary Controller < P> PROT MOD
Ethernet < R> CONTL MOD
PS

X
Software < S> CONTL MOD
Voting PS

Y
< T> CONTL MOD
PS
Z
Ethernet- IONet
Primary Controller
Control
Protection
Monitoring
<R>, <S>, <T> are Control processor
Backup Protection
Emergency over speed
Synchro check protection
<X>, <Y>, <Z> are back up processor
MARK VI BOARDS

I/O Terminal Board


I/O Board
Processor Card
Communication Card
Protective Processor <X>, <Y>, <Z>
Rack Power Supply
Power Distribution Board
MARK VI I/O
General Purpose I/O
Contact Input
Relay Output
Analog I/O
Thermocouple Inputs
RTD inputs
Turbine specific I/O
Vibration Inputs
Speed Inputs
Servo channels for control valves (LVDT or LVDR )
Flame Inputs
Automatic Synchronizing
MARK VI COMMUNICATION
External Communication
HMI to Mark VI
HMI to DCS
Internal Communication
VCMI & Control processors
DCMI to I/O boards
I/O signal flow
Unit data Highway (UDH)
Ethernet network between controllers and HMI
Plant data Highway (PDH)
Connects HMI server with printers DCS etc
IONET
IONet is Ethernet network used to
communicate data between the VCMI
communication board in control module,
the I/O boards and three independent
sections of protection module
IONet also communicate data between
controllers in TMR system
CONTROL SYSTEM TOOLBOX

Window based application used to configure & maintain


Mark VI control equipment
Primary function includes
Graphical based editor for configuring application code
Block macros and module library support
Live data block flow diagrams
On line code change
On line help files
I/O configuration & monitoring
Signal management and signal trending
Report Generation
PASSWORD ADMINISTRATION

0-Level: Read only like view, monitor live data


1-Level: All function allowed in 0-Level and Change
Controller Variables and signals and drive advanced
maintenance like change the value of variable, force
signals in a controller
2-Level: All function allowed in 0 & 1 Level and full
controller access and drive advanced maintenance like
make code change, download,put in database and get
from data base
3-Level: Drive Block Area and Menu maintenance like
alter block area and change application menu structure
4-Level: Fuull Drive access like change GE
parameter,edit hardware
CIMPLICITY

Cimplicity is a graphical interface made up of


one or more screens used to monitor and control
the turbine operation
Cimplicity servers allows operator to directly
interface to the mark VI controller (UDH) using
graphical screen
The cimplicity server interface to the mark VI is
done by the cimplicity project. This project is
controlled by a project file using cimplicity work
bench program
TROUBLE SHOOTING TOOLS

Finder/Signal Browser