0% found this document useful (1 vote)
159 views

Excitation System Introduction - 20150818

This document provides an overview of the EXC9000 excitation system, including its components, operation, and interfaces. It consists of three main cubicles (regulator, rectifier, de-excitation) that work together. The regulator cubicle controls excitation using multiple CPU channels for redundancy. It interfaces with other systems using CAN bus, MODBUS, and an HMI. The rectifier cubicle supplies power using thyristors and controls dynamic current. The de-excitation cubicle provides resistance and crowbar protection. Diagrams and pictures are included to illustrate the system and its parts.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (1 vote)
159 views

Excitation System Introduction - 20150818

This document provides an overview of the EXC9000 excitation system, including its components, operation, and interfaces. It consists of three main cubicles (regulator, rectifier, de-excitation) that work together. The regulator cubicle controls excitation using multiple CPU channels for redundancy. It interfaces with other systems using CAN bus, MODBUS, and an HMI. The rectifier cubicle supplies power using thyristors and controls dynamic current. The de-excitation cubicle provides resistance and crowbar protection. Diagrams and pictures are included to illustrate the system and its parts.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 41

Introduction of EXC9000

excitation system
System chart
Character
• Various CPUs co-operating;
• CAN bus communication;
• PSS2A software module;
• Digital signal processing;
• Residual voltage flashing
• Dynamic current equalization
• Multi-language HMI;
• MODBUS communication port;
• Featured debug software.
Regulator cubicle
• Two microcomputer channels
• One analog channel
• 4 circuit boards
• HMI
• Synchronize transformer
• Power module
Regulator chart

Ä£ÄâÁ¿×ÜÏß °å C ͨ µÀ ¿ª ¹ØÁ¿×ÜÏß °å ÖÇÄÜI/O°å ÈË»ú½çÃæ

CAN×ÜÏß

DSP CPU I/O I/O CPU DSP


µ¥Æ¬»úϵ ͳ °å

Aͨ µÀ¹¤ ¿Ø»ú Bͨ µÀ¹¤ ¿Ø»ú


Regulation mode
× Ô¶¯Í¨ µ À

AVR
Channel A
FCR

× Ô¶¯Í¨ µ À

AVR
Channel B
FCR

Channel C Manual
C ͨ µ À
Operation mode
• The regulator works under master-slave
mode, that means Channel A is running
channel, Channel B and Channel C are
standby channels which are tracing with
Chanel A at all times, and Channel B is
the default one. Once Channel A is fault, it
will switchover to the standby channel
automatically, and if Channel B is fault, it
will switchover to Channel C as well.
Circuit boards

ANB (Analog data board) DIB (Digital data board)

LOU (Local operation unit) IIU (Intelligent I/O unit)


Microcomputer channel
• Various CPUs:
– Main CPU: regulation and logical control
– DSP CPU: digital signal processing
– Chip microcomputer: pulse control
– Chip microcomputer: fault detect
– Chip microcomputer: CAN bus
communication control
COMPACT PCI microcomputer

Channel A Channel B
COMPACT PCI microcomputer

CPU board

I/O board DSP board


Analog channel (manual channel)
• Analog channel is based
on integrated circuits. It
used field current as feed-
back. The set value is
given by a 12-bit accuracy
serial D/A module which is
controlled by a chip
microcomputer. And the
regulation is functioned by
integrated circuits. The
control voltage output is
sent to a pulse module
for phase triggering.
HMI
• Manufacturer: Pro-face
• Model: GP2301
• Color: STN, 16 colors
• Protocol supported: MODBUS
HMI (main)
HMI (screen selection)
HMI (function set)
HMI (failure record)
Synchronize transformer

500VA/450VA/50VA, Y/△/Y, 470V/220V/52V


Power module

T-60B, 60W, 5V/12V/-12V DRP-240-24, 240W, 24V


MEANWELL, Taiwan MEANWELL, Taiwan
Debug software (main interface)
Parameters set

Analog variable Event monitoring


monitoring

State variable
monitoring

Commander list
Debug software (analog variable monitoring)
Debug software (parameter set)
Debug software (special test)
Rectifier cubicle
• Quality thyristors
• Quality cooling fan
• Dynamic current
equalization
• High insulation pulse
transformer
• HMI
• One of the rectifiers can quit
when running
Thyristors
• Manufacturer: ABB
• Model: 5STP 24h2800
• 2625A / 2800V
PCB

Intelligent control board Pulse amplifier board

Pulse transformer board


LCD display
LCD display (main)
LCD display (option)
LCD display(failure record)
De-excitation cubicle
• Quality F.C.B (ABB)
• BOD crowbar
• Quality de-excitation
resistance (ZnO)
• Flashing circuit
• LCD display
F.C.B
• Manufacturer: ABB
• Model: E2N-E 2000A/1000V
• Contact: 4
• Auxiliary contact: 5 NC + 5 NO
F.C.B
De-excitation resistance
• Material: ZnO
• Allowed temperature rise: 130K
De-excitation resistance
PCB

Intelligent control board Transducer board

BOD board
LCD display (main)
LCD display (operation)
HMI (option)
HMI (failure record)
The end