HVAC
HVAC
2011
• Design Conditions
• Indoor Design Conditions
• Outdoor Design Condition
• Envelop Optimization beyond code compliance
• Roof & Wall Insulation and U factor
• Fenestration Light transmittance and U factor
• Glass to Wall Ratio
• Glass Shading
• Tightness of Envelop
• Ventilation (Fresh & Exhaust Air)
• Why some standards encourage to exceed Ashrae 62.1 by 30% or more?
• Heat Recovery between fresh and exhaust air.
• Variable speed fans operation.
• Double Skin Commercial Hood??
Proper Design Conditions
• Design Conditions
• Indoor Design Conditions Ashrae Standard 55 -2010 Allows to raise the typically
used DB of 23.3 to 24.4 OC in hot ambient to a range of 24.4 to 25.5 O C while
Int’l Energy Conservation code (ICCC 2009) specify minimum indoor design
conditions of 24 O C
2 O 2 O
Average - Average -
Watt/m . K BTU/Hr/Ft . F Coeficient North East South West
W/m2 BTU/Hr /ft 2
Glass / Wall Heat Transmission (U=0.1) 3.8 6.4 7.7 5.9 6.0
Glass / Wall Heat Transmission (U=0.056) 8.3 9.5 8.7 11.5 9.5
Glass To wall Ratio : Why Mechanical Engineer are Passive?
• Mechanical Engineers are still on the receiving end with the architect and most
often don’t comment at all on the envelop or offers any advice to the architect
and developer.
• Architects tend to finalize the building architectural impression and offer it to the
owner at early stage of the project prior to the involvement of the mechanical
engineer.
• Architect are reluctant to change the ratio as often that involves unpaid work
variation that means time and cost.
• Shading to the southern façade is quite effective but can be rarely incorporated
once design is finalized.
• Building tightness test are now required in Abu Dhabi Emirate.
Fresh Air: The magic of Heat recovery
Preferred Solution
Notice Cladding
& Glass Colors
Fresh Air: The magic of Heat recovery
Alternative Solution
Notice Cladding
& Glass Colors
Fresh Air: The magic of Heat recovery
Non Recommended Solution
Minimum Wheel
CHILLED WATER
Efficiency < 65% 44°F/54°F
Fresh Air > 30% of Ashrae
Std 62.1 Supplied at
around 13OC
2" PRE FILTER BAG FILTER
Notice Cladding
& Glass Colors
SUPPLY AIR
FRESH AIR
PURGE AIR
• Fresh Air should not exceed the Amount specified in ASHRAE Standard 62.1
2010 in hot and humid countries and ignore the additional points achieved in few
Green buildings codes as you will be penalized in the energy consumption part.
EPA Indoor Air Quality Guide Quote: “source control is also a more cost-efficient
approach to protecting indoor air quality than increasing ventilation because
Notice Cladding
increasing ventilation can increase energy costs”. i.e. eliminating frying at your
& Glass Colors
homes will reduce the smell, fire hazard and your fat intake and improve your
Health and safety.
• Fresh air should not exceed that value of exhaust air by more than 10%.
• Residential Kitchen hood should be a circulating hood while permanent kitchen
exhaust of 50 CFM should be installed at the kitchen ceiling plenum level.
• Residential Kitchens and Toilet exhaust can utilize the same duct and both
should be used for heat recovery.
• Fresh air of 2 ACH should be supplied to lift lobbies to stop any cooking smell
mitigation.
Fresh Air: Key Recommendations (cont’d)
• Double Skin Commercial kitchen hoods are controversial where the rule of thumb
state that 80% make up air portion can be used in commercial kitchen is a recipe
of trouble
• Peripheral perforated plenum with low velocity is recommendedNotice
withCladding
the
possibility to cool the air down to 30 deg. C. & Glass Colors
• Preference to use UL listed hood with minimum exhaust flow and make use of
transfer air from dinning areas.
• VFD on both exhaust and make up air fans.
Recommended
Low air
velocity
< 0.4 m/s
X (75 FPM)