Generator & Transformer Protection
Generator & Transformer Protection
Protection
By
Krishna Kumar, B.E., M.Tech, MIE
Assistant Engineer (R&D)
What is Protection?
The objective of a protection scheme is to
keep the power system stable by isolating
only the components that are under fault.
Performance and Design Criteria for System-
Protection Devices
• Reliability
• Selectivity
• Speed
• Cost
• Simplicity
• Size
Protection equipment for different types of generators with different rating
Protection relays for the generator transformer Unit
Standard:
ANSI/IEEE C 37.2 - 1979
Types of Generator Grounding
Types of Generator Grounding
1. Generator Protection
• Generators are designed to run at high load factor for a
large number of years and permits certain incidences of
abnormal working conditions.
• Load factor: It is used to describe how much the power
system is loaded compared to the peak load.
Requirements :
(i) Be triple pole type
(ii) Shall be able to operate when the fault current from
the generator terminals becomes low due to
excitation system characteristic
(iii) Shall have under voltage criteria
(iv) Shall reset to de-energised position if under-voltage
criteria disappears
Requirements:
(i) Be triple pole type
(ii) Have an alarm unit and a trip unit
(iii) Have a continuously adjustable negative sequence
current setting
(iv) Have alarm unit range covering negative phase
sequence current of 5-10% of generator rated current
continuously adjustable
(v) Have a definite time setting range of 1-10 secs.
associated with an alarm unit
(vi) Have a trip unit with a variable time current
characteristics matching with the generator I22t
characteristic
Generator Overload Protection (5 1G)
- Prevents the steam turbine and generator from exceeding the permissible
operating time at reduced frequencies
- Ensures that the generating unit is separated from the network at a preset
value of frequency that is less than the final stage of system load shedding
- Prevents the AVR from exciting the machine at reduced speeds when some
protective relays may not perform at all
- Prevent over fluxing of the generator. The over fluxing relay is used to
protect against small overfluxing for long periods while the over voltage
and under frequency relays also protect against large over fluxing for short
times
• The stator under frequency relay measures the frequency of the stator
terminal voltage
• Though under frequency tripping is recornmended by turbine
manufactures, care should be taken by grid operating personnel in ensuring
that machines are not run at lower frequencies and instead resort to means
like load shedding in the event of overload.
Requirements:
(i) Have one alarm stage and two tripping stages
(ii) Shall have setting of range of 45 Hz - 55 Hz with a
least count of 0.1 Hz for each stage
(iii) Timer for alarm stage have a range of 0.5 to 5
second with a least count of 0.5 second. Timers for
each tripping stage shall have range of 1 to 10
seconds with a least count of 0.1 second
(iv) Shall have undervoltage blocking
Setting Recommendations –
-Stator under frequency relay pick up level = 48.5 Hz
- Time delay for alarm - 2 Sec.
Inter turn fault protection (95G) :
• It is generally considered difficult to obtain reliable protection against short
circuit of one turn if the stator winding has large number of turns per phase.
• Inter turn fault protection is recommended only for machines where there is
a split winding and all the six terminals are brought out on the neutral side.
• For generator with split neutrals, conventional inter-turn fault protective
scheme comprises a time delayed low set over-current relay which senses the
current flowing in the connection between the neutrals of the stator winding.
• Alternatively a split phase differential protection may be used.
Requirements:
• (i) Over current relay with time delay (ii) Over current relay shall have built
in filters to reject higher harmonics (iii) Range of over current shall be
selected depending on maximum spill current for external fault
Setting Recommendation:
• Overcurrent relay shall be set to maximum unbalanced current in case of
external fault.
• Time delay 0.2 - 0.4 seconds
Generator Transformer Over Fluxing Protection (99 GT) :
-Overfluxing protection is provided to safeguard the generator, generator
transformer and unit auxiliary transformer against operation at flux
densities which may cause accumulative damage to the core.
-From the fundamental equation V = 4.44 x f x n x 4, the level of flux is
proportional to the ratio of terminal voltage to frequency (v/f). This ratio
is monitored by the protective relay.
-An over fluxing condition is more likely to occur while the generator is
separated from the system and the speed is allowed to drop, but it can
also happen with the machine on load if the tap changer of the generator
transformer (HV side) is on a low tap position and the excitation of the
generator is manually increased. In this case the increased generator
terminal voltage knay cause over fluxing tripping at nominal frequency.
-The over fluxing protection operates with a time delay after which the
tripping functions are executed.
-This protection must be provided for generator-transformers of size 10
MVA and above.
Requirements :
(i) Shall be phase to phase connected.
(ii) Shall operate on the principle of measurement of voltage io
frequency ratio.
(iii) Have inverse time characteristics compatible with generator
transformer over fluxing withstand capability for tripping.
(iv) Provide an independent alarm with a definite time delay of
value of V/f between 100% to 130% of rated value.
(v) Have a high resetting ratio of 98% or better.
Setting Recommendations:
The overfluxing capability of the transformer must be checked
and the characteristic matched accordingly for both alarm and
trip.
Generator Over Voltage Protection (59G):
-An over voltage on the terminals of the generator can
damage the insulation of the generator, bus ducting,
breakers, generator transformer and auxiliary
equipment such as voltage transformers, excitation
transformer etc.
-This should be provided for machines of all sizes,
hydro and thermal
Requirements:
(i) Be single pole type/or triple pole type
(ii) Shall have two separately adjustable stages
(iii)Have a continuously adjustable setting range of 100 - 140%
of rated voltage
(iv)Have a drop off to pick up ratio greater than 95%
(v) Have a continuously variable time delay setting range of 0.5 -
5 seconds for one relay and 2 to 20 seconds for the other
relay.
Setting Recommendations:
Stage 1 - Over voltage relay pick up - 1.15 x Vn
Timers t1 - 10 seconds
Stage 2 - Over voltage relay pick up - 1.3 x Vn
Timer t2 - 0.5 seconds
Dead machine protection (27/50G) :
-Despite existence of interlocking schemes, a number of generators
have been inadvertently energized while at stand still or on
turning gear. The generator and rotor may get damaged beyond
repair under this condition. Other protective relays like loss of
excitation, back up impedance, reverse power would operate with
delays and this is not admissible. The dead machine protection
permits fast tripping.
-This should be installed in switchyard panel rather than in
generator panel to ensure that protection is available during
maintenance periods when the generator protection can be
rendered inoperative by switching off the DC supply to the panel.
-This protection is recommended for all-machines of size 100 MVA
and above. The protection is connected to trip generator breakers,
generator transformer breaker and the HV Bus.
Requirements:
(i) Shall consist of 3 high speed over current relays of
range (0.02 - 20 In) to initiate instantaneous tripping
if generator terminal voltage is below set value.
(ii) Shall have under voltage relays of range (0.2-1 Un)
to permit operation of over current relays when
voltage is low
(iii) Shall have timers with adjustable range (0-605) to
avoid operation of protection for nearby fault when
the machine is in service.
(iv) Shall be secure against voltage transients at closing
Generator VT fuse failure monitoring (60G):
This has to be provided for all the machines since it is required
for blocking of relays which can mal-operate in the event of
PT fuse blowing in primary side or secondary side.
Requirements:
(i) Be triple pole type
(ii) Be able to detect fuse failure in both primary and secondary
side of VT
(iii)Have a fixed setting of 70% of rated voltage and have a
time delay of 40 to 50 milli- seconds on pick up
(iv)Be of voltage balance or equivalent type
(v) Have sufficient contacts to block tripping of those relays
which are voltage dependent and give alarm
Rotor ground fault protection:
This protection shall be provided for machines of all sizes. It is recommended
that the protection is connected only for alarm and the operator may take the
machine out at the earliest opportunity after the first earth fault has occurred.
The tripping logic should also include unit tripping in case field circuit
breaker opens when the machine is running.
Requirements:
(i) Shall be based on DC injection principle or low frequency AC injection
principle
(ii) Shall be single stage or two stages
(iii) Shall have built-in time delay to prevent unwanted operation of the relay
Alternatively
A sensitive voltage function operating on bridge measuring basis with auxiliary
equipment. This shall have two levels, one for alarm and one for trip.
Setting ranges : Alarm stage 100 ohm to 25 k ohm, Time delay 2-60 Seconds
Trip stage 100. ohm to 25 K ohm, Time delay 2-60 Seconds
Setting Recommendations:
- alarm level - 25 K ohm
- pick up level - 5 K ohm
- timer t1 - 1 seconds
- timer t2 - 5 seconds
Generator-Transformer Protection
Generator Transformer Differential Protection (87 GT/87 T):
Requirements:
(i) Be triple pole with individual phase indication
(ii) Have unrestricted instantaneous high set over current units which shall not
operate during inrush
(iii) Have an adjustable or multi bias setting
(iv) Have second harmonic or other inrush proof features and also shall be stable
under normal over fluxing conditions. Magnetising inrush proof feature shall not
be achieved through any intentional time delay e.g. use of timers to block relay
operation or using disc operated relays.
(v) Have one bias winding per phase and per C.T. input
(vi) Have an adjustable operating current
(vii) Have an operating time not greater than 30 milli seconds at 5 times of setting
(viii) Shall have facility for ratio and phase angle correction either through
auxiliary transformer or through in built provisions
Generator Transformer Backup Overcurrent
Protection (5 1 GT)
Requirements:
(i) Be triple pole type
(ii) Be of definite time over current type
(iii) Have an adjustable setting range of 50-200% of
rated current and 0.5 - 5 seconds time delay.
Generator Transformer Back Up Earth Fault
Protection (51 NGT):
This relay monitors the current in the generator
transformer neutral. It can detect faults in the
transformer HV side or in the adjacent network.
Requirements:
(i) Be of single pole type
(ii) Be of definite time characteristic
(iii)Have an adjustable setting range of 10 to 100%
of rated current
(iv)Have a timer setting range of 0.5 to 5 seconds
HV winding cum overhang differential protection (87 HV/87 NT) :
This is a unit type protection which operates for earth faults on the
generator transformer HV side and also covers a large portion of the
HV winding and the HV terminals upto the HV current transformers.
Requirements:
(i) Be triple pole type (Single pole if used as Restricted E/F Protection)
(ii) Have operating time less than 30 milliseconds at 2 times setting
(iii)Be high impedance or low impedance type
(iv)Operating current shall be 0.1 - 0.4 In
(v) High stability against maximum through fault condition, CT
saturation, harmonics and DC transients
(vi)Be provided with suitable non linear resistors across the relay to
limit the peak voltage to 1000 volts, in case of high impedance type
(vii)Be provided with faulty phase identification
UAT Protections
Unit Transformer Differential Protection (87 UAT):
• This is a unit type protection covering the unit
transformer and the cable connection to the unit
board.
• This protection operates for phase faults, but not for
single phase to earth faults as this current is limited
by the neutral earthing resistance.
• The unit transformer differential relay initiates a
general trip and unit shutdown
Requirements:
-Be triple pole with individual phase indication
-Have unrestricted instantaneous high set over current unit which shall
not operate during inrush
-Have an adjustable or multi bias setting
-Have second harmonic or other inrush proof features and also should be
stable under normal over fluxing conditions, magnetising inrush proof
feature shall not be achieved through any intentional time delay e.g.
use of timers to block relay operation or using disc operated relays.
- Have one bias winding per phase and per C.T. input
- Have an adjustable operating current
- Have an operating time not greater than 30 milli seconds at 5 times of
setting
- Shall have facility for ratio and phase angle correction either through
auxiliary transformer or through in built provisions
Unit Transformer back up over current protection
(51 UAT) Relay:
-Be triple pole type
-Be of definite time over current type
-Have an adjustable setting range of 50-200% of rated
current and 0.5 to 5 seconds time delay
Unit Transformer back-up earth fault
protection (51N UAT) :
(i) Be single pole type
(ii) Be of definite time over current type
(iii)Have a setting rage of 10-100% of rated
current and time setting range of 0.5-5
seconds
Unit transformer restricted earth fault protection (64
UAT):
(i) Be single pole type
(ii) Have operating time less than 30 milli seconds at 2 times
setting
(iii)Be high impedance or low impedance type
(iv)Operating current shall be 0.1 - 0.4 In
(v) High stability against maximum through fault condition,
CT saturation, harmonics and DC transients
(vi) Be provided with suitable non-linear resistors across the
relay to limit the peak .voltage to 1000 volts, in case of high
impedance type
(vii) Be provided with fault indication
Thank You