Earthing Practices New
Earthing Practices New
• Earth: The conductive mass of the earth, whose Electric Potential at any
point is conventionally assumed and taken as ZERO.
• Earth Electrode: A Conductor or group of Conductors in Intimate
contact with and providing as electrical connection to earth.
• Earth Electrode Resistance: The resistance of an earth electrode to
the general mass of earth.
• Earthing Conductor: A protective conductor connecting the main
earthing terminal to an earth electrode or other means of earthing.
• Equipotential Bonding: Electrical connection putting various
exposed conductive parts and extraneous conductive parts at a
substantially equal potential.
Example: Inter connect protective conductor, earth continuity
conductors and risers of AC/HV Systems if any.
EARTHING PRACTICES
Based on IS:3043-1987 Standard
• Lightning
• Switching Surges
• Static Electricity
• Contact with High Voltage
• Resonant Condition
• Restriking ground faults
International Classification of System Earthing
If / A = K x 1/ t or A = If t / K
K1sec =136 – 170 for copper, 90 – 112 for Al, 49 – 62 for Steel
K3sec =79 – 98 for copper, 52 – 65 for Al, 28 – 36 for Steel
Initial Temp : 400 C to 3950 C for Cu, 3250 C for Al, 5000 C Steel
Earth Fault Protection
• Firstly – Voltages appear between exposed conductive parts
if constituting a shock hazard (Indirect Contact)
• Secondly – Fault current that flows in phases and protective
conductors of the circuit fading the faulty equipment which
may be of a such a magnitude as to cause excessive
Temperature.
The earth fault loop Impedance has to be low enough to
allow adequate earth fault current to flow to cause an over
current protective device in the faulty circuit to operate in
sufficiently short time.
Where it is not possible to achieve a low enough earth fault
loop impedance, disconnection may be initiated by fitting a
RCD or Voltage operate ELCB.
Earthing Conductors
• Bare Copper Conductors – minimum 25 mm2 cross
section Area.
• Bare Steel Conductors – minimum 50 mm2 cross
section Area.
• Aluminium or Copper clad Aluminium conductors
not allowed underground.
• Minimum Cross section area of copper or coated
steel should be 16 mm2.
• Metallic conduits, Ducts, trunks can be used as
circuit protective conductors.
• If flexible metal conduits are used, separate
conductor to be used to maintain integrity of the
path.
O.C.Protective device for E/F Protection
• A contact potential of 65 Volts can be tolerated by human
body for 10 sec.
• A contact potential of 250 Volts can be withstood by a
human body for not more than 100 milli sec.
Note: The depth of the burial is not more than 1/20th of spacing.
The Crank of the megger should be 135 rpm.
DATA Processing Installations
Leakage current measurements are prescribed in is : 10422
– 1982.
High Integrity Earth Connections: The aim of providing
high integrity earth connection by using robust or
duplicate conductors in association with permanent
connections.