The document discusses why sliding stem control valves, Fisher ED valves with single ported, balanced plugs and cage guides, equal percentage trim, 316 stainless steel trim, PTFE packing, sizing valves for 60% opening, spring and diaphragm actuators, and two-stage digital positioners are recommended for control valve selection. Additional improvements could include smart digital positioners that communicate diagnostics over HART or fieldbus.
Download as PPTX, PDF, TXT or read online on Scribd
100%(1)100% found this document useful (1 vote)
385 views
Control Valve Selection & Sizing
The document discusses why sliding stem control valves, Fisher ED valves with single ported, balanced plugs and cage guides, equal percentage trim, 316 stainless steel trim, PTFE packing, sizing valves for 60% opening, spring and diaphragm actuators, and two-stage digital positioners are recommended for control valve selection. Additional improvements could include smart digital positioners that communicate diagnostics over HART or fieldbus.
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 13
Control Valve Selection & Sizing
Why Sliding Stem?
• Wider control range than rotary.
• Less intrusive maintenance than rotary.
• Less dead band and hysteresis than rotary. Control Valve Selection & Sizing Why Sliding Stem?
• Less chance of cavitation and noise than
rotary due to more evenly distributed pressure losses leading to higher pressure recovery factor 𝐹𝐿 . Control Valve Selection & Sizing Why Fisher ED?
• Single ported – This is preferred as differential
expansion issues experienced with double ported valves are avoided. • Balanced plug – This is preferred as none of our applications require tight shut off, so we are not concerned with extra leak path and can specify a smaller actuator. • Cage guided – Allows easy characterisation through correct cage selection. Control Valve Selection & Sizing Why Equal Percentage Trim?
• Linear trim only suitable for constant pressure drop
applications as shown below. Our applications do not have constant pressure drop. Control Valve Selection & Sizing Why Equal Percentage Trim?
• Quick opening trim typically suitable for on/off
control and relief applications. Our applications are all modulating control.
• Our applications have pumped flows and long
piping runs, as flow rate increases pump discharge pressures decrease and frictional pressure drops through the piping system increase reducing pressure drop across the valve. Control Valve Selection & Sizing Why Equal Percentage Trim?
Equal %
LINEAR Control Valve Selection & Sizing Why 316 stainless steel trim?
• Trim must be a compromise between cost and
good service life. • Cheap, low grade trim materials not suitable for hydrocarbon service. • Expensive alloys not justified for standard hydrocarbon service. • 316 is industry standard stainless offering reasonable resistance to erosion and corrosion without unjustifiable expense. Control Valve Selection & Sizing Why PTFE packing?
• PTFE packing preferred to graphite due to
reduced stem friction. • But PTFE only suitable up to 232℃ above which graphite should be specified. • All three of our applications have a normal working temperature of 50℃, well within range required for PTFE. • Extension bonnet not required at 50℃. Control Valve Selection & Sizing Why Size for Required 𝐶𝑣 at ~60% Opening?
• Valve must be sufficiently sized to pass
maximum flow capacity. • But over sized valves cost more and give poor control. • Oversized valves operate in 0 – 25% open region where gains are too high. • Extreme case – Imagine trying to fill a cup from a fire hydrant!!! Control Valve Selection & Sizing Why Size for Required 𝐶𝑣 at ~60% Opening?
• 60% opening typically around mid-point of
control range allowing good margin of openings either side for maximum and minimum flow. Control Valve Selection & Sizing Why Spring & Diaphragm Actuator?
• Spring and diaphragm actuators generally
have less friction than piston actuators. • More maintenance is required for piston actuators as piston actuator friction increases with age as o rings and lubrication wear. • Spring and diaphragm actuators have a faster response for small signal changes, piston actuators can be faster across full range. Control Valve Selection & Sizing Why a Two Stage Positioner? • Use of a positioner gives more accuracy due to position feedback and faster response due to ability to supply large quantities of air quickly. • Two stage positioner gives high sensitivity from pre-amplifier and good response across the range from power-amplifier. • Alternative spool type valve positioners do not have high gain preamplifier resulting in more dead time and slower response. Control Valve Selection & Sizing Further Positioner Improvements? • If included in First Vue Software a smart positioner such the Fisher DCV6200 may have been specified. • Allow valve diagnostics to be communicated over HART or fieldbus for maintenance. • Uses hall effect sensor for position feedback to eliminate backlash and wear associated with mechanical linkage.