Chapter 3
Chapter 3
SUMIT K RATHORE
EE DEPT, GCET
Content
Synthesis of Unsymmetrical phasors from their symmetrical components
Power in terms of symmetrical components
Sequence circuits of Y and Δ impedances
Sequence circuits of a symmetrical transmission line
Sequence circuits of the synchronous machine
Sequence circuits of a Y- Δ transformer
Unsymmetrical series impedances
Sequence networks
2
Instruction Objective of lesson
Normal types of fault are:
Fault due to lightning
Tree limbs falling on the line
Wind damage
Insulation deterioration
Vandalism
4
Types of fault
Symmetrical fault :
Usually three phase to ground fault
Unsymmetrical fault
The fault is unbalanced in nature
5
Sources of Asymmetrical fault are (cont.)
One phase open circuit
6
Sources of Asymmetrical fault are (cont.)
One phase open circuit
7
Sources of Asymmetrical fault are (cont.)
SLG fault
8
Need for fault analysis
Design of protection system requires the
knowledge of fault current.
The information obtained from the fault studies are
used:
to select the sizes of circuit breaker,
fuse and characteristic,
setting of relay.
9
Instruction Objective of lesson
Upunitl now we have studied faults that are symmetrical
(all the three lines are shorted) but this kind of fault rare in
system, and unsymmetrical faults are major and to study
them or analyze them we need a simple technique this is
called symmetrical component analysis discovered by C L
Fortescue.
SYNTHESIS OF UNSYMMETRICAL PHASOR FROM THEIR
SYMMETRICAL COMPONENT
CL Fortescue suggested that n related unbalanced phasors
can be resolved into n system of balanced phasors called the
symmetrical components of the original phasors.
The n phasors of each set of components are equal in
magnitude(length) and the angle between adjacent phasors
of the set are equal.
This method is applicable to any unbalanced systems we
will confine attention to three phase system.
SYNTHESIS OF UNSYMMETRICAL PHASOR FROM THEIR
SYMMETRICAL COMPONENT
According to CL Fortescue unbalanced phasors of three phase system can be
resolved into three balanced systems of phasors. The balanced sets of
components are :
1. positive sequence component consisting of three phasors equal in
magnitude, displaced from each other by 120 in phase and having same
phase sequence as the original phasor.
2. negative sequence components are consisting of three phasors equal in
magnitude, displaced from each other by 120 in phase and having phase
sequence opposite to that of original phasor.
3. zero sequence components consisting of three phasors equal in magnitude
and with zero phase displacement from each other.
SYNTHESIS OF UNSYMMETRICAL PHASOR FROM THEIR
SYMMETRICAL COMPONENT
SYNTHESIS OF UNSYMMETRICAL PHASOR FROM THEIR
SYMMETRICAL COMPONENT
It is customary when solving problem by symmetrical components to
designate the three phases of system as a, b and c of the voltages and currents
of sequence of positive sequence components of unbalanced phasors is abc,
negative sequence as acb.
If original voltage sequence is Va, Vb, and Vc then positive sequence sets of
symmetrical components are designated by subscript 1, that becomes Va1,
Vb1, Vc1.
Similarly negative sequence components are Va2, Vb2, Vc2 and the zero
sequence components are Va0, Vb0 and Vc0.
And phasor representing currents are represented by I followed by subscripts
SYNTHESIS OF UNSYMMETRICAL PHASOR FROM THEIR
SYMMETRICAL COMPONENT
Since each of the original unbalanced phasors is the sum of its components,
the original phasors expressed in terms of their components are
=1ej2л/3= -0.5+j0.866
OPERATORS
If operator is applied twice in succession the phasor is rotated through 240
and three succession
a2= 1/_240o=-0.5-j0.866
And
a3=1/_360o=1/_0o=1
An important difference must be noted between uses of operators j and a. the
operator j is unit magnitude at 90 and –j means that complex number j is
changed by an angle of 180 to give unit magnitude at 270 thus -j
j=1/_90 and –j=1/_270=1/_-90
Hence it is said sometimes that +j indicate rotation through 90 and –j indicate
rotation through -90 statement is correct but a similar statement does not
apply to operator a since
A=1/_120
OPERATORS
-a=1/_120 x 1/-180 = 1/_ -60
a -a2
-1 -a3 1 a3
-a
a2
SYMMETRICAL COMPONENT OF UNSYMMETRICAL
PHASORS
Lets see how to solve unsymmetrical phasors into their symmetrical
components.
Synthesis of three unsymmetrical phasors form three sets of
symmetrical phasors done by use of equation as below
Or in matrix form
SYMMETRICAL COMPONENT OF UNSYMMETRICAL
PHASORS
For convenience we let
Then as
Ia+Ib+Ic=In
Which shows complex power can be computed from symmetrical components of voltage and
currents of unbalanced three phase circuit.
PHASE SHIFT OF SYMMETRICAL COMPONENT IN STAR-
DETLA TRANSFORMER BANK
Before we learn phase shift let us examine standard method of marking
transformer terminals.
Primary and secondary is wound on core as in figure.
High voltage winding marked by H1, H2 and low tension winding is
marked as X1, X2.
Current flowing from H1 to H2 produces flux in common core in the same
directions current flowing from X1 to X2.
Transformer theory shows that current must flow out at terminal X1 when
current is flowing into terminal H1 with magnetizing current neglected for
the magneto motive forces produced by the currents
in two coils must cancel each other all times.
The flux common to both the coil is due
to magnetizing current alone.
PHASE SHIFT OF SYMMETRICAL COMPONENT IN STAR-
DETLA TRANSFORMER BANK
For that we have to mark the terminal by dot that indicate
direction of current flow from the terminals whether the
current Ip and Is are in phase or out of phase by 180 degree.
The direction of arrow and dot marked on winding terminal
H1 and X1 are positive at the same time with respect to H2
and X2 if dot is on upper side in both winding that is called
in phase
If on low tension side dot is on bottom of winding that
indicate both current are out of phase by 180degree.
PHASE SHIFT OF SYMMETRICAL COMPONENT IN STAR-
DETLA TRANSFORMER BANK
For three phase transformer high tension terminals are
marked H1, H2 and H3 & for low tension terminals are
marked X1, X2 and X3.
For the figure YY or ∆ ∆ transformers the markings are
such that voltages to neutral from terminals H1, H2 and H3
are in phase with the voltages to neutral from terminals X1,
X2 and X3 respectively .
PHASE SHIFT OF SYMMETRICAL COMPONENT IN STAR-
DETLA TRANSFORMER BANK
High tension terminals H1, H2, H3 are connected to
termoinals A,B,C respectively and phase sequence is ABC
similarly for low tension winding X1,X2,X3.
Now carefully see winding AN of Y connected side which
is linked magnetically with phase winding bc on ∆
connected side.
Location of dots on windings shows that VAN is in phase
with Vbc
PHASE SHIFT OF SYMMETRICAL COMPONENT IN STAR-
DETLA TRANSFORMER BANK
American standard for designating terminals H1 and X1 on
Y- ∆ transformer requires that positive sequence voltage
drop from H1 to neutral lead the positive sequence voltage
drop from X1 to neutral by 30 degree regardless of whether
Y or ∆ winding is on high tension side.
Similarly voltage from H2 to neutral leads the voltage from
X2 to neutral by 30 and voltage from H3 to neutral leads
the voltage from X3 to neutral by 30 degree.
VA1 leads Vb1 by 30degree which enables us to determine
that terminal to which phase b is connected should be
labeled X1.
PHASE SHIFT OF SYMMETRICAL COMPONENT IN STAR-
DETLA TRANSFORMER BANK
PHASE SHIFT OF SYMMETRICAL COMPONENT IN STAR-
DETLA TRANSFORMER BANK
PHASE SHIFT OF SYMMETRICAL COMPONENT IN STAR-
DETLA TRANSFORMER BANK
Van Vbc
PHASE SHIFT OF SYMMETRICAL COMPONENT IN STAR-
DETLA TRANSFORMER BANK
Figure(b) shows that normal designation of winding
terminals by which we normally designate the transformer
winding but figure (a) shows nomenclature is most
convenient for computations in former case we need to
exchange a for b, b for c and c for a.
PHASE SHIFT OF SYMMETRICAL COMPONENT IN STAR-
DETLA TRANSFORMER BANK
Inspection of positive and negative sequence phasor
diagram shows that Va1 leads VA1 by 90 and Va2 lags
VA2 by 90.
The diagram shows VA1 and VA2 in phase which is not
necessarily ture but phase shift between VA1 and VA2 does
not alter the 90 relation between VA1 and Va1 or between
VA2 and Va2.
PHASE SHIFT OF SYMMETRICAL COMPONENT IN STAR-
DETLA TRANSFORMER BANK
UNSYMMETRICAL SERIES IMPEDANCE
System becomes unbalanced only upon the occurrence of
unsymmetrical fault. Let see the system which having
unequal impedance.(We should reach to conclusion that is
important in analysis by symmetrical components)
The sequence impedances of rotating machines will generally differ from one another. This is due to the
different conditions that exist when the sequence currents flow. The flux due to negative-sequence
currents rotates at double the speed of rotor while that due to positive-sequence currents is stationary
with respect to the rotor. The resultant flux due to zero-sequence currents is ideally zero as these flux
components add up to zero, and hence the zero-sequence reactance is only due to the leakage flux. Thus,
the zero-sequence impedance of these machines is smaller than positive- and negative-sequence
impedances.
The positive- and negative-sequence impedances of a transmission line are identical, while the zero-
sequence impedance differs from these. The positive- and negative-sequence impedances are identical as
the transposed transmission lines are balanced linear circuits. The zero-sequence impedance is higher
due to magnetic field set up by the zero-sequence currents is very different from that of the positive- or
negative-sequence currents. The zero-sequence reactance is generally 2 to 3.5 times greater than the
positive- sequence reactance. It is customary to take all the sequence impedances of a transformer to be
identical, although the zero-sequence impedance slightly differs with respect to the other two.
POSITIVE AND NEGATIVE SEQUENCE NETWORK
Obtaining the values of sequence impedances of power system is to enable
us to construct the sequence network for the complete system.
The network of particular sequence shows all the paths for the flow of
current of that sequence in system.
Three phase synchronous generator and motors have internal voltages of
positive sequence only since they are designed to generate balance
voltages.
Since the positive and negative sequence impedances are same in static
symmetrical system.
conversion of positive sequence network to negative sequence network is
accomplished by changing if necessary only the impedances that represents
rotating machinery and by omitting the emfs
Electromagnetic forces are omitted on assumption of balanced generated
voltages and the absence of negative sequence voltages induces from
outside sources
POSITIVE AND NEGATIVE SEQUENCE NETWORK
Since all the neutral points of symmetrical three phase
system are at the same potential when balanced three phase
curents are flowing, all the neutral points must be at same
potential for either positive or negative sequence currents
Therefore neutral of symmetrical three phase system is the
logical reference potential for specifying positive and
negative sequence voltage drop and is the reference bus for
positive and negative sequence network.
Impedance connected between neutral of machine and
ground is not a part of either the positive or negative
sequence network because neither positive nor negative
sequence current can flow in impedance so connected.
ZERO SEQUENCE NETWORK
Zero sequence currents are same in magnitude and phase at
any point in all the phases of system
Therefore zero sequence current will flow only if return
path exists through which a completed circuit is provided.
The reference for zero sequence voltages is potential of the
ground at the point in the system at which any particular
voltage is specified.
Since zero sequence current may be flowing in ground, the
ground is not necessarily at same potential at all points and
the reference bus of zero sequence network does not
represent a ground of uniform potential.
ZERO SEQUENCE NETWORK
The zero-sequence components are the same both in magnitude and in
phase. Thus, it is equivalent to a single-phase system and hence, zero-
sequence currents will flow only if a return path exists. The reference point
for this network is the ground.
Case 2: Y-Y Bank with both neutral grounded: In this case, a path through transformer exists for the
zero-sequence current. Hence zero-sequence current can flow in both sides of the transformer
provided there is closed path for it to flow. Hence the points on the two sides of the transformer are
connected by the zero-sequence impedance of the transformer.
Case 3: Y- ∆ Bank with grounded Y: In this case, there is path for zero-sequence current to ground
through the Y as the corresponding induced current can circulate in the ∆. The equivalent circuit
must provide for a path from lines on the Y side through zero-sequence impedance of the
transformer to the reference bus. However, an open circuit must exist between line and the
reference bus on the ∆ side. If there is an impedance Zn between neutral and ground, then the zero-
sequence impedance must include 3Zn along with zero-sequence impedance of the transformer.
Case 4: Y- ∆ Bank with ungrounded Y: In this case, there is no path for zero-sequence current. The
zero-sequence impedance is infinite and is shown by an open circuit.
Case 5: ∆ -∆ Bank: In this case, there is no return path for zero-sequence current. The zero-
sequence current cannot flow in lines although it can circulate in the ∆ windings.
ZERO SEQUENCE NETWORK
Conclusion
The sequence networks are three separate networks which are the single-
phase equivalent of the corresponding symmetrical sequence systems.
These networks can be drawn as follows: For the given condition (steady
state, transient, or subtransient), draw the reactance diagram (selecting
proper base values and converting all the per unit values to the selected
base, if necessary). This will correspond to the positive-sequence network.
Determine the per unit negative-sequence impedances of all elements (if
the values of negative sequence is not given to any element, it can
approximately be taken as equal to the positive-sequence impedance).
Draw the negative-sequence network by replacing all emf sources by short
circuit and all impedances by corresponding negative-sequence
impedances in the positive-sequence network.
Determine the per unit zero-sequence impedances of all the elements and
draw the zero-sequence network corresponding to the grounding conditions
of different elements.
Conclusion
Unbalanced voltage and currents can be resolved into their symmetrical
components.
Problem are solved by treating each set of components separately and
super imposing the results
In balanced network having no coupling between phases the currents of
one phase sequence induces voltage drop of like sequence only
Knowledge of positive sequence is necessary for load flow studies on
power system
Fault calculation and stability studies that involves unsymmetrical faults
that needed negative and zero sequence components also.
Synthesis of zero sequence network requires particular care because the
zero sequence network may differ from others considerably
Reference
Elements of power system analysis by Willian D Stevenson Jr. International student edition
Power system analysis by JB Gupta
http://elearning.vtu.ac.in/P2/EE61/Ch03/html/0019.htm
http://nptel.iitm.ac.in/courses/Webcourse-contents/IIT-KANPUR/power-system/chapter_8/8_5.html
THANK YOU