Direct Design Method "DDM"
Direct Design Method "DDM"
METHOD
“DDM”
1
Load Transfer Path For Gravity Loads
3
Simplified Load Transfer
4
Gravity Load Transfer Paths
5
Gravity Load Transfer Paths
6
Stiffness Based Load Sharing
7
Stiffness Based Load Sharing
8
Stiffness Based Load Sharing
B
Slab T = 200 mm
Beam Width, B = 300 mm
Beam Depth, D
a) 300 mm
b) 500 mm
c) 1000 mm 9
Moment Distribution in Beam-Slab
a) H = 300 mm
c) H = 1000 mm b) H = 500 mm 11
Moment Distribution in Beams Only
a) H = 300 mm
c) H = 1000 mm b) H = 500 mm
12
Moment Distribution in Slabs Only
13
The Design Strip Concept
Column Strip
Middle Strip
Design Strip
14
(1) General Description
In reinforced concrete buildings, a basic and common type of
floor is the slab-beam-girder construction. As shown in Fig.1(a),
the shaded slab area is bounded by the two adjacent beams on
the sides and portions of the two girders at the ends.
Fig.1(a)
15
(1) General Description
When the length of this area is two or more times its width, almost
all of the floor load goes to the beams, and very little, except some
near the edge of the girders, goes directly to the girders. Thus the
slab may be designed as a one-way slab, with the main
reinforcement parallel to the girder and the shrinkage and
temperature reinforcement parallel to the beams. The deflected
surface of a oneway slab is primarily one of single curvature.
16
(1) General Description
When the ratio of the long
span L to the short span S as
shown in Fig.1(b) is less than
about 2, the deflected surface
of the shaded area becomes
one of double curvature.
Fig.1(b)
The floor load is carried in both directions to the four supporting
beams around the panel; hence the panel is a two-way slab.
Obviously, when S is equal to L, the four beams around a typical
interior panel should be identical; for other cases the long beams
take more load than the short beams. 17
Behaviour of two way slabs
Equating the center deflections of the short and long strips gives
5w a 4a 5w b 4b
(a )
384EI 384EI
Behaviour of two way slabs
w a 4b
4 b
wb a
From the eq.(b) it is clear that larger share of the load is carried
in the short direction, the ratio of the two portions of the total load
being inversely proportional to the fourth power of the ratio of the
spans.
Behaviour of two way slabs
w a 4b
4 b
wb a
b b
4 w a 256 w b 3 .5 w a 150.06 w b
a a
b b
3 w a 81w b 2 .5 w a 39.06 w b
a a
b
2 w a 16 w b
a
b
1 wa wb
a
Behaviour of two way slabs
Fig.2(a)
23
Fig.2(b)
(1) General Description
Flat slab floors differ from flat plate floors in that flat slab floors
provide adequate shear strength by having either or both of the
following: (a) drop panels (i.e., increased thickness of slab) in the
region of the columns; or (b) column capitals (i.e., tapered
enlargement of the upper ends of columns).
In flat plate floors a uniform slab thickness is used and the shear
strength is obtained by the embedment of multiple-U stirrups or
structural steel devices known as shearhead reinforcement within
the slab of uniform thickness. Relatively speaking, flat slabs are
more suitable for larger panel size or heavier loading than flat
plates. 24
(2) General Design Concept of ACI Code
The basic approach to the design of two-way floor systems
involves imagining that vertical cuts are made through the entire
building along lines midway between the columns. The cutting
creates a series of frames whose width lies between the
centerlines of the two adjacent panels as shown in Fig.3.
Fig.3 25
(2) General Design Concept of ACI Code
The resulting series of rigid frames, taken separately in the
longitudinal and transverse directions of the building, may be
treated for gravity loading floor by floor as would generally be
acceptable for a rigid frame structure consisting of beams and
columns, in accordance with ACI.
A typical rigid frame would consist of (1) the columns above and
below the floor, and (2) the floor system, with or without beams,
bounded laterally between the centerlines of the two panels (one
panel for an exterior line of columns) adjacent to the line of
columns.
26
(2) General Design Concept of ACI Code
Thus the design of a two-way floor system (including two-way
slab, flat slab, and flat plate) is reduced to that of a rigid frame;
hence the name "equivalent frame method.”
29
(2) General Design Concept of ACI Code
Once the longitudinal variation in factored moments and
shears has been obtained, whether by ACI "DDM" or "EFM,"
the moment across the entire width of the floor system being
considered is distributed laterally to the beam, if used, and to
the slab. The lateral distribution procedure and the remainder
of the design is essentially the same whether "DDM" or "EFM"
has been used.
30
(3) Total factored static moment
Consider two typical interior panels ABCD and CDEF in a two-
way floor system, as shown in Fig.4. Let L1 and L2 be the panel
size in the longitudinal and transverse directions, respectively.
Fig.4
Fig.5 31
(3) Total Factored Static Moment
Let lines 1-2 and 3-4 be centerlines of panels ABCD and CDEF,
both parallel to the longitudinal direction. Isolate as a free body
[see Fig.5] the floor slab and the included beam bounded by the
lines 1-2 and 3-4 in the longitudinal direction and the transverse
lines 1’-3’ and 2’-4’ at the faces of the columns in the transverse
direction. The load acting on this free body [see Fig.6] is wuL2 per
unit distance in the longitudinal direction. The total upward force
w uL 2L n
acting on lines 1’-3' or 2'-4' is , where wu is the factored load
2
per unit area and Ln is the clear span in the longitudinal direction
between faces of supports.
32
(3) Total Factored
Static Moment
WuL 2L2n
Mneg Mpos (1)
8 Fig.8 33
(3) Total Factored Static Moment
For a typical exterior panel, the negative moment at the interior
support would be larger than that at the exterior support. The
maximum positive moment would occur at a section to the left of
the mid-span, as shown in Fig.11.
Fig.10
Fig.9
Fig.11
34
(3) Total Factored Static Moment
In practical design, it is customary to use Mpos at midspan for
determining the required positive moment reinforcement.
For this case,
WuL 2L n L n L
Mneg (left ) Mpos Vmidspan n (3 )
2 4 2
35
(3) Total Factored Static Moment
and, by writing the moment equilibrium equation about the right
end of the free body shown in Fig.10,
WuL 2L n L n Ln
Mneg (right ) Mpos Vmidspan ( 4)
2 4 2
36
(3) Total Factored Static Moment
w uL 2L2n
ACI- uses the symbol M0 to mean 8
and calls M0 the total
factored static moment. It states, Absolute sum of positive and
average negative factored moments in each direction shall not be
less than M0"; or
Mneg (left ) Mpos (right ) w uL 2L2n
Mpos M0 in which (5)
2 8
wu = factored load per unit area
Ln = clear span in the direction moments are being determined,
measured face to face' of supports (ACI), but not less than 0.65L1
L1 = span length in the direction moments are being determined,
measured center to center of supports
L2 = transverse span length, measured center to center of
37
supports
(3) Total Factored Static Moment
Equations (1) and (2) are theoretically derived on the basis that
Mneg(left), Mpos, and Mneg(right) occur simultaneously for the same
live load pattern on the adjacent panels of the equivalent rigid
frame defined in Fig.3.
If the live load is relatively heavy compared with dead load, then
different live load patterns should be used to obtain the critical
positive moment at midspan and the critical negative moments at
the supports. In such a case, the "equal" sign in Eqs.(1) and (2)
becomes the "greater" sign. This is the reason why ACI states
"absolute sum . . . shall not be less than Mo" as the design
requirement. 38
(3) Total Factored Static Moment
To avoid the use of excessively small values of Mo in the case of
short spans and large columns or column capitals, the clear span
Ln to be used in Eq.(5) is not to be less than 0.65L1 (ACI).
When the limitations for using the direct design method are met, it
is customary to divide the value of Mo into Mneg into Mpos, if the
restraints at each end of the span are identical (Fig.4 to 8); or into
[Mneg(left) + Mneg(right)]/2 and Mpos if the span end restraints are
different (Fig.9 to 11). Then the moments Mneg(left), Mneg(right),
and Mpos must be distributed transversely along the lines 1‘-3', 2‘-
4', and 5-6, respectively. This last distribution is a function of the
relative flexural stiffness between the slab and the included beam.
39
Total Factored Static Moment in Flat Slabs.
Consider the typical interior panel of a flat slab floor subjected to
a factored load of wu per unit area, as shown in Fig.12. The total
load on the panel area (rectangle minus four quadrantal areas) is
supported by the vertical shears at the four quadrantal arcs. Let
Mneg and Mpos be the total negative and positive moments about a
horizontal axis in the L2 direction along the edges of ABCD and
EF, respectively. Then
Fig.13
Fig.12 41
Total Factored Static Moment in Flat Slabs.
Considering the half-panel ABCDEF as a free body, recognizing
that there is no shear at the edges BC, DE, EF, and FA, and
taking moments about axis 1-1,
L1L 2 c 2 c w uL1L 2 L1 w u c 2 2c
Mneg Mpos w u 0 (7 )
2 8 2 4 8 3
Letting Mo Mneg Mpos
2
2 c 1 2 2c
3
1 4c
Mo w uL 2L11
2
w uL 2L11 (8 )
8 L1 3L 2L1 8 3L1
42
Total Factored Static Moment in Flat Slabs.
ACI states that circular or regular polygon shaped supports shall
be treated as square supports having the same area. For flat
slabs, particularly with column capitals, the clear span Ln
computed from using equivalent square supports should be
compared with that indicated by Eq.(8), which is L1 minus 2c/3. In
some cases, the latter value is larger and should be used,
consistent with the fact that ACI does express its intent in an
inequality.
43
Two way floor system for slab with beams
Figure-1 shows a two-way slab floor with a total area of 12,500 sq ft. It
is divided into 25 panels with a panel size of 25 ft x 20 ft. Concrete
strength is fc 3000 psi and steel yield strength is fy=40,000 psi.
Service live load is to be taken as 138 psf. Story height is 12 ft. The
preliminary sizes are follows: slab thickness is 6.5 in.; long beams are
14 28 in. Overall; short beams are 12 24 in. overall; upper and
lower columns are 15 15 in. The four kinds of panels (corner, long-
sided edge, short-sided edge, and interior) are numbered 1, 2, 3, and 4
in Fig.-1. Determine the total factored static moment in a loaded span
in each of the four equivalent rigid frames whose widths are
designated A, B, C and D in Fig.2. 44
Given data
Fig.-1
45
For two way slab (with beams), the total factored static moment in a
loaded span in each of the four equivalent rigid frame whose widths
are designated A, B, C and D in Fig.2
Fig.-2 109
46
The factored load wu per unit floor area is
wu=1.2wD +1.6wL
=1.2(6.5)(150/12) +1.6(138)
Figure-1 shows a flat slab floor with a total area of 12,500 sq ft. It is
divided into 25 panels with a panel size of 25 ft x 20 ft. Concrete
strength is fc 3000 psi and steel yield strength is fy=40,000 psi. Service
live load is to be taken as 140 psf. Story height is 10 ft. Exterior
columns are 16 in. square and interior columns are 18 in. round. Edge
beams are14 24 in. Overall; Thickness of slab is 7.5 in. outside of
drop panel and 10.5 in. through the drop panel. Sizes of column capital
and drop panels are shown in Fig.-1. Determine the total factored
static moment in a loaded span in each of the four equivalent
rigid frames whose widths are designated A, B, C and D in Fig.2.
48
Fig.-1
49
Neglecting the weight of the drop panel, the service dead load is
(150/12)(7.5)=94 psf; thus
wu=1.2wD +1.6wL
=1.2(9.4) +1.6(140)
=113 + 224
=337 psf
25
2 2
2c
0.337 20 25 2 1
1 1
Mo w uL 2L211 396 ft kips
8 3L1 8 325
(Frame A in long direction)
25
2 2
2c
0.337 10 25 2 1
1 1
Mo w uL 2L211 198 ft kips
8 3L1 8 325
(Frame B in long direction)
50
25
2 2
2c
0.337 25 20 2 1
1 1
Mo w uL 2L211 293 ft kips
8 3L1 8 320
(Frame C in short direction)
25
2 2
2 2c 2
8 0.337 12.5 20 1 320 147 ft kips
1 1
Mo w uL 2L11
8 3L 1
(Frame D in short direction)
The equivalent square area for the column capital has its side
equal to 4.43 ft; then, using Eq.5, with Ln measured to the face of
capital (i.e., equivalent square),
51
w uL 2L2n 0.337 20 25 4.43 356 ft kips
1 1
Mo
2
8 8
(Frame A in long direction)
8 8
(Frame B in long direction)
8 8
(Frame C in short direction)
8 8
(Frame D in short direction)
Insofar as flat slabs with column capitals are concerned, it
appears that the larger values of 396 ft-kips and 293 ft-kips should
be used because Eq.8 is specially suitable; in particular, ACI
states that the total factored static moment shall not be less than
that given by Eq.5. 52
Two way floor system for flat plate slab
Figure-1 shows a flat plate floor with a total area of 4500 sq ft. It is
divided into 25 panels with a panel size of 1512 ft. Concrete
strength is fc 4000 psi and steel yield strength is fy= 50,000 psi.
Service live load is 72 psf. Story height is 9 ft. All columns are
rectangular, 12 in. in the long direction and 10 in. in the short
direction. Preliminary slab thickness is set at 5.5 in. No edge beams
are used along the exterior edges of the floor. Determine the total
factored static moment in a loaded span in each of the four
equivalent rigid frames whose widths are designated A, B, C and D in
Fig.1.
53
Fig.-1
54
The dead load for a 5.5 in slab is
wD=(5.5/12)(150)=69 psf
wu =1.2wD +1.6wL
=1.2(6.9) +1.6(72)
8 8
(Frame A in long direction)
8 8
(Frame B in long direction)
55
Using Eq.5, with clear span Ln measured face-to-face of columns,
8 8
(Frame C in short direction)
1 1
Mo w uL 2L n 0.198 7.5 12 0.83 23.15 ft kips
2 2
8 8
(Frame D in short direction)
56
(4) Ratio of Flexural Stiffnesses of Longitudinal
Beam to Slab
When beams are used along the column lines in a two-way floor
system, an important parameter affecting the design is the relative
size of the beam to the thickness of the slab. This parameter can
best be measured by the ratio αf of the flexural rigidity (called
flexural stiffness by the AC1 Code) EcbIb of the beam to the
flexural rigidity ECSIS, of the slab in the transverse cross-section of
the equivalent frame shown in Fig.14,15&16. The separate moduli
of elasticity Ecb and Ecs, referring to the beam and slab, provide for
different strength concrete (and thus different Ec values) for the
beam and slab. 57
(4) Ratio of Flexural Stiffnesses of Longitudinal
Beam to Slab
Fig.14
Fig.15
Fig.16 58
(4) Ratio of Flexural Stiffnesses of Longitudinal
Beam to Slab
The moments of inertia Ib and Is refer to the gross sections of the
beam and slab within the cross-section of Fig.16. ACI permits the
slab on each side of the beam web to act as a part of the beam,
this slab portion being limited to a distance equal to the projection
of the beam above or below the slab, whichever is greater, but not
greater than four times the slab thickness, as shown in Fig.17.
Fig.17
59
(4) Ratio of Flexural Stiffnesses of Longitudinal Beam to Slab
E cbIb
f (9 )
E csIs
b w h3
Ib k (10)
12
60
(4) Ratio of Flexural Stiffnesses of Longitudinal Beam to Slab
In which
bE t t bE t
2 3
t
1 1 4 6 4 1
bw h h h bw h
k (11)
bE t
1 1
bw h
where
h = overall beam depth
t =overall slab thickness
bE =effective width of flange
bw = width of web
61
Two way floor system for slab with beams
For the two-way slab with beams design problem-1, Compute the ratio
f of the flexural stiffness of the longitudinal beam to that of the slab in
the equivalent rigid frame for all the beams around panels 1, 2, 3, and 4
in Fig.-3.
62
(a) B1-B2, Referring to Fig.3, the effective width bE for B1-B2 is the
smaller of 14 + 2 (21.5) = 57 and 14 + 8 (6.5) =66
thus bE = 57 in. Using Eq.11
Fig.-3 63
Fig.-4
64
bE 57 t 6 .5
4.07, 0.232
b w 14 h 28
1428
3
k 1.774, Ib 1.774 45,400 in.4
12
Is
1
2406.53 5490 in.4 f
EcbIb 45400
8.27
12 EcsIs 5490
65
(b) B3-B4, Referring to Fig.3, the effective width bE for B3-B4 is
the smaller of 14 + 21.5 =35.5 in. and14 + 4 (6.5) = 40; thus
bE = 35.5 in. Using Eq.11
bE 35.5 t 6 .5
2.54, 0.232
bw 14 h 28
1428
3
k 1.484, Ib 1.484 38,000 in.4
12
Is
1
1206.53 2745 in.4 f
EcbIb 38,000
13.83
12 EcsIs 2745
66
(c) B5-B6, Referring to Fig.4, the effective width bE for B5-B6 is the
smaller of 12 + 2 (17.5) = 47 in. and 12 + 8 (6.5) = 64
thus bE = 47 in. Using Eq.11
bE 47 t 6 .5
3.92, 0.271
b w 12 h 24
1224
3
k 1.762, Ib 1.762 24,400 in.4
12
Is
1
3006.53 6870 in.4 f
EcbIb 24,000
3.50
12 EcsIs 6870
67
(d) B7-B8, Referring to Fig.4, the effective width bE for B7-B8 is
the smaller of 12 +17.5 = 29.5 in. and12 + 4 (6.5) = 38; thus
bE = 29.5 in. Using Eq.11
bE 29.5 t 6 .5
2.46, 0.271
bw 12 h 24
1224
3
k 1.480, Ib 1.480 20,500 in.4
12
Using Eq.9, where Ecb=Ecs
Is
1
1506.53 3435 in.4 f
EcbIb 20,500
5.96
12 EcsIs 3435
The resulting f values for B1 to B8 around panels 1, 2, 3 and 4
are shown in Fig.4. For the design, the f values vary between
3.50 and 13.83; thus the equivalent rigid frames have their
substantial portion along or close to the column lines, even
68
though their widths vary from 10 to 25 ft.
Fig.-3 69
(5) Minimum slab thickness for deflection control
70
(5) Minimum slab thickness for deflection control
Slabs without interior beams spanning between supports.
The minimum thickness, with the requirement that the ratio of long
to short span be not greater than 2, shall be that given by Table-1,
but not less than:
In the flat slab and flat plate two-way systems, there may or may
not be edge beams but there are definitely no interior beams in
such systems.
71
Table-1 Minimum thickness of slab without interior beams
Ln Ln Ln Ln Ln Ln
75
28 31 31 31 34 34
73
(5) Minimum slab thickness for deflection control
Slabs Supported on Beams.
Slabs supported on shallow beams where αfm ≤ 0.2.
The minimum slab thickness requirements are the same as for
slabs without interior beams.
Slabs supported on medium stiff beams where 0.2 < αfm < 2.0.
fy
L n 0.8
For this case, Min t 200,000
(12)
36 5( f m 0.2)
75
(6) Nominal requirements for slab thickness and size
of edge beams, column capital, and drop panel
76
(6) Nominal requirements for slab thickness and size
of edge beams, column capital, and drop panel
Slab Thickness. As discussed in Section-5, ACI Formulas
[Eqs.12&13], along with ACI-Table [Table-1] set minimum slab
thickness for two-way floor systems. In addition, ACI set lower
limits for the minimum value based on experience and practical
requirements. These lower limits for two-way slab systems are
summarized:
Flat plates and flat slabs without drop panels 5 in.
Slabs on shallow interior beams having fm < 0.2 5 in.
Slabs without interior beams but having drop panels 4 in.
Slabs with stiff interior beams having fm 2.0 3.5 77in.
(6) Nominal requirements for slab thickness and size
of edge beams, column capital, and drop panel
78
(6) Nominal requirements for slab thickness and size
of edge beams, column capital, and drop panel
Fig.18
For the two-way slab with beams problem-1, Determine the minimum
thickness requirement for deflection control; and compare it with the
preliminary thickness of 6.5 in.
83
Fig.-3 84
The average ratios αfm for panels 1, 2, 3, and 4 may be computed from
the α values shown in Fig.4; thus
1
α fm for panel 1 (5.96 8.27 3.55 13.83) 7.90
4
1
α fm for panel 2 (3.50 8.27 3.50 13.83) 7.29
4
1
α fm for panel 3 (5.96 8.27 3.50 8.27) 6.50
4
1
α fm for panel 4 (3.50 8.27 3.50 8.27) 5.89
4
85
Since the αfm values for all four panels are well above 2, Eq.13
applies. The minimum thickness for all panels, using Ln=24 ft,
Sn=18.83 ft, and fy=40,000 psi, become
0 .2 f y
Ln 0.8
40,000 24121.0
min t 6.07 in.
9Ln 924
36 36
Sn 18.83
86
Two way flat slab floor system
Review the slab thickness and other nominal requirements for the
dimensions in this flat slab design described in problem-1.
87
(a) Stiffness of edge beams.
Before using Table-1, the αf values for the edge beams are
needed. The moment of inertia of the edge beam section
shown in Fig.2 is 22,9000 in4. Thus the αf value for the long
edge beam is
Fig.-2
88
89
Fig.-3
Ib 22,900 22,900
f 5.42
Is 1207.53
4220
12
and for the short edge beam, it is
Ib 22,900 22,900
f 4.34
Is 1507.53
5270
12
Ln 20.57(12)
min t 6.17 in.
40 40
The minimum thickness required is, from part (b), 6.17 in. The 7.5
in. slab thickness used is more than ample; 6.5 in. should
probably have been used.
91
(d) Thickness of drop panel.
In order that the full 3-in. projection of the drop below the 7.5 in.
slab is usable in computing reinforcement, the 6 ft 8 in. side of the
drop is revised to 7 ft so that one-fourth of the distance between
the edges of the 5-ft column capital and the 7-ft drop is just equal
to (10.5 - 7.5) = 3 in.
92
Two way floor system for flat plate slab
Review the slab thickness and other nominal requirements for the
dimensions in the flat plate design example.
93
For fy = 50 ksi, for a flat plate which inherently has f = 0 and
Ln = 15-1=14 ft, from Table-1
For fy=50 ksi, for a flat plate which inherently has αf = 0, and
Ln=15-1=14 ft, from Table-1,
95