Menghitung Kebutuhan Titik Lampu Pada Ruangan Rumah Tinggal: Fisika Bangunan 2

This document discusses calculating lighting requirements for rooms in a residential home. It provides recommended lighting levels in lux for different room types like living rooms, bedrooms, dining rooms, and bathrooms. It also shows examples of calculating the number of light fixtures needed for different sized rooms using the formula: N = E x L x CU x LLF, where N is the number of fixtures, E is the recommended lighting level, L is the room area, CU is the coefficient of utilization, and LLF is the light loss factor. The document provides the calculations for several example rooms.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
102 views13 pages

Menghitung Kebutuhan Titik Lampu Pada Ruangan Rumah Tinggal: Fisika Bangunan 2

This document discusses calculating lighting requirements for rooms in a residential home. It provides recommended lighting levels in lux for different room types like living rooms, bedrooms, dining rooms, and bathrooms. It also shows examples of calculating the number of light fixtures needed for different sized rooms using the formula: N = E x L x CU x LLF, where N is the number of fixtures, E is the recommended lighting level, L is the room area, CU is the coefficient of utilization, and LLF is the light loss factor. The document provides the calculations for several example rooms.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 13

Fisika Bangunan 2

Istiana Adianti, ST., MSc

Menghitung Kebutuhan
Titik Lampu Pada Ruangan
Rumah Tinggal

Oleh:
Rezha Aulia Narulita
161411567
KUAT PENERANGAN (E)

Perkantoran = 200 - 500 Lux


Apartemen/Rumah = 100 - 250 Lux
Ruang Tamu = 50 - 100 Lux
Ruang keluarga = 50 - 100 Lux
Tempat Baca = 200 Lux
Ruang Makan = 100 - 200 Lux
Ruang Tidur = 20 - 50 Lux
Selasar/Hall = 25 - 50 Lux
Hotel = 200 - 400 Lux
Rumah Sakit/Sekolah = 200 - 800 Lux
Basement/Toilet
/Coridor Hall/Gudang
/Lobby = 100 - 200Lux
Restaurant/Store/Toko = 200 - 500 Lux
Ruang
Tamu Lumen

Rumus:
𝑨
𝑵 = 𝑬 . 𝑳 . CU . LLF

7,5𝑚²
N = 100 Lux . . 0,5 . 0,8
1800 𝑙𝑢𝑚𝑒𝑛

N = 1,041667

Dibulatkan jumlah =
1 Titik Lampu

General Lighting
Indirect Lighting

Contoh lampu yg digunakan


Kamar Tidur Ut

Lumen

Rumus:
𝑨
𝑵 = 𝑬 . 𝑳 . CU . LLF

14𝑚²
N = 50 Lux . . 0,5 . 0,8
1400 𝑙𝑢𝑚𝑒𝑛

N = 1,25
Dibulatkan jumlah =
1 Titik Lampu

Self Light
General Lighting

Contoh lampu yg digunakan


Dapu
rLumen

Rumus:
𝑨
𝑵 = 𝑬 . 𝑳 . CU . LLF

9𝑚²
N = 100 Lux . . 0,5 . 0,8
1020 𝑙𝑢𝑚𝑒𝑛

N = 2,2058
Dibulatkan jumlah =
2 Titik Lampu

Indirect Lighting

General Lighting

Contoh lampu yg digunakan


Kamar Mandi/W
Lumen

Rumus:
𝑨
𝑵 = 𝑬 . 𝑳 . CU . LLF

3,75 𝑚²
N = 100 Lux . . 0,5 . 0,8
665 𝑙𝑢𝑚𝑒𝑛

N = 1,409

Dibulatkan jumlah =
1 Titik Lampu

Contoh lampu yg digunakan


Kamar
Anak
Lumen

Rumus:
𝑨
𝑵 = 𝑬 . 𝑳 . CU . LLF

11 𝑚²
N = 50 Lux . . 0,5 . 0,8
1020 𝑙𝑢𝑚𝑒𝑛

N = 1,348039

Dibulatkan jumlah =
1 Titik Lampu

Self Light
General Lighting

Contoh lampu yg digunakan


Ruang Makan

Lumen

Rumus:
𝑨
𝑵 = 𝑬 . 𝑳 . CU . LLF

21 𝑚²
N = 80 Lux . . 0,5 . 0,8
1800 𝑙𝑢𝑚𝑒𝑛

N = 2,333
Dibulatkan jumlah =
2 Titik Lampu

Indirect Lighting
General Lighting

Contoh lampu yg digunakan


Ruang
Keluarg
Lumen

a
Rumus:
𝑨
𝑵 = 𝑬 . 𝑳 . CU . LLF

21 𝑚²
N = 80 Lux . . 0,5 . 0,8
1800 𝑙𝑢𝑚𝑒𝑛

N = 2,333

Dibulatkan jumlah =
2 Titik Lampu

Indirect Lighting
General Lighting

Contoh lampu yg digunakan


Kamar
Mandi /WC Lumen

Rumus:
𝑨
𝑵 = 𝑬 . 𝑳 . CU . LLF

3 𝑚²
N = 100 Lux . . 0,5 . 0,8
665 𝑙𝑢𝑚𝑒𝑛

N = 1,12782
Dibulatkan jumlah =
1 Titik Lampu

Contoh lampu yg digunakan