Prepare Setting Files: Main Points To Remember

1) The document discusses the SFT 2841 software for connected mode operation. 2) When in connected mode, the software allows monitoring and setting protection parameters for Sepam units connected via a network. 3) Key functions include viewing measurements, alarms, settings parameters, and diagnosing protection devices.

Uploaded by

Thức Võ
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
132 views40 pages

Prepare Setting Files: Main Points To Remember

1) The document discusses the SFT 2841 software for connected mode operation. 2) When in connected mode, the software allows monitoring and setting protection parameters for Sepam units connected via a network. 3) Key functions include viewing measurements, alarms, settings parameters, and diagnosing protection devices.

Uploaded by

Thức Võ
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 40

SFT 2841 IN CONNECTED MODE

 Prepare setting files C Main points to remember

B Parameter setting

?
A Overview of the software
Situate SFT 2841
connected
Starting the application

 Click on the icon Same access for SFT


disconnected

 Select the working language

 Choose the operating mode:

– connected
– point to point via the front panel
– via the network

SFT2841 connected EN 2007_01.ppt


2
Connection via the network

 Choice of the network

 If required: creation or
modification of the
network

 Connection to Sepam
units via the network

 Starting of SFT 2841


software on the chosen
station

SFT2841 connected EN 2007_01.ppt


3
SFT 2841 expert UMI

 The protection and parameter setting data


may be saved.

 Reports may be edited.

SFT2841 connected EN 2007_01.ppt


4
PARAMETER SETTING

C Main points to remember

B Parameter setting

?
A Overview of the software
Situate SFT 2841
connected
Current operation

 Metering and operating


data
– alarm messages
– tripping current
– number of operations
– logic status of inputs,
outputs and LEDs

 Parameter setting
– of each protection
function
– of control logic
– of general installation
and Sepam data

SFT2841 connected EN 2007_01.ppt


6
Logipam

– Selection
– Choice in the list
– Apply
– Activate

– Delete

– Download onto the PC

– Automatic updating

SFT2841 connected EN 2007_01.ppt


7
Logipam internal resources

 LOGIPAM:
– internal bits
– counters
– clocks
– delays

SFT2841 connected EN 2007_01.ppt


8
General information on connected mode

– Connection
– Sepam type
– Sepam name
– Code operating mode
– Remote control
– Internal clock

SFT2841 connected EN 2007_01.ppt


9
General diagnosis
Series 20

– General characteristics
– Software versions
– Sepam status
– Clock with time-setting
– Presence of modules
– Monitoring of
communication exchanges

SFT2841 connected EN 2007_01.ppt


10
General diagnosis
Series 40

– General characteristics
– Software versions
– Sepam status
– Clock with time-setting
– Presence of modules
– Monitoring of
communication exchanges

SFT2841 connected EN 2007_01.ppt


11
General diagnosis
Series 80

– General characteristics
– Software versions
– Sepam status
– Clock with time-setting
– Presence of modules
– Monitoring of
communication exchanges

SFT2841 connected EN 2007_01.ppt


12
Diagnosis: LED, input and output status
Series 40 & 80

– Display of LEDs
– Display of validated inputs
– Display of outputs

– Testing of 3s pulse outputs

SFT2841 connected EN 2007_01.ppt


13
Diagnosis: remote indication (TS) status
Series 40 & 80

– Status transmitted via the


communication link

SFT2841 connected EN 2007_01.ppt


14
Measurements
Series 80

Network measurements:
 Current measurements
– rms
– demand
– maximum
– residual
– additional

 Voltage measurements
– phase-to-neutral
– phase-to-phase
– positive-sequence
– negative-sequence

 Frequency measurement

SFT2841 connected EN 2007_01.ppt


15
Measurements: vector diagram
Series 80

 Display
– voltage
– current

 Select
– scale
– référence

SFT2841 connected EN 2007_01.ppt


16
Power and energy measurements
Series 80

 Power measurements
– active
– reactive
– apparent
– power factor

 Energy measurements
– active
– reactive

SFT2841 connected EN 2007_01.ppt


17
Temperature measurements
Series 80

 MET 148 modules

SFT2841 connected EN 2007_01.ppt


18
Network diagnosis
Series 80

– Unbalance ratio
– Phase displacement
– Number of trips
– Phase
– Earth
– Total Harmonic Distortion

SFT2841 connected EN 2007_01.ppt


19
Network diagnosis
Series 80

 Machine diagnosis
– Differential measurements
– Phase angles
– Impedance measurements

– Thermal overload

– Running hours counter

SFT2841 connected EN 2007_01.ppt


20
Network diagnosis
Series 80

 Tripping contexts
– Selection by date

SFT2841 connected EN 2007_01.ppt


21
Switchgear diagnosis
Series 80

– Cumulative breaking
current
– …

SFT2841 connected EN 2007_01.ppt


22
Alarm management
Series 80

 Current alarms

– Not acknowledged

– Clear
– Reset

 Alarm history
– 200 alarms

SFT2841 connected EN 2007_01.ppt


23
Disturbance recording
Series 80

– Selection by
date
– Recovery of recording

– Voluntary trigger

SFT2841 connected EN 2007_01.ppt


24
On-line help
Series 80

 On-line help

SFT2841 connected EN 2007_01.ppt


25
MAIN POINTS TO REMEMBER

C Main points to remember

B Parameter setting

?
A Overview of the software
Situate SFT 2841
connected
Network diagnosis functions
Tripping current
 This function gives the RMS values of the phase currents and residual currents at time
of the last trip.

 The measurement is defined as the maximum RMS value measured during a 30 ms


interval after the activation of the O1 output.

Acquisition of tripping current TRIPI1.

RETURN

SFT2841 connected EN 2007_01.ppt


27
Machine operating assistance functions
Current phase displacement
 Current phase displacement between the main phase currents (I)
and additional phase currents (I') (1, 2, 3) is calculated for each
phase.

 The angle is measured in the clockwise direction.

 The information is used to check Sepam wiring when 87T protection


functions are implemented.

I

I’1

RETURN

SFT2841 connected EN 2007_01.ppt


28
Metering functions
Power factor (Cos)
 This function gives the phase displacement between the phase
currents and the phase-to-neutral voltages.

 The + and - signs and the IND (inductive) and CAP (capacitive)
indications give the direction of power flow and the type of load.

Q
V
-CAP +IND

I P
-IND +CAP

RETURN

SFT2841 connected EN 2007_01.ppt


29
Network diagnosis functions
Phase displacement
 This function gives:
Io
– phase displacement measured between the residual voltage and residual
current in the trigonometric direction
0 Vo
– phase displacement between the V1, V2, V3 voltages and I1, I2, I3
currents respectively, in the trigonometric direction
I
 The measurements are used during Sepam commissioning to check
 V that the voltage and current inputs are wired correctly.

 The angle is positive when the current is leading compared to the


voltage (trigonometric direction).

 the angle is modified by 180° by the setting incomer / feeder.

RETURN

SFT2841 connected EN 2007_01.ppt


30
Machine operating assistance
Differential / through current
 Differential / through current is calculated for the implementation
of the differential protection functions 87T and 87M.
 It is calculated for each phase by:
 
    I  I
I diff  I  I  It 
2
 When a transformer is used (87T), the Idiff / It calculation takes
into account the vector shift and transformation ratio..
 The Idiff / It value is expressed with respect to In, the rated
current of the main channels.

Idiff = Iadjusted + It = max ( Iadjusted ,


I’adjusted I’adjusted )

RETURN

SFT2841 connected EN 2007_01.ppt


31
Metering functions
Physical values measured
 Sepam measures the following physical values:
– phase current (3I)
– residual current (Io)
– phase voltage (3V)
– residual voltage (Vo)
 Each measured signal is processed by Sepam to produce all
the values necessary for the metering, diagnosis and protection
functions.

RETURN

SFT2841 connected EN 2007_01.ppt


32
Metering functions
RMS measurement
 RMS measurement is only used by the phase current metering
function and for the thermal overload protection function (49). The
RMS values take into account harmonics up the the 13th.

 For all other metering and diagnosis functions, the H1 fundamental


50 Hz or 60 Hz component is used.

RETURN

SFT2841 connected EN 2007_01.ppt


33
Metering functions
Residual current
 This function gives the RMS value of the residual current obtained
by:
– measurement: Io
– calculation of the sum of the phase currents: Io

 Accuracy at Ino: ±1%.


 Accuracy ± 2% from 0.3 to 1.5 Ino
 Accuracy ± 3% from 0.1 to 0.3 Ino

 The measurement range extends to 40 Ino when Io measurement


is used. In the other cases, the range extends to 20 Ino.

RETURN

SFT2841 connected EN 2007_01.ppt


34
Metering functions
Demand phase current

A Demand current

5mn 5mn 5mn 5mn 5mn


100A

55A 63A 89A 78A 59A t

 Resetting to zero:
– by the clear key on the display unit if one of the two screens is
displayed,
– by the clear command in the SFT2841 software,
– via the communication link (remote control order TC4).
RETURN

SFT2841 connected EN 2007_01.ppt


35
Metering functions
Peak demand current
 At the end of each integration period, i.e. once the new demand
current values are available, the function determines the greatest
demand current value obtained since the last reset.

A Peak demand current

5mn 5mn 5mn 5mn 5mn


100A

55A 63A 89A 89A 89A t

RETURN

SFT2841 connected EN 2007_01.ppt


36
Metering functions
Phase-to-phase voltage
 This function gives the RMS value of the 50 or 60 Hz
component of the phase-to-phase voltages.

 U21 voltage between phases 2 and 1 (U21=V1-V2)


 U32 voltage between phases 3 and 2 (U32=V2-V3)
 U13 voltage between phases 1 and 3 (U13=V3-V1)

– by calculation when 3 phase-to-earth VTs are connected,


– by measurement (U21 and U32) and by calculation (U13) when 2
phase-to-phase VTs are connected,
– by measurement (U21) when only one phase-to-phase VT is
connected, in which case the U32 and U13 voltages are not
available.

RETURN

SFT2841 connected EN 2007_01.ppt


37
Metering functions
Frequency
 This measurement is based on:
– U21 if only one phase-to-phase voltage is available,
– positive sequence voltage if the U21 and U32 measurements are
available.

 The frequency is not displayed (replaced by ****) if:


– U21 or Vd is less than 40% of Un.
– frequency is out of range.

 Accuracy at Unp: ±0.01Hz


 25 to 65 Hz range Sepam series40 and 80
 45 to 55 Hz if 50Hz Sepam series 20
 55 to 65 Hz if 60Hz Sepam series 20

RETURN

SFT2841 connected EN 2007_01.ppt


38
Metering functions
Power factor (Cos)
 Capacitive/inductive circuit:
 If V is leading compared to I, in the trigonometric (counter-clockwise)
direction, then  is positive.
 A capacitive (CAP) circuit is one in which the current is leading
compared to the voltage ( <0).
 An inductive (IND) circuit is one in which the current is lagging
compared to the voltage ( >0).

V
 
I I

V
RETURN

SFT2841 connected EN 2007_01.ppt


39
Metering functions
Active, reactive and apparent power
 For an incoming circuit:  For an outgoing circuit:
– Power supplied to the busbars is negative.
– Power supplied to the busbars – Power supplied by the busbars is positive.
is positive.
– Power supplied by the busbars
is negative.

Direction of Direction of
power flow power flow

RETURN

SFT2841 connected EN 2007_01.ppt


40