Power Transformers
Power Transformers
STEP-UP TRANSFORMERS
STEP-DOWN TRANSFORMERS
POWER TRANSFORMERS
Step-Down Transformers:
All the Transformers in the Sub Stations &
Distribution centers are step down
transformers
Power Transformers
A transformer is a static device used for
transferring of power from one voltage to
another voltage without change in frequency.
Operates on the principle of mutual
induction between two circuits linked by a
common magnetic field.
EMF induced in a winding is proportional
to the flux density in the core, cross section
of the core, frequency and no. of turns in the
winding.
A transformer basically consists of:
The phase displacement is indicated by the angle in terms of clock face. The H.V.
vector being at 12 O'clock (zero) and the corresponding L.V. vector at hour hand
number thus,
Phase displacement zero = 0 Letter Y represents star-connected HV
Phase displacement 180° = 6 Letter y represents star-connected L.V.
Phase displacement 30° lag = 1 Letter D represents delta onnectedHV
Phase displacement 30° lead = 11 Letter d represents star-connected L.V.
Letter Z represents star-connected zig-zag.
Thus the symbol Yy0 represents a star/star winding with 0° displacement.
Figure 1.28(c): Vector Groups of 3 Phase Transformers
Transformers - Vector groups - Standards
Connection
Salient Aspects
Third Harmonic
Star/Star Yy0 or Yy6
Economical for small H.V. transformers
Possibility to provide neutral connection
No triplen currents flow.
Neutral voltage may oscillate, and triplen voltages may be high in shell-type units.
3rd harmonic currents and voltages circulate in the delta
Delta/Delta Dd0 or Dd6
Suitable for large H.V. transformers.
Large load unbalance can be tolerated, triplen voltages are damped out.
The absence of a star point may be a disadvantage.
They are not present in the line. 3rd harmonic current circulate in delta winding.
Star/Delta Dy or Yd
Very common for supply networks.
One star point for a neutral to serve mixed 1-ph and 4-ph loads.
Delta winding can carry triplen currents and so stabilize the star point voltage.
Interconnected Star/Star Yz1 or Yz11
Reduces triplen voltages and not sensitive to conditions of unbalanced loading.
Restricted to low-voltage windings.
Phase voltages are composed of half-voltages with a 60° displacement, 15% more turns are required.
Sometimes used in rectifier supply.
• VECTOR GROUPS
Transformers - Vector groups - Standards
Features of Power Transformers
• Single Phase
• Three phase
– Star or Delta connected Primary
– Star or Delta connected Secondary
– With or without Tertiary winding
• Provided with Off-circuit tap switch or On-
load Tap Changer for voltage regulation
Codes and Standards
• Codes or Regulations are mandatory requirements
stipulated to ensure the safety of the product during testing
and service.
Primary and secondary windings on any one limb have induced EMFs
that are in time phase. Different combinations of internal connections
and connections to terminals produce different phase divergence of
sec. voltage.
Off circuit tap changer : Tap changing can be effected only when
transformer is kept off. These are cheaper. They are used where
frequency of tap changing is very less.
On load tap changer : Here tap changing is effected without
interrupting load. On load tap changer normally consists of
transition resistors which bridge the circuit during tap changing
operation.
Two types of OLTCs :
Single compartment type – In this type selection of taps and
switching are carried out on the same contacts.
Double compartment type – In this tap selection is done
separately and switching is done in a separate diverter switch.
Cooling Arrangement
Controlling the temperature inside the transformer is necessary
to reduce thermal degradation of insulation to ensure longer life.
Heat generated in the tramsformer is transmitted to
atmosphere through oil.
Different types of cooling:
ONAN type – Oil natural and air natural. Hot oil is circulated by
natural means dissipating heat to atmosphere by natural means.
ONAF type – Oil natural, air forced. Here air is blown on to the
cooling surfaces. Forced air takes away heat at a faster rate.
OFAF type – Oil forced, air forced. If the oil is force circulated
within the transformer and radiator by means of an oil pump, in
addition to forced air, still better rate of heat dissipation is
achieved over ONAF
OFWF type – Oil forced, water forced. Here water is employed
for cooling oil instead of air. Ambient temp. of water is less than
atmospheric air. Hence better rate of cooling is obtained. In this
type oil to water heat exchangers are employed. Differential
pressure between oil and water is maintained. Oil is circulated at
a higher pressure.
ODAF/ODWF type – Oil directed, air/water forced. If the oil is
directed to flow past the windings, large quantities of heat can
be taken away by oil. Cool oil is directed to flow through the
windings in predetermined paths. Oil is circulated by a forced oil
system like oil pumps. This ensures faster rate of heat transfer.
Oil Preservation System: Oil readily absorbs moisture.
Presence of moisture reduces dielectric strength of oil. Different
methods are available to reduce contamination of oil with
moisture.
1. Silicagel Breather: It is connected to the conservator tank. It
consists of a cartridge packed with silicagel dessicant and a small
cup containing oil. Air is drawn into the conservator thro. oil cup
and breather where most of the moisture is absorbed.
2. Bellows and Diaphragm sealed conservators: A bellow type
barrier or a diaphragm type barrier is fitted in the conservator.
Air entering the conservator tank pushes the diaphragm
downwards. As oil expands the diaphragm is pushed upwards.
Position of diaphragm is indicated by oil level indicator.
Diaphragm acts as a barrier.
3. Gas sealed Conservators: In this method a cushion of an inert
gas like Nitrogen is provided over oil surface in the conservator.
Gas pressure is always maintained higher than atmospheric
pressure. Nitrogen gas pressure inside the conservator is
regulated by nitrogen cylinder and pressure reducing valve which
admit Nitrogen to the conservator when the pressure falls.
Excessive pressure developed inside the conservator is relieved
through a relief valve.
STRENGTHENING OF WINDING
• Hi-β core steels like M0H, ZDKH, etc are available in which
the specific core losses are lower than normal grades.
• Generally0.27M4 grade CRGO core is used.
• With HIB 0.27 grade core losses are reduced by16%.
• HIB 0.23 grade core losses are reduced by24%.
• ZDKH 0.23 grade core reduces losses by 38%.
A A
ViewA-A
Conventional Steplap
Design Principles
Windings- L.V winding
L.V Windings in Transformers are either
Spiral OR layer wound for low current ratings
Helical Wound with radial cooling ducts
for higher ratings.
Disc type wound
Distributed Cross-over (Run-over) coils
The conductor used is paper insulated rectangular
copper (PICC)
For higher currents, transposed conductors are used, to
uniformly distribute the current across the cross section
of the wire of coil.
Spiral/Layer type Winding
Conductor – Layer 1
Conductor – Layer 3
Cooling Duct
Design Principles- L.V winding
Start Finish
- Layer winding or
Cg
Cs
α = K √ Cg/Cs
Design Principles
Impulse Voltage Distribution
α= 0
α =5
α= 10
X
Disc Type Winding
Press-board Cylinder
Disc winding concepts
Conventional Shielded Interleaved
4 32 1 3 2S1 6 25 1
5 67 8 4 5S6 3 74 8
9 8 7 9
V
O
L
Impulse Voltage
T Distribution
A
G
E
1. Plain Disc Winding
2. Rib Shield Winding
G
3. Inter-leaved Disc Winding
R
A
D
I
E
N
T
P
u
• Optimized design
Optimization
• Objective of Optimization
To arrive at a design that yields minimum
capitalized cost.
• DESIGN OPTIMISATION
• DESIGN ANALYSIS “FEM” 2D / 3D ENGINEERING
• ANALYSIS
• ELECTROMAGNETIC
• ELECTROSTATIC
• STRUCTURAL
• THERMAL
• COMPUTER AIDED DRAFTING
• DATABASE AND DATA MANAGEMENT
What is Quality?
Conformance Quality
Performance Quality
Appearance Quality
Functional Quality QUALITY OF
DESIGN/GRADE
Esteem Quality
‘Ability’ Quality
FITNESS FOR USE
Inter-relationship between
‘Fitness for Use’ parameters
QUALITY OF
DESIGN
QUALITY OF
CONFORMANCE
FITNESS
FOR USE
ABILITY
CHARECTERISTICS
FIELD SUPPORT
Poor quality results in failures.
Types of failures
Oil Forced Water The heat is exchanged from oil to cooling water. Both oil and
O.F.W.F.
Forced cooling water are circulated through radiator.
The ambient air used for cooling. This method is useful for oil
A.N. Air Natural
less transformer upto 1.5 MVA.
• In OFAF, the Oil is forced and the Air is also forced. The disadvantage is that, the Transformer
does not have a ONAN rating. Auxiliary supply must always be ensured.
• Radiators can be of two types :
• (1) Tank Mounted- For Small Capacity Trs.
• (2) Separately Mounted- for Large Trs.
• Normally standby Fan for each bank and standby oil pump is specified to take care of failure
of any Fan/ Pump.
• In OFWF cooling system, the pressure of oil in the cooler is maintained above the pressure of
water. The inlet temperature of Water should not exceed 300 C. A complete standby water
cooler is maintained which must be designed to be taken into service when desired. Normally
Hydro station Gen Transformer have this cooling
• Flow indicators with alarm are provided for OFWF cooling.
• Alarm is provided for cooler fan failure/ AC auxiliary supply failure
• Cooler fans and oil pumps are controlled by winding Temperature Mercury switches and
insulating oil requirement:
• 1.0/lt per kVA for Transformers from 400 to1600 kVA
• 0.6lts per kVA for Transformers from 1600 to 80000 kVA
• 0.5lts per kVA for Transformers above 80000 kVA
1. Tank 2. Cooler 1. Tank 2. Cooler
3. Oil Pump 4. Conservator 3. Oil Pump 4. Fan
5. Coolent Flow (Forced Water) 5. Coolent Flow (Forced Water)
3 Alarm Circuit
4 Trip circuit
5 Battle plates
7 Deflector plate
8 Drain plug
9 Mercury switch
10 Test lever
Diagrammatic Illustration of 2 & 3 Relays (Alarm Circuit Closed)
Actuated Protective (Buchholz) Relay:
Although the transformer is a very reliable piece of
apparatus modern conditions of supply and
distribution demand that all possible precautions be
taken to preserve continuity of electrical service.
An oil immersed transformer is not completely
protected unless it is filled with a gas actuated relay.
It defects faults prior to primary break down and
minimizes the propagation of any damage which may
occur within the transformers by giving an alarm.
The relay is therefore particularly effective in
cases of:
◦ Short circuit of core laminations.
◦ Broken down core bolt insulation.
◦ Over treating of some parts of windings.
◦ Bad contacts
◦ Short circuits between phases/turns
◦ Earth faults
◦ Puncture of bushing insulators inside tank
Further more the relay can prevent the
development of conditions leading to a fault in
transformer such as taking of oil level owing to
leaks or the ingress of air as a result of defects in
the oil circulating systems.
• Operation Features:
• The operation of Buchholtz relay is based
upon the fact that every kind of fault in an oil
filled transformer causes decomposition of
the insulating material either liquid or solid,
due to over heating in the fault zone or due to
the action of an intense electric field which in
turn result in a more or less violent generation
of gases. These reach the relay through the
pipe connecting the transformer to the
conservator.
Construction of buchholtz relay:
• The gas activated relay comprises an oil tight cast iron housing which has
on either side a flange for mounting purpose.
• Type MR (Machine Fabique Reinhiussen) make OLTC provides three
different protections for the Diverter Switch.
• RS2001 protection Relay: It will respond to pre Set Oil Flow Pressure and
even low energy faults and isolate the transformer protected.
• Rupture Disc: It is a standard protection without signal contacts, provided
on the top cover with every Diverter and it respond to large energy faults
and prevents damage by isolating the TR.
• Pressure Relief Device M. PreC is Optional. It replaces the Rupture Disc, it
can be in additional to RS 2001. It isolates the Transformer in case of
faults.
• All these are designed to operate with a response time commensurate
with the pressure created inside the diverter due to fault. Hence these are
not replaceable with other makes.
Construction:
• The gas activated relay comprises an oil tight cast iron housing which has on either
side a flange for mounting purpose.
• Type MR (Machine Fabique Reinhiussen) make OLTC provides three different
protections for the Diverter Switch.
• RS2001 protection Relay: It will respond to pre Set Oil Flow Pressure and even low
energy faults and isolate the transformer protected.
• Rupture Disc: It is a standard protection without signal contacts, provided on the
top cover with every Diverter and it respond to large energy faults and prevents
damage by isolating the TR.
• Pressure Relief Device M. PreC is Optional. It replaces the Rupture Disc, it can be
in additional to RS 2001. It isolates the Transformer in case of faults.
• All these are designed to operate with a response time commensurate with the
pressure created inside the diverter due to fault. Hence these are not replaceable
with other makes.
• Pressure Relief Valve
• Vent Pipe
Temperature Indicators:
(1) For Oil Temperature
(2) For Winding Temperature
They indicate maximum temperature, Resettable they indicate current temperature.
Each indicator has two sets of mercury switches operated by temperature to give alarm and trip.
The WTI has additional switch for auto operation of cooling equipment.
The coolers can automatically start or stop.
It has a temperature sensing bulb placed in a Socket on the top of the transformer tank.
Two capillary tubes connect the bulb and the instrument.
One capillary tube connects the operating bellow.
The second one connects a compensating bellow.
The operating system is filled with a liquid which changes its volume as the temperature varies.
The compensating bellow acts on the operating bellow to compensate the Ambient Temperature.
The bellow expands or contracts as the temperature varies.
This is transmitted to the temperature indicator.
The graduated temperature settings can be adjusted.
OTI & WTI work on the same principle but in WTI an additional bellow heated by a resistor in the
WTI CT circuit which represents the actual winding temperature is provided.
As it is not possible to measure the winding temperature directly, it is measured by thermal imaging.
Temperature variations in the heating element are proportional to the winding temperature.
It simulates the increase in the winding Temperature over Oil Temperature. This indicates the Hot
Spot Temperature.
• TEMPERATURE INDICATORS OF A POWER TRANSFORMER
Themometers for EHV Transformers
• MOG
• MOG WITH OIL LEVEL SWITCH
On Load Tap Changers
Topics to be covered
• What is tap changer
• Types of tap changers
• Principle of tap change
• Tapping winding arrangements
• Tap change operation
• Parts of tap changer
• Inspection of tap changer
• Maintenance of tap changer
What is tap changer?
• An equipment used for voltage regulation of
transformers in energy net works and
industrial applications.
• By changing tapping on a winding, it varies
the turns ratio and hence the out put voltage.
Types of Tap Changers
• Based on application
–Off-Circuit tap changer
–On Load Tap Changer (OLTC)
8
7
6 5
4 3
1
2
R2 R1
M2 T2 T1 M1
N
1 2 3
M2 T2 T1 M1 M2 T2 T1 M1 M2 T2 T1 M1
M2 T2 T1 M1 M2 T2 T1 M1 M2 T2 T1 M1
4 5 6
Parts of Tap Changer
• Motor drive mechanism
– Should rotate in both the directions
– Step-by-step operation
– Tap change in progress indication
– Tap change complete indication
– Sequence contact
– Remote Tap position control & indication
Tap Changer Head Cover
Diverter Switch
Transition Resistance
Blow-up view of
Diverter Switch
Inspection
Intervals
Inspection Intervals
• Inspection can be done in one day.
• Recommended to call OLTC manufacturer – at least
first time.
• Table gives number of tap change operations
determining inspection intervals
• Regardless of number of operations, inspect after 4
years if the operating voltage is ≥220 KV and 6-7
years if <220KV
Inspection Intervals
• Tap selectors are generally maintenance-free. For
industrial transformers where no. of operations are
very high, inspect after about 1,000,000 operations.
• Diverter switch unit to be replaced after about
800,000 operations.
• If no. of operations/year is >15000, use oil filter for
the diverter unit. This increases the life by removing
most of abrasive particles responsible for
mechanical wear.
Summary of inspection work
• Withdrawing and reinstalling diverter unit
• Cleaning diverter oil switch compartment and
diverter switch unit and OLTC conservator.
• Changing the diverter oil.
• Determining contact wear
• Measuring transition resistors
• Checking protective relay.
• Diverter should not be exposed to air for more than
10 hours
Tap Changer Oil Quality
Standard values for transformer oil testing according to
CIGRE 12 – 13 (1982) apply to tap changer oil at
service temperature.
C-2. ELECTRICAL TESTS - Dielectric Dissipation Factor (Tan Delta & Loss Tangent)
Dissipation factor: Power loss in dielectric/apparent power (Volt Amp)
Voltage and resulting current deviates from II radians.
Is measure of dielectric losses in oil & hence the amount of heat energy dissipated.
1) Tan delta at 90° for unused oil - maximum 0.2
2) Tan delta at 90° oil before charging transformer - maximum 0.05
3) Tan delta at 90° for oil above 145 KV - maximum 0.2
4) Tan delta at 90° for oil below 145 KV - maximum 1.0
Low value of tan delta indicates low losses.
Cg
Cs
α = K √ Cg/Cs
SPECIFICATIONS FOR TRANSFORMER OIL - IS 335 - 1983
S.N CHARACTERISTICS UNITS LIMIT IS335
1983
1 Appearance - - Clear free of Sediments and
Suspended Matter
2 Density at 27" C g/cm3 max. 0.89
3 Kinematic Viscosity 27 C mm2/s max. 27
4 Flash Point (PM) "C min. 130
5 Pour Point C max. -6
6 Interfacial Tension 27 C N/M min. 0.04
7 Neutralisation Number mgKOH/g max. 0.03
8 Water Content ppm max. 50
9 Corrosion Sulfur - - Non-Corrosive
10 Inhibitor - - Not Present
11 Breakdown Voltage Unfiltered Filtered KV min. 30 60
12 Dielectric Dissipation at 90"C * factor - tan 6 - max. 0.003
13 Resistivity @ 60C/S at 90"C Ohm - cm min. 35xl012
14 Oxidation Test 164 hrs, 100 C a) Neutralisation mgKOH/g max. 0.40 0.10
Number b) Sludge wt% max.
15 Aging Test Ohm-cm min. 0.2 xlO12 0.2 0.05 0.05
ASTM - D - 1934 - 72, 96 hrs 115° C a) mgKOH/g max.
Resistivity at 90° C b)Tan 6 at wt% max.
90° C c) Total Acidity d)Total Sludge max.
TRANSFORMER OIL
SPECIFICATIONS
TRANSFORMER OIL SPECIFICATIONS
• NEW OIL:
An unused mineral insulating oils intended to use
in transformers for insulation and cooling
purpose.
• IS-335/1993 – Specification for uninhibited
new insulating oils.
• IS-12463/1988 – Specification for inhibited
mineral insulating oils.
TRANSFORMER OIL SPECIFICATIONS
• Ageing characteristics
a) Resistivity (Min)
1) at 27˚C • 2.5 x 1012 ohm-cm
2) at 90˚C • 0.2 x 1012 ohm-cm
b) Tanδ at 90˚C (Max) • 0.20
c) Total acidity (Max) • 0.05 mg KOH/gm
d) Total sludge (Max) • 0.05 % by weight
• Presence of Oxidation inhibitor • The oil shall contain natural anti
oxidant additives.
• Water content • 50 ppm
• SK value • Under consideration
IS-1866/2000-Recommended Limits of Unused
Mineral Oil filled in New Transformer
BDV (KV),Min 40 50 60
IS-1866/2000-Violation Limits for in service oils
• Group 1:
• Group 2:
• Group 4:
• Group 3:
• Functional Properties:
Viscosity, Pour point, Water content, BDV, Density,
Tanδ.
• Stability Properties:
Appearance, Acidity, IFT, corrosive Sulfur, Antioxidant
additive
• Performance Properties:
Oxidation Stability, Sludge
• HSE Properties(Health,Safety&Environment)
Flash Point, PCB(polychlorinated biphenyl) content,
PCA(polycyclic aromatics) content
RECONDITIONING,
RECLAMATION &
RE-REFINING
•RECONDITIONING (Filtration):
Contd…
•RECONDITIONING (Filtration):
Direct Purification:
Filtration of new unused oils for the first time
and storing in drums and tankers before filling
the equipments.
Purification by circulation:
Filtration of in service oils for de-gassing, de-
sludging, improving BDV & Water content and
drying out of wet winding.
•RECONDITIONING (Filtration):
Limitations
values.
Use full for the state electricity departments as the higher
• INTERRUPTION TO CONSUMERS.
• LOSS OF REVENUE TO POW'ER SUPPLY COMPANIES.
• LOSS OF MATERIALS LIKE TRANSFORMER OIL, WINDING
MATERIALS WHICH EFFECT THE ECONOMY OF THE NATION.
• CRED1TABILITY OF THE SUPPLY COMPANY IS EFFECTED.
• HEAVY EXPENDITURE IN REPAIRING THE TRANSFORMERS.
• THE TRANSFORMERS GET DERATED IN THEIR
• CAPACITY AFTER EVERY REPAIR.
FAILURE OF POWER TRANSFORMERS
Classification of failures
• Failure in the Magnetic Circuit i.e in cores, yokes & clamping
structure.
• Failure in the windings i.e in the coils, minor insulation and
terminals.
• Failure in the dielectric circuit i.e the coils and major insulation.
• Structural failures.
Failures may be due to
• Manufacturing defects, poor design, faulty material, Bad
workmanship.
• Faulty and abnormal operations including careless drying out &
installation, lack of adequate supervision abnormal transient or
sustained operating conditions.
• Insufficient protection.
Failure of magnetic circuits
• Failure of insulation of core bolts, causing local short circuit between laminations
produces local eddy currents. Some times these failures may cause charring of
insulation of coils and distort the whole core.
• Failure of insulation between laminations produces large eddy currents effecting
the core & insulation of windings.
• When core clamping bolts are not effectively locked, due to vibrations set up in the
transformers, will weaken core insulation and produce failures similar to those in
(1).
• Presence of minute metallic filling between the laminations produces intense local
eddy currents.
• Due to frequent switching on at higher tap-positions, heavy in rush magnetizing
current associated with high flux density and large electro magnetic forces are
created and windings are strained.
• Higher flux densities produce higher harmonic voltages/currents which have
adverse effect on dielectric strength of coils.
• When the transformers are operated at higher voltages with rated frequency,
higher flux densities are resulted effecting the core.
• In older transformers due to ageing of core plates, materials of lamination may
deteriorate & result in increase in iron loss and rise in temperature of the
transformer. This may result in to damage of coils & sludge formation.
Failure in the windings:
• Due to Presence of sharp edges on the copper conductors, in high Voltage transformers, if
the transformer vibrates on load or if the windings are subjected to repeated
electromagnetic shocks the sharp edges of adjacent turns will cut through insulation and
result in to inter turn faults.
• A short circuit between turns may results from dislodging of one or more turns of a coil.
• Due improper adjustment of coil supports where adjustable coil clamping is used, proper
fixing of coils are not achieved and during operation of transformers some of the conductors
of the coil will be dislodged.
• Due penetration of moisture in to the insulation of coils, the coils are bound to fail sooner or
later.
• Improper drying out of the transformer at site may cause premature failure.
• When transformers are subjected to more or less rapidly fluctuating loads, the expansion and
contraction of winding conductors alternately increases and decreases mechanical pressures
on insulation between turns. There by windings will be weakened susceptible for failure
when subjected to electric or magnetic shocks.
• Badly made joints between coils may over heat on load and local carbonization of oil may
occur. The heat generated at the joints will be transmitted along winding conductor and
insulation around the conductor will be carbonized and inter turn short do occur.
• Sustained heavy over loads do cause insulation getting brittle and eventually failure of
insulation & short circuit in the windings.
Failure the insulation
• Entry of moisture in to the transformer oil due to breathing action greatly reduces dielectric
strength of oil and insulation winding causing failure of transformer.
• Prolonged overloading causes deterioration of oil & insulation.
• Dielectrics having different specific permittivity are often used in series and unless their
thicknesses are correctly proportioned they may be subjected to abnormally high dielectric
stresses.
• Solid insulation permittivity 5
• Oil Insulation permittivity 2
• The total voltage across two such dielectrics in series divides up so that the voltages across
equal thicknesses of each are inversely proportional to the permittivity. There fore the
thicknesses of such insulation are to be properly proportioned, So that the voltage across the
each insulation in with in the safe working limit or other wise the dielectric of insulation do
fail one after another, due to corona and overheating.
• Corona may take place from sharp conducting edges or small diameter conductors when the
surface voltage gradient is high.
• Insulating parts, such as cylinders tubes & terminal boards made of compressed paper
bonded with synthetic resin may occasionally have their surfaces contaminated sduring
manufacturing process. These insulations may fail when transformer is in service.
• Narrow oil ducts reduce serviceable life of transformers
MAIN REASONS FOR FAILURE OF DISTRIBUTION
TRANSFORMERS
• DEVIATION OF STANDARDS AT THE TIME OF ERECTION OF TRANSFORMERS
AND LT LINES
• NON MAINTENANCE OF TRANSFORMERS, THEIR STRUCTURES AND
CONNECTED LINES
• MEDDLING BY THE CONSUMERS
• ABNORMAL OPERATING CONDITIONS
• MANUFACTURING DEFECTS
• IMPROPER REPAIRS TO THE FAILED TRANSFORMERS
VARIOUS DEFECTS/DAMAGES NOTICED IN FAILED DISTRIBUTION TRANSFORMERS
• BURNING OF HV COILS
• TOP AND BOTTOM HV COILS DEFORMED
• HV TOP COILS DAMAGED
• BOTTOM HV COILS DAMAGED
• LV COIL TURNS MELTED EVEN EFFECTING CORE PLATES IN SOME CASES
• HV COILS & LV COILS DAMAGED COMPLETELY
• COMPLETE CHARRING OF HV COILS
• MELTING OF LV BUSH RODS
• HV JUMPERS CUT
• LV JUMPERS FUSED
• LV SIDE BUSHINGS CRACKED
• HV SIDE BUSHINGS FLASH OVER
• CARBONISATION OF CONTACTS OF LT CIRCUIT BREAKER IN CSP TRANSFORMER
• LT CIRCUIT BREAKER MECHANISM DAMAGED
• LA S ON CSP TRANSFORMERS ARE DAMAGED
• OIL LEVEL LOW
S. Make & Capacity of Weight Quality of Total Remarks
N Distribution Transformer of Core Oil Weight
o &
Windin
g
1 Kirloskar 100 KVA 560 Kgs 340 Ltrs 1180 Kgs Copper wound conventional
transformer
2 ECE 100KVA 485 Kgs 320 Ltrs 1045 Kgs Copper Wound conventional
transformer
3 HACK 100 KVA BRIDGE 506 Kgs 305 Ltrs 1072 Kgs Copper Wound conventional
transformer
4 STEL 100KVA 230 Kgs 185 Ltrs 650 Kgs Aluminum wound conventional
transformer
5 STEL 100 KVA 260 Kgs 220 Ltrs 700 Kgs Aluminum wound CSP
transformer
6 TE 100 KVS 279 Kgs 240 Ltrs 685 Kgs Aluminum wound CSP
transformer
7 VE 100 KVA 275 Kgs 185 Ltrs 580 Kgs Aluminum wound CSP
transformer
8 VE 100 KVA 270 Kgs 205 Ltrs 595 Kgs Aluminum wound conventional
transformer
9 WEBER 250 KVA 505 Kgs 340 Ltrs 1145 Kgs Aluminum wound conventional
transformer
10 SDE 250 KVA 660 370 Ltrs 1355 kgs Aluminum wound conventional
KGS transformer
Analysis of Failure of Transformers
5 Monitoring LT loads currents by taking tong tester readings Quarterly or whenever frequent LT
fuse blowing is observed
6 Checking of complete earthing system at transformer Half yearly
structure/plinth
7 Measurement of IR values of transformer and earth resistance Half yearly
of the structure
8 Testing of oil for dielectric strength Half yearly
9 Acidity testing of the oil Yearly
10 Checking of operation of LT breakers of CSP transformers Monthly
11 Checking of LA s and their connections Quarterly and also before monsoon
sets in
12 Checking of LT lines complete Quarterly and also before monsoon
sets in
MEASURES FOR REDUCTION OF FAILURE OF TRANSFORMERS
The overhead travelling crane and jib cranes are obviously the
most convenient and safe means. Precautions mentioned below must
be adhered to:
• All equipment used for handling the oil should be cleaned and
flushed with clean transformer oil before use ( the oil used for
washing must be discarded). Particular attention should be paid
to the cleanliness of bungs, valves and other parts where dirt or
moisture tends to collect.
Transformer
Measurements
Protection
Buchholz relay, oil temperature, winding temperature,
pressure relief device, magnetic oil level gauge, differential
over current, earth fault, etc. Protection scheme should be
checked for proper functioning.
Tapchanger
Manually, electrical (local and remote), parallel
operations. IR value of motor and control wiring to be
checked.
Marshalling Box
All control wiring should be checked.
16. Check the oil level in the diverter switch and if found less, top
up with fresh oil.
Dos:
1. Check the packing externally for possible transit damage before
unpacking.
4. Handle the bushing with manila rope slings without any undue
force on porcelain insulator.
6. Remove the wax tape protection on the oil end of the bushing
(at the time of erection) and clean the surface with hot
transformer oil.
7. Check the oil level and IR value of the bushing in vertical
position only, taking care that the bushing is cleaned and no
rope or sling etc. is touching the terminal and ground.
8. Check the breakdown value (BDV) of oil taken from drain plug
or siphoning from the bottom – most portion of bushing. This
should not be less than the recommended value.
9. Check the IR value and tan δ value (if possible) with bushing in
position on transformer with jumper connection removed.
Record these readings for reference and guidance for future
measurements.
12. Maintain the log book records of periodical checks (i.e. tan δ and
BDV of oil) up to date.
Don’ts
1. Do not unpack the bushing from the crate unless required to be
mounted on the transformer.
6. Do not keep the top cap cover open for any longer time than
required as it contaminates the oil.
7. Do not tighten the nuts and bolts in excess to stop any leakage,
this could damage the cemented joints on porcelain.
POWER TRANSFORMERS –
STANDARDS OF PROTECTION
Earth faults
Phase to Phase faults
Inter turn faults
Core faults
Tank faults
EARTH FAULTS:
In this case, the fault current is controlled
mainly by the leakage reactance of the winding
and generally the currents are of high
magnitude.
PHASE-TO-PHASE FAULTS:
Faults between phases within a transformer are
relatively rare. If such a fault does occur it will
give rise to a substantial current compared to
the earth fault current.
INTER – TURN FAULTS:
A high voltage transformer connected to an
overhead transmission system is very likely
to be subjected to steep fronted impulse
voltages. Hence the risk of partial winding
flash over is high. It is opined that 70% to
80% of all transformer failures arise from
faults between turns or inter turn faults.
A short circuit of a few turns of the winding
will give rise to heavy fault current in the
short-circuited loop, but the impact on
terminal currents will be very small because
of the high ratio of transformation between
the whole windings and the short circuited
turns.
CORE FAULTS:
• If any portion of the core insulation becomes defective, it
will cause sufficient eddy currents to flow, causing severe
over heating, which may reach a magnitude sufficient to
damage the winding.
contd..
• Large fault currents produce severe
mechanical stresses in transformers, the
maximum stress occurs during the first cycle
of asymmetric fault current and so cannot be
arrested by automatic tripping of the circuit.
Conservator Alarm
Transformer
Tank
Trip
Buchholz relay is used in the so-called conservator type
transformer in which the transformer tank is completely filled
with oil, and a pipe connects the transformer tank to an auxiliary
tank or " Conservator“ which acts as an expansion chamber.
Figure shown is Buchholz relay connected into the pipe leading
to the conservator tank and arrange to detect gas produced in the
transformer tank. As the gas accumulates for a minor fault the
oil level falls and, with it a float `F' which operates a mercury
switch sounding an alarm.
When a more serious fault occurs within the transformer during
which intense heating takes place, an intense liberation of gases
results.
These gases rush towards the conservator and create a rise in
pressure in the transformer tank due to which the oil is forced
through the connecting pipe to the conservator. The oil flow
develops a force on the lower float shown as "V" in the figure
and over trips it causing its contacts to complete the trip circuit
of the transformer breaker. Operation of the upper float
indicates an incipient fault and that of the lower float a serious
fault.
Buchholz relay Operation : Certain Precautions:
The Buchholz relay may become operative not only during faults
within the transformer. For instance, when oil is added to a
transformer, air may get in together with oil, accumulate under
the relay cover and thus cause a false operation of the gas relay.
For this reason when the 'Gas' alarm signal is energized, the
operators must take a sample of the gas from the relay, for which
purpose a special cock is provided. Gases due to faults always
have color and an odour and are inflammable.
The lower float may also falsely operate if the oil velocity in
the connection pipe, though not due to internal faults, is
sufficient to trip over the float. This can occur in the event of
an external short circuit when over currents flowing through
the windings overheat the copper and the oil and cause
the oil to expand. If mal-operation of Buchholz relay due
to overloads or external short circuits is experienced, it
may be necessary that the lower float is adjusted for
operation for still higher velocities.
In installing these relays the following requirements should be
fulfilled.
a) The conductors connecting the contacts to the terminals on
the cover must have paper insulation, as rubber insulation may be
damaged by the oil.
b) The floats must be tested for air tightness, for example, by
submerging them in hot oil to create a surplus pressure in them.
c) The relay cover and the connection pipe should have a
slope of 1.5 to 3 percent and not have any protruding surface to
ensure unrestricted passage of the gases into the conservator.
NORMS OF PROTECTION TO BE FOLLOWED AS PER A.P.E.R.C.
ORDERS
S.No. Voltage Protection Scheme
POWER STATIONS
Voltage ratio & HV Side LV Side Common relays
capacity
i. 11/132 KV GT 3-Non-dir O/L + 1-Non-dir E/L -- Differential or Overall
relay and/or standby E/F + differential, Overflux,
REF Buchholz,
OLTC Buchholz,
PRV, OT, WT
i. 220 /6.6KV 3-Non-dir O/L + 1-Non-dir E/L 3-Non-dir. O/L relays Differential, Overflux,
Station T/Fs relay and/or standby E /F + Buchholz,
REF OLTC Buchholz,
PRV, OT, WT
1 132/33/11KV upto 8 MVA 3 O/L relays + 1 E/L 2 O/L relays + 1 E/L Buchholz, OLTC
relay relay Buchholz, OT, WT
2 132/33/11KV above 8 MVA 3 O/L relays + 1 dir. E/L 3 O/L relays + 1 E/L Differential,
and below 31.5 MVA relay relay Buchholz, OLTC
Buchholz, OT, WT
3 132/33KV, 31.5 MVA & 3 O/L relays + 1 dir. E/L 3 O/L relays + 1 E/L Differential,
above relay relay Overflux,
Buchholz, OLTC
PRV, OT, WT
4 220/33 KV, 31.5MVA & 3 O/L relays + 1 dir. E/L 3 O/L relays + 1 dir. relay Differential,
50MVA 220/132KV, relay Overflux,
100 MVA Buchholz, OLTC
PRV, OT, WT
5 400/220KV 315MVA 3 directional O/L relays 3 directional O/L relays Differential,
(with dir.highset) (with dir.highset)+1 Overflux,
+1 directional E/L relays. directional E/L relays. Buchholz, OLTC
Restricted E/F relay Restricted E/F relay PRV, OT, WT and
+ 3 Directional O/L overload (alarm)
relays for action relay
Breaker failure protection: The LBB protection scheme will be
provided for all 220KV stations (along with
busbar protection scheme)
Transformers ;
o Instant of switching in
o Design of transformer
o Type of transformer connection
o Method of neutral grounding
o The fault MVA rating of transformer
o When transformers connected in parallel.
A Differential relay compares the currents on both sides of the
transformer. As long as there is no fault within the protected
equipment (Transformer), the current circulates between the two
CTs and no current flows through the differential element. But for
internal faults the sum of the CTs secondary currents will flow
through the differential relay making it to operate.
Two basic requirements that the differential relay connections
are to be satisfied are :
a) It must not operate for load or external faults.
b) It must operate for internal faults.
• The Protective zone of a Differential relay
includes faults in Transformer, faults on
Buses or cables between CT and
transformer and then rapidly initiate
disconnection of the supply to the main
transformer. Then damages as well as non-
selective tripping of other protective relays
are prevented.
As on-load tap change facilities are invariably provided
in the grid transformers, any departure from the nominal
tap position will result in spill currents in the relay circuits.
Further, the CTs are often of different types and have
dissimilar magnetization characteristics, again resulting in
spill current during heavy through fault conditions.