SA14 Subsystem Configuration Modbus
SA14 Subsystem Configuration Modbus
Subsystem Configuration
(Modbus)
• Bit device : This refers to data where each bit has a meaning. An
internal relay is equivalent to a bit device.
• Word device : This refers to data where a word unit (1 word = 16 bits)
contains the meaning. A holding register is equivalent to a word device.
HOLDING A 10
REGISTER
4 03
B XXXXX 06
Function code:
A:
Read: Read a packet of data designated on the Communication I/O Builder in word
units.
Write: Write a packet of data designated on the Communication I/O Builder. With
readback.
B:
Read: Read a packet of data designated on the Communication I/O Builder in word
units.
Write: Only write the changed single bit device or single word device to the
subsystem. With readback.
Readback function:
When there is read back, FCS reads the status of the devices designated in the
Communication I/O Builder back, then compare them with those stored in the I/O
image of FCS. The communication packet to write to the designated devices of
Modbus PLC is sent when discrepancy is detected.
Select serial
communication
Select
Communication
module
Select for
Redundant card
Select Modbus
Transmission
Select Parity bit request
Reception carrier
detection
Connection method
of the ALR121 (2-
Element- With respect to the address of the subsystem data buffer, the
element numbers are displayed on Communication I/O Builder. The
element number is not for set, only for display
Buffer- This sets the buffer for the communicated data. This is a required
setting item of the Communication I/O Builder
Scan- Set whether to read the communication I/O Analog data into the
communication I/O data buffer at the beginning of high-speed scan of the
FCS.
• The default value Scan setting is 1 Second.
Service Comment -A text comment can be set.
Label- The name of the function block I/O terminal can be set as a user-
defined label.
YOKOGAWA INDIA LIMITED Page.14
Subsystem Configuration -Modbus
Modbus I/O map Generation :
Accessing subsystem data varies according to the type of communication
module used
TAG_1
PVI
IN
%WW0001
Subsystem
[Analog Input]
16 Bit data
Gain =
Bias =
Redundant V-net
ALR121
Modbus-RTU
Dual Redundant Link
FG
TX+ 12 RX-
RX+ 14 TX-
TX- 11 RX+
RX- TX+
13
SG SG
15
FG
TX Send Data
RX Receive Data
GND Signal Ground
Error Codes:
A3B0 : No Response
A3B1 : Inappropriate station number
A3B5 : Too many communication processing points
A3B6 : Write to a read-only device occurred
A3C3 : Function code error
A3C2 : Address error